Permit Application Status

PRCOM20225949


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20225949
Building Permit - Commercial
Withdrawn
CITY OF LEES SUMMIT
NEW SHELL BUILDING
NEW SHELL FOR FUTURE RESTAURANTS
12/02/2022
07/11/2023
05/09/2024
Locations
Contacts
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
KLOVER ARCHITECTS, Address:10955 LOWELL AVE, Phone:(913) 649-8181  
ARC GENERAL CONTRACTING, Address:7833 BARTON ST, Phone:(913) 492-8008  
tbauer@arcgc.com, Address:tbauer@arcgc.com  
METALCRAFT INC, Address:5138 MERRIAM DR., Phone:(913) 707-8824  
  
KANSAS CITY PLUMBING COMPANY LLC, Address:6320 BROOKSIDE PLAZA STE 285, Phone:(816) 591-4433  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 01/06/2023 06/13/2023
Mike Weisenborn
Building Plan Review Rejected 02/06/2023 02/02/2023
Joe Frogge
Final Development Plan
Resolved
02/13/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 1/12/22 - acknowledged in letter
Engineered truss package
Corrective Action Required
01/30/2023

Copies of the engineered truss package were not provided at the time of permit application. Action required: Comment is informational. Truss package deferred to construction. 1/12/22 - deferred per request
Miscellaneous Correction
Resolved
02/02/2023

Fire partition detail incomplete. Action required: Provide complete UL detail for fire rated wall. Must include, but not be limited to, nail/screw patterns, penetration information, and roof deck connection. (inspector's do not have access to UL information in field) 1/12/22 - Nail/screw patterns must be provided.
Suite address
Corrective Action Required
06/13/2023

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: This building has been assigned the address of 1010 NW Pryor Rd with tenant suites A, B, C, & D with A being the southernmost and D being the northernmost.
Licensed Contractors Rejected 02/06/2023 02/02/2023
Joe Frogge
LC - General Contractor
Resolved
02/13/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 1/12/22 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
01/30/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 1/12/22 - acknowledged in letter 2/13/23 - Phase One Electric not currently licensed with us.
Fire Plan Review Approved with Conditions 02/06/2023 01/30/2023
Ben Hicks
Construction documents for fire alarm systems
Corrective Action Required
01/30/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Submit PE stamped drawings to Lee's Summit Fire Dept for review. Acknowledged in letter.
Construction documents - Fire protection systems
Corrective Action Required
01/30/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Submit PE stamped drawings to Lee's Summit Fire Dept for review Action Required: Submit PE stamped shop drawings to Lee's Summit Fire. Noted deferred submittal in plans. Acknowledged in letter.
Installation acceptance testing
Corrective Action Required
01/30/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Informational, call 816-969-1300 to schedule alarm/ sprinkler/ hood testing. Acknowledged in letter.
Posting of occupant load
Corrective Action Required
01/30/2023

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action Required: Acknowledged in letter, verified at inspection.
Address numbers required
Corrective Action Required
01/30/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Acknowledged in letter, verified at inspection.
Knox box required
Corrective Action Required
01/30/2023

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required: Acknowledged in letter, verified at inspection.
Building Plan Review Rejected 01/19/2023 01/12/2023
Joe Frogge
Final Development Plan
Corrective Action Required
01/11/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 1/12/22 - acknowledged in letter
Engineered truss package
Corrective Action Required
01/11/2023

Copies of the engineered truss package were not provided at the time of permit application. Action required: Comment is informational. Truss package deferred to construction. 1/12/22 - deferred per request
Miscellaneous Correction
Corrective Action Required
01/11/2023

Fire partition detail incomplete. Action required: Provide complete UL detail for fire rated wall. Must include, but not be limited to, nail/screw patterns, penetration information, and roof deck connection. (inspector's do not have access to UL information in field) 1/12/22 - Nail/screw patterns must be provided.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Resolved
01/12/2023

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25' of roof mounted hvac. (Mech schedule specifies unpowered receptacles)
NEC Article 230.72 Grouping of disconnects
Resolved
01/12/2023

2017 NEC 230.72 Grouping of disconnects. (A) General. The two to six disconnects as permitted in 230.71 shall be grouped. Each disconnect shall be marked to indicate the load served. (see code for exception) Action required: provide clearly marked means of disconnecting entire power supply to building or group disconnects next to each other.
Licensed Contractors Rejected 01/19/2023 01/12/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
01/11/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 1/12/22 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
01/11/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 1/12/22 - acknowledged in letter
Fire Plan Review Approved with Conditions 01/19/2023 01/12/2023
Ben Hicks
Construction documents for fire alarm systems
Corrective Action Required
01/11/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Submit PE stamped drawings to Lee's Summit Fire Dept for review. Acknowledged in letter.
Type I hood - Where required
Resolved
01/12/2023

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action Required: Any cooking appliences producing grease laden vapors requires hood
Construction documents - Fire protection systems
Corrective Action Required
01/11/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Submit PE stamped drawings to Lee's Summit Fire Dept for review Action Required: Submit PE stamped shop drawings to Lee's Summit Fire. Noted deferred submittal in plans. Acknowledged in letter.
Installation acceptance testing
Corrective Action Required
01/11/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Informational, call 816-969-1300 to schedule alarm/ sprinkler/ hood testing. Acknowledged in letter.
Posting of occupant load
Corrective Action Required
01/11/2023

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action Required: Acknowledged in letter, verified at inspection.
Address numbers required
Corrective Action Required
01/11/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Acknowledged in letter, verified at inspection.
Knox box required
Corrective Action Required
01/11/2023

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required: Acknowledged in letter, verified at inspection.
Portable fire extinguishers for commercial cooking equipment.
Resolved
01/12/2023

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action Required: Class K required for kitchen
Portable fire extinguishers - general
Resolved
01/12/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Show locations of extinguishers
Duct smoke detectors
Resolved
01/12/2023

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action Required: CFM of RTU's requires duct detection
Illumination required
Resolved
01/12/2023

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action Required: Show locations of emerg. interior lights, exit lights, exterior emerg. means of egress lights
Emergency power for illumination
Resolved
01/12/2023

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action Required: Show all emerg. lighting and exits
Fire Plan Review Rejected 12/16/2022 12/16/2022
Ben Hicks
Construction documents for fire alarm systems
Corrective Action Required
12/15/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Submit PE stamped drawings to Lee's Summit Fire Dept for review
Type I hood - Where required
Corrective Action Required
12/15/2022

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action Required: Any cooking appliences producing grease laden vapors requires hood
Construction documents - Fire protection systems
Corrective Action Required
12/15/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Submit PE stamped drawings to Lee's Summit Fire Dept for review Action Required: Submit PE stamped shop drawings to Lee's Summit Fire. Noted deferred submittal in plans
Installation acceptance testing
Corrective Action Required
12/15/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Informational, call 816-969-1300 to schedule alarm/ sprinkler/ hood testing
Posting of occupant load
Corrective Action Required
12/16/2022

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action Required: Verified at inspection
Address numbers required
Corrective Action Required
12/16/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Verified at inspection
Knox box required
Corrective Action Required
12/16/2022

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required: Knox box placed above FDC
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
12/16/2022

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action Required: Class K required for kitchen
Portable fire extinguishers - general
Corrective Action Required
12/16/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Show locations of extinguishers
Duct smoke detectors
Corrective Action Required
12/16/2022

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action Required: CFM of RTU's requires duct detection
Illumination required
Corrective Action Required
12/16/2022

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action Required: Show locations of emerg. interior lights, exit lights, exterior emerg. means of egress lights
Emergency power for illumination
Corrective Action Required
12/16/2022

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action Required: Show all emerg. lighting and exits
Building Plan Review Rejected 12/16/2022 12/13/2022
Joe Frogge
Final Development Plan
Corrective Action Required
12/13/2022

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
Engineered truss package
Corrective Action Required
12/13/2022

Copies of the engineered truss package were not provided at the time of permit application. Action required: Comment is informational. Truss package deferred to construction.
Miscellaneous Correction
Corrective Action Required
12/13/2022

Fire partition detail incomplete. Action required: Provide complete UL detail for fire rated wall. Must include, but not be limited to, nail/screw patterns, penetration information, and roof deck connection. (inspector's do not have access to UL information in field)
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
12/13/2022

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25' of roof mounted hvac. (Mech schedule specifies unpowered receptacles)
NEC Article 230.72 Grouping of disconnects
Corrective Action Required
12/13/2022

2017 NEC 230.72 Grouping of disconnects. (A) General. The two to six disconnects as permitted in 230.71 shall be grouped. Each disconnect shall be marked to indicate the load served. (see code for exception) Action required: provide clearly marked means of disconnecting entire power supply to building or group disconnects next to each other.
Licensed Contractors Rejected 12/16/2022 12/13/2022
Joe Frogge
LC - General Contractor
Corrective Action Required
12/13/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
12/13/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
12/02/2022 Application Form Commercial Permit Application
12/09/2022 Plans Lot 12 - West Pryor - Permit Set
12/16/2022 Letter Fire Building Plan Review
12/19/2022 Letter DS P/R Corrections Document
01/11/2023 Letter City Response - Lot 12 - SOWP - 01_11_23
01/11/2023 Plans Lot 12 - SOWP - ADD1 and City Comment Sheets - 01_11_23
01/12/2023 Letter Fire Building Plan Review
01/12/2023 Letter DS P/R Corrections Document
01/30/2023 Plans LOT 12 - SOWP - ADD2 SHEETS
01/30/2023 Letter Lot 12 - SOWP - Project Narrative - 01_27_23 - ADD 2
01/30/2023 Letter Fire Building Plan Review
02/13/2023 Letter Applicant Letter - FDP (DFDP)
02/13/2023 Plans LOT 12 - SOWP - ADD2 SET
02/13/2023 Letter SOWP - LOT 12 - GC AND CONTACTS
03/27/2023 Approved Plans Approved 1.18.23 SWP Lot 12 FDP
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home