Permit Application Status

PRCOM20220884


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20220884
Building Permit - Commercial
Certificate of Occupancy
TI SUMMIT CREST PLAZA LLC
CHANGE OF TENANT
TENANT FINISH FOR GYM
03/10/2022
05/05/2022
09/19/2022
09/28/2022
Locations
Contacts
EVARDY CONSTRUCTION LLC, Address:7111 W 151ST ST STE 375, Phone:(816) 729-5780  
TS@EvardyConstruction.com, Address:TS@EvardyConstruction.com, Phone:(573) 783-9450  
CHIEF HEATING & COOLING INC, Address:920 NW TECHNOLOGY DR, Phone:(816) 246-4646  
GARWIN ELECTRIC LLC, Address:27065 W 102, Phone:(913) 780-1200  
PRO DESIGN CONTRACTORS LLC, Address:918 E WARREN ST, Phone:(913) 308-6900  
TRILEAF ARCHITECTURE & ENGINEERING, Address:1515 Des Peres Road, Ste. 200, Phone:(314) 997-6111  
TI SUMMIT CREST PLAZA LLC, Address:7611 STATE LINE RD STE 301  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/22/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
07/22/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. As built plans received July 22, 2022.
Installation acceptance testing
Corrective Action Required
07/22/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at the occupancy inspection.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/22/2022

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have documentation of a current annual inspection. Verified at inspection.
Alarm Plan Review Released for Construction 06/29/2022 06/29/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
06/29/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Received 6/29/2022.
Alarm testing.
Corrective Action Required
06/29/2022

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Call (816) 969-1300 to schedule an alarm, preferably outside of other store business hours.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/29/2022

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing panel shall have documentation of an annual insprction. Verified at inspection.
Fire Plan Review Approved 05/06/2022 05/04/2022
Jim Eden
Posting of occupant load
Resolved
05/04/2022

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Construction documents for fire alarm systems
Informational
05/04/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Provide plans for review and approval for adding or adjusting the location of alarm notification appliances.
Address numbers required
Resolved
05/04/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required- Correct and post the address on the remaining doors. Verified at inspection.
Construction documents - Fire protection systems
Informational
05/04/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for review and approval for work needed to maintain adequate sprinkler coverage.
Duct smoke detectors
Resolved
05/04/2022

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required- If provided (shown on plans) provide remote test/reset switches and connect to existing building alarm.
Panic and fire exit hardware
Resolved
05/04/2022

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. Verified at inspection.
Miscellaneous Correction
Resolved
05/04/2022

Exterior doors that are blocked and no longer usable from the interior but still have the appearnce from the exterior as a usable door shall be posted on the exterior "NOT AN EXIT, THIS DOOR BLOCKED". Verified at inspection.
Building Plan Review Approved 05/06/2022 05/02/2022
Joe Frogge
IBC 602.1 Type of Construction - general
Resolved
05/02/2022

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Change Code Data - Building Design Information to reflect correct building type which is 5B.
IBC 1606.2 Design dead load - structural
Resolved
05/02/2022

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new ceiling mounted equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load.
Licensed Contractors Approved 04/29/2022 04/29/2022
Joe Frogge
Fire Plan Review Rejected 03/22/2022 03/22/2022
Jim Eden
Posting of occupant load
Corrective Action Required
03/22/2022

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Construction documents for fire alarm systems
Corrective Action Required
03/22/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Provide plans for review and approval for adding or adjusting the location of alarm notification appliances.
Address numbers required
Corrective Action Required
03/22/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required- Correct and post the address on the remaining doors. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
03/22/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for review and approval for work needed to maintain adequate sprinkler coverage.
Duct smoke detectors
Corrective Action Required
03/22/2022

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required- If provided (shown on plans) provide remote test/reset switches and connect to existing building alarm.
Panic and fire exit hardware
Corrective Action Required
03/22/2022

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
03/22/2022

Exterior doors that are blocked and no longer usable from the interior but still have the appearnce from the exterior as a usable door shall be posted on the exterior "NOT AN EXIT, THIS DOOR BLOCKED". Verified at inspection.
Building Plan Review Rejected 03/22/2022 03/16/2022
Joe Frogge
IBC 602.1 Type of Construction - general
Corrective Action Required
03/16/2022

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Change Code Data - Building Design Information to reflect correct building type which is 5B.
IBC 1606.2 Design dead load - structural
Corrective Action Required
03/16/2022

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new ceiling mounted equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load.
Licensed Contractors Approved 03/10/2022 03/10/2022
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $862.13 $862.13 Paid 05/05/2022
7232302-Commercial License Tax Fee $13,972.50 $13,972.50 Paid 03/16/2022
$13,972.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Plumbing Inspection - Commercial Passed 5/6/2022 5/6/2022 05/06/2022
In-wall Inspection Partial 5/27/2022 05/27/2022
Misc
Corrective Action Required
05/27/2022
AREAS APPROVED: 5/27/22 - 114,113,115,112,109,111,110,104,103,102
Above Ceiling Inspection Partial 6/2/2022 6/2/2022 06/02/2022
Misc
Corrective Action Required
06/02/2022
AREAS APPROVED: - 6/2/22 HARD LID 114, 113, 111, 112
Above Ceiling Inspection Partial 6/29/2022 6/29/2022 06/29/2022
Misc
Corrective Action Required
06/02/2022
AREAS APPROVED: - 6/2/22 HARD LID 114, 113, 111, 112 - 6/29/22 109,110,103,102
Alarm Test Passed 7/19/2022 07/22/2022
Sprinkler - Flow Test Passed 07/22/2022
In-wall Inspection Passed 7/22/2022 07/22/2022
Misc
Corrective Action Required
05/27/2022
AREAS APPROVED: 5/27/22 - 114,113,115,112,109,111,110,104,103,102
Above Ceiling Inspection Passed 7/22/2022 07/22/2022
Misc
Corrective Action Required
06/29/2022
AREAS APPROVED: - 6/2/22 HARD LID 114, 113, 111, 112 - 6/29/22 109,110,103,102
Occupancy Inspection - Codes Commercial Temporary C of O 7/22/2022 7/22/2022 07/22/2022
Misc
Corrective Action Required
07/22/2022
-PROVIDE HAMMER ARRESTORS AT LAUNDRY - ANTI SIPHON AT MOP SINK SPIGOT SEE FIRE DEPT REPORT FOR FIRE CORRECTIONS **OK FOR TCO**
Occupancy Inspection - Fire Temporary C of O 7/22/2022 7/22/2022 07/22/2022
Occupancy Inspection - Codes Commercial Full C of O 9/28/2022 9/28/2022 09/28/2022
Misc
Resolved
09/28/2022
Documents & Images
Date Uploaded File Type Document Name
03/10/2022 Application Form AnyTime Fitness_Commercial Permit Application (original)
03/10/2022 Plans 689411_Lee's Summit MO_Anytime Fitness_Permit Set_01_14_22
03/16/2022 Letter License Tax Bill
03/23/2022 Letter DS P/R Corrections Document
04/29/2022 Letter 00_Rev 2 Narrative
04/29/2022 Plans 689411_Lee's Summit MO_Anytime Fitness_Revision 2_04_27_22
04/29/2022 Letter 00_Rev 01 Response Letter
05/05/2022 Approved Plans approved - 689411_Lee's Summit MO_Anytime Fitness_Revision 2_04_27_22
05/05/2022 Receipt Receipt for transaction:2022-002926
05/05/2022 Letter DS Building Permit
05/06/2022 Letter INSPECTION SUMMARY
05/10/2022 Letter Fire Building Plan Review
05/27/2022 Letter INSPECTION SUMMARY
06/02/2022 Letter INSPECTION SUMMARY
06/29/2022 Plans ANYTIME FITNESS LEES SUMMIT FA-Layout1
06/29/2022 Letter Fire (Alarm) Plan Review Notice
06/29/2022 Letter INSPECTION SUMMARY
07/22/2022 Anytime Fitness FS
07/22/2022 Letter INSPECTION SUMMARY
07/22/2022 Letter INSPECTION SUMMARY
07/22/2022 Letter Fire (Sprinkler) Plan Review
07/22/2022 Letter Codes Temporary Certificate of Occupancy
08/02/2022 Letter Fire Loss Reduction Form
09/28/2022 Letter Field Certificate of Occupancy
09/28/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home