Permit Application Status

PRCOM20216110


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20216110
Building Permit - Commercial
Certificate of Occupancy
TI SUMMIT CREST PLAZA LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR NEW RESTAURANT
11/24/2021
02/18/2022
08/15/2022
11/16/2022
Locations
Contacts
STEPHEN MASLAN & COMPANY, Address:8011 PASEO, Phone:(816) 444-6260  
smaslan1950@gmail.com, Address:smaslan1950@gmail.com  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
GALLOWAY'S ELECTRIC, Address:218 N PARK DR, Phone:(816) 835-1777  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
INNOVATIVE DESIGN & RENOVATION, Address:8011 PASEO #201, Phone:(816) 531-2221  
TI SUMMIT CREST PLAZA LLC, Address:7611 STATE LINE RD STE 301  
ALL ACTION CONTRACTORS, Address:303 NW CENTRAL ST, Phone:(816) 985-4068  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 11/01/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
11/01/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Received Oct. 24, 2022
Installation acceptance testing
Corrective Action Required
11/01/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Coordinated alarm testing with the hood system test. Call (816) 969-1300 to schedule a test.
Fire Plan Review Approved with Conditions 02/24/2022 10/13/2022
Jim Eden
Construction documents for fire alarm systems
Informational
10/13/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Submit plans for modification to the fire alarm system for review and approval.
Construction documents - Fire protection systems
Partial Correction
10/13/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Submit plans for review and approval for modifications to the sprinkler and for the hood system. Hood system plans submitted Oct 12, 2022. Released for construction with the following conditions: 1. The hood exhaust system shall come on automatically if the suppression system is activated when the hood is off. 2. The pull station shall be located near the means of egress and no closer than 10 feet to the hood and no farther than 20 feet. 3. Call (816) 969-1300 to schedule testing.
Miscellaneous Correction
Corrective Action Required
10/13/2022

IFC 904.12.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area not less than 10 feet (3048 mm) and not more than 20 feet (6096 mm) from the kitchen exhaust system... Action required- Move the manual pull and K-class fire extinguisher away from the hood to meet this requirement. 2/17/2022 Per S. Maslan, the contractor will provide drawings for the hood fire suppression system.
Licensed Contractors Approved 02/24/2022 02/18/2022
Joe Frogge
Building Plan Review Approved with Conditions 02/24/2022 02/18/2022
Joe Frogge
Health Dept Inspection
Corrective Action Required
02/16/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/15/21 - Not addressed. 1/18/21 - Acknowledged in letter.
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
02/16/2022

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Specify installation of metal studs in wall behind and 18" adjacent to Type I hood. (or provide verification that the existing construction is non-combustible) 1/18/21 - Acknowledged in letter. 12/15/21 - response letter says existing studs are metal - field verify
IMC 602.2.1 Materials within plenums
Corrective Action Required
02/16/2022

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC piping is specified for DWV but mechanical design is not clear as to whether this is a plenum or hard ducted return. Clarify. 1/18/21 - Acknowledged in letter. 12/15/21 - Return is ducted per architect - field verify
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
02/16/2022

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) near new roof mounted equipment to comply. (or provide verification of existing) 12/15/21 - response refers to note on mechanical plans. unable to find note. 1/18/21 - Acknowledged in letter. Still unable to find note. To be field verified.
Fire Plan Review Approved with Conditions 02/24/2022 02/17/2022
Jim Eden
Construction documents for fire alarm systems
Informational
02/16/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Submit plans for modification to the fire alarm system for review and approval.
Construction documents - Fire protection systems
Corrective Action Required
02/16/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Submit plans for review and approval for modifications to the sprinkler and for the hood system.
Miscellaneous Correction
Corrective Action Required
02/16/2022

IFC 904.12.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area not less than 10 feet (3048 mm) and not more than 20 feet (6096 mm) from the kitchen exhaust system... Action required- Move the manual pull and K-class fire extinguisher away from the hood to meet this requirement. 2/17/2022 Per S. Maslan, the contractor will provide drawings for the hood fire suppression system.
Licensed Contractors Approved 02/04/2022 02/14/2022
Joe Frogge
LC - MEP Subs
Resolved
02/14/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 12/15/21 - Not addressed. 1/18/21 - Acknowledged in letter.
Building Plan Review Approved with Conditions 02/04/2022 01/31/2022
Joe Frogge
Health Dept Inspection
Corrective Action Required
01/28/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/15/21 - Not addressed. 1/18/21 - Acknowledged in letter.
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
01/28/2022

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Specify installation of metal studs in wall behind and 18" adjacent to Type I hood. (or provide verification that the existing construction is non-combustible) 1/18/21 - Acknowledged in letter. 12/15/21 - response letter says existing studs are metal - field verify
IMC 602.2.1 Materials within plenums
Corrective Action Required
01/28/2022

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC piping is specified for DWV but mechanical design is not clear as to whether this is a plenum or hard ducted return. Clarify. 1/18/21 - Acknowledged in letter. 12/15/21 - Return is ducted per architect - field verify
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
01/28/2022

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) near new roof mounted equipment to comply. (or provide verification of existing) 12/15/21 - response refers to note on mechanical plans. unable to find note. 1/18/21 - Acknowledged in letter. Still unable to find note. To be field verified.
Fire Plan Review Rejected 02/04/2022 01/28/2022
Jim Eden
Construction documents for fire alarm systems
Informational
01/28/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Submit plans for modification to the fire alarm system for review and approval.
Construction documents - Fire protection systems
Corrective Action Required
01/28/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Submit plans for review and approval for modifications to the sprinkler and for the hood system.
Miscellaneous Correction
Corrective Action Required
01/28/2022

IFC 904.12.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area not less than 10 feet (3048 mm) and not more than 20 feet (6096 mm) from the kitchen exhaust system... Action required- Move the manual pull and K-class fire extinguisher away from the hood to meet this requirement.
Health Department Review Approved 01/28/2022
Joe Frogge
Fire Plan Review Rejected 01/24/2022 01/20/2022
Jim Eden
Posting of occupant load
Informational
01/20/2022

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage at 29.
Construction documents for fire alarm systems
Informational
01/20/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net Note: Type 1 hood to be tied to the alarm system.
Construction documents - Fire protection systems
Informational
01/20/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Informational
01/20/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hood trip and alarm test.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
01/14/2022

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Action Required) Provide 1 K-Class extinguisher. Placement to be made by the manual pull. 12/14/2021 (Verified At Inspection)
Miscellaneous Correction
Informational
01/20/2022

(Action Required) 2018 IFC 5307.3 Insulated liquid carbon dioxide systems with more than 100 pounds of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide specs and placement of tank. Gas detection may be required. 12 /14/2021 Installer to provide specs and placement. Also to determine if gas detection is needed.
Misc
Corrective Action Required
01/20/2022

904.12.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area not less than 10 feet (3048 mm) and not more than 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. Action required- Relocate the manual pull and K class extinguisher to meet this requirement.
Licensed Contractors Rejected 01/24/2022 01/18/2022
Joe Frogge
LC - MEP Subs
Corrective Action Required
01/14/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 12/15/21 - Not addressed. 1/18/21 - Acknowledged in letter.
Building Plan Review Rejected 01/24/2022 01/18/2022
Joe Frogge
Health Dept Review
Resolved
01/28/2022

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/15/21 - Not addressed. 1/18/21 - Noted in response form as approved but we have yet to receive notification from Jackson County.
Health Dept Inspection
Corrective Action Required
01/14/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/15/21 - Not addressed. 1/18/21 - Acknowledged in letter.
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
01/14/2022

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Specify installation of metal studs in wall behind and 18" adjacent to Type I hood. (or provide verification that the existing construction is non-combustible) 1/18/21 - Acknowledged in letter. 12/15/21 - response letter says existing studs are metal - field verify
IMC 602.2.1 Materials within plenums
Corrective Action Required
01/14/2022

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC piping is specified for DWV but mechanical design is not clear as to whether this is a plenum or hard ducted return. Clarify. 1/18/21 - Acknowledged in letter. 12/15/21 - Return is ducted per architect - field verify
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
01/14/2022

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) near new roof mounted equipment to comply. (or provide verification of existing) 12/15/21 - response refers to note on mechanical plans. unable to find note. 1/18/21 - Acknowledged in letter. Still unable to find note. To be field verified.
Building Plan Review Rejected 12/21/2021 12/15/2021
Joe Frogge
Health Dept Review
Corrective Action Required
12/14/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/15/21 - Not addressed.
Health Dept Inspection
Corrective Action Required
12/14/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 12/15/21 - Not addressed.
ICC A117.1 404.2.5 Two Doors or gates in series
Resolved
12/15/2021

ICC A117.1 404.2.5 - Two doors or gates in series. Distance between two hinged or pivoted doors or gates in series shall be 48 inches minimum plus the width of any door or gate swinging into the space. The space between the doors and gates shall provide a turning space. Action required: Provide compliant turning space in vestibule. (or remove vestibule which we do not require)
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
12/15/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 54" clearance at approach to entry vestile. re: figure 404.2.3.2 (f)
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
12/15/2021

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Specify installation of metal studs in wall behind and 18" adjacent to Type I hood. (or provide verification that the existing construction is non-combustible) 12/15/21 - response letter says existing studs are metal - field verify
IMC 602.2.1 Materials within plenums
Corrective Action Required
12/14/2021

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC piping is specified for DWV but mechanical design is not clear as to whether this is a plenum or hard ducted return. Clarify. 12/15/21 - Return is ducted per architect - field verify
IBC 1606.2 Design dead load - structural
Resolved
12/17/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report or design to verify that existing roof structure will support additional load imposed by new equipment.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
12/14/2021

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) near new roof mounted equipment to comply. (or provide verification of existing) 12/15/21 - response refers to note on mechanical plans. unable to find note.
Licensed Contractors Rejected 12/21/2021 12/15/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
12/14/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 12/15/21 - Not addressed.
Fire Plan Review Approved with Conditions 12/21/2021 12/14/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
12/14/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage at 29.
Construction documents for fire alarm systems
Corrective Action Required
12/14/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net Note: Type 1 hood to be tied to the alarm system.
Construction documents - Fire protection systems
Corrective Action Required
12/14/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
12/14/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hood trip and alarm test.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
12/14/2021

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Action Required) Provide 1 K-Class extinguisher. Placement to be made by the manual pull. 12/14/2021 (Verified At Inspection)
Miscellaneous Correction
Corrective Action Required
12/14/2021

(Action Required) 2018 IFC 5307.3 Insulated liquid carbon dioxide systems with more than 100 pounds of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide specs and placement of tank. Gas detection may be required. 12 /14/2021 Installer to provide specs and placement. Also to determine if gas detection is needed.
Misc
Resolved
12/14/2021

(Informational Purposes) A Knox Box is not required for the space.
Building Plan Review Rejected 12/08/2021 12/06/2021
Joe Frogge
Health Dept Review
Corrective Action Required
12/06/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
12/06/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
ICC A117.1 404.2.5 Two Doors or gates in series
Corrective Action Required
12/06/2021

ICC A117.1 404.2.5 - Two doors or gates in series. Distance between two hinged or pivoted doors or gates in series shall be 48 inches minimum plus the width of any door or gate swinging into the space. The space between the doors and gates shall provide a turning space. Action required: Provide compliant turning space in vestibule. (or remove vestibule which we do not require)
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
12/06/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 54" clearance at approach to entry vestile. re: figure 404.2.3.2 (f)
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
12/06/2021

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Specify installation of metal studs in wall behind and 18" adjacent to Type I hood. (or provide verification that the existing construction is non-combustible)
IMC 602.2.1 Materials within plenums
Corrective Action Required
12/06/2021

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC piping is specified for DWV but mechanical design is not clear as to whether this is a plenum or hard ducted return. Clarify.
IBC 1606.2 Design dead load - structural
Corrective Action Required
12/06/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report or design to verify that existing roof structure will support additional load imposed by new equipment.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
12/06/2021

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) near new roof mounted equipment to comply. (or provide verification of existing)
Licensed Contractors Rejected 12/06/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
12/06/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 12/08/2021 11/29/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
11/29/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage at 29.
Construction documents for fire alarm systems
Corrective Action Required
11/29/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net Note: Type 1 hood to be tied to the alarm system.
Construction documents - Fire protection systems
Corrective Action Required
11/29/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
11/29/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hood trip and alarm test.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
11/29/2021

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Action Required) Provide 1 K-Class extinguisher. Placement to be made by the manual pull.
Miscellaneous Correction
Corrective Action Required
11/29/2021

(Action Required) 2018 IFC 5307.3 Insulated liquid carbon dioxide systems with more than 100 pounds of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide specs and placement of tank. Gas detection may be required.
Misc
Corrective Action Required
11/29/2021

(Informational Purposes) A Knox Box is not required for the space.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $200.00 $200.00 Paid 02/18/2022
8331507-Sewer Connection Fee $330.00 $330.00 Paid 02/18/2022
7232302-Commercial License Tax Fee $5,977.50 $5,977.50 Paid 02/18/2022
$2,692.50
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 11/16/2022
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 11/16/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 2/25/2022 2/25/2022 02/25/2022
Misc
Corrective Action Required
02/25/2022
2/25/22 - PARTIAL INSPECTION ON UNDERSLAB AT REAR NORTH LINE TO TENANT EXIT THROUGH COOLER AT TURN EAST TO FIRST WYE CONNECTION ONLY
Underslab Plumbing Inspection - Commercial Not Ready 3/3/2022 3/3/2022 03/03/2022
Misc
Corrective Action Required
02/25/2022
2/25/22 - PARTIAL INSPECTION ON UNDERSLAB AT REAR NORTH LINE TO TENANT EXIT THROUGH COOLER AT TURN EAST TO FIRST WYE CONNECTION ONLY - 3/2/22 NO NEW UNDERSLAB PLUMBING TO INSPECT -
Underslab Plumbing Inspection - Commercial Passed 3/24/2022 3/24/2022 03/24/2022
Misc
Resolved
03/24/2022
2/25/22 - PARTIAL INSPECTION ON UNDERSLAB AT REAR NORTH LINE TO TENANT EXIT THROUGH COOLER AT TURN EAST TO FIRST WYE CONNECTION ONLY - 3/2/22 NO NEW UNDERSLAB PLUMBING TO INSPECT -
Hood/Duct Inspection Partial 6/13/2022 06/13/2022
Misc
Corrective Action Required
06/13/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION
Hood/Duct Inspection Partial 6/14/2022 6/14/2022 06/14/2022
Misc
Corrective Action Required
06/13/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION 6/14/22 - 1ST LAYER WRAP
In-wall Inspection Failed 6/14/2022 6/14/2022 06/14/2022
Misc
Corrective Action Required
06/14/2022
PROVIDE BOCCA PROTECTION PLATES ALL TOP AND BOTTOM PLATE DWV, NAIL PROTECTION PLATES AT DWV STUD PENETRATIONS, SECURE ALL MC
Hood/Duct Inspection Partial 6/15/2022 6/15/2022 06/15/2022
Misc
Corrective Action Required
06/14/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION 6/14/22 - 1ST LAYER WRAP 6/15/22 - 2ND LAYER WRAP
In-wall Inspection Partial 6/15/2022 6/15/2022 06/15/2022
Misc
Corrective Action Required
06/14/2022
6/15/22 - IN WALL BATH 103,104, DINING 101 OK TO COVER
Hood/Duct Inspection Partial 6/16/2022 6/16/2022 06/16/2022
Misc
Corrective Action Required
06/15/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION 6/14/22 - 1ST LAYER WRAP 6/15/22 - 2ND LAYER WRAP 6/16/22 - LIGHT TEST AT EXTENSIONS
Hood/Duct Inspection Partial 6/20/2022 6/17/2022 06/17/2022
Misc
Corrective Action Required
06/16/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION 6/14/22 - 1ST LAYER WRAP 6/15/22 - 2ND LAYER WRAP 6/16/22 - LIGHT TEST AT EXTENSIONS 6/17/22 - LIGHT TEST AT HOOD TO DUCT, 1ST LAYER WRAP ON EXTENSIONS
Hood/Duct Inspection Failed 6/20/2022 6/20/2022 06/20/2022
Misc
Corrective Action Required
06/17/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION 6/14/22 - 1ST LAYER WRAP 6/15/22 - 2ND LAYER WRAP 6/16/22 - LIGHT TEST AT EXTENSIONS 6/17/22 - LIGHT TEST AT HOOD TO DUCT, 1ST LAYER WRAP ON EXTENSIONS ** 6/20/22 NO INSPECTION PERFORMED, DOOR LOCKED NO ACCESS
Hood/Duct Inspection Partial 6/22/2022 6/22/2022 06/22/2022
Misc
Corrective Action Required
06/20/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION 6/14/22 - 1ST LAYER WRAP 6/15/22 - 2ND LAYER WRAP 6/16/22 - LIGHT TEST AT EXTENSIONS 6/17/22 - LIGHT TEST AT HOOD TO DUCT, 1ST LAYER WRAP ON EXTENSIONS 6/22/22 - 2ND LAYER WRAP, FRESH AIR DUCTS
Gas Service Inspection - Commercial Passed 9/9/2022 09/09/2022
Electrical Service Inspection Passed 9/9/2022 09/09/2022
Hood/Duct Inspection Passed 9/9/2022 9/9/2022 09/09/2022
Misc
Resolved
09/09/2022
6/13/22 - LIGHT TEST PARTIAL HOOD INSPECTION 6/14/22 - 1ST LAYER WRAP 6/15/22 - 2ND LAYER WRAP 6/16/22 - LIGHT TEST AT EXTENSIONS 6/17/22 - LIGHT TEST AT HOOD TO DUCT, 1ST LAYER WRAP ON EXTENSIONS 6/22/22 - 2ND LAYER WRAP, FRESH AIR DUCTS
Above Ceiling Inspection Failed 9/9/2022 9/9/2022 09/09/2022
Misc
Corrective Action Required
09/09/2022
9/9/22 - SECURE ALL MC OFF CEILING GRID, COMPLETE CEILING GRID, SUPPORT PEX WATER LINES OFF GRID, DEMO UNUSED WILD MC OR LAND TO BOX
Gas Piping Inspection - Commercial Passed 9/14/2022 9/14/2022 09/14/2022
Above Ceiling Inspection Passed 9/14/2022 9/14/2022 09/14/2022
Misc
Resolved
09/14/2022
Alternate Protection Systems Inspection Not Ready 11/9/2022 11/09/2022
Alarm Test Passed 11/14/2022 11/14/2022
Alternate Protection Systems Inspection Passed 11/14/2022 11/14/2022
In-wall Inspection Passed 11/14/2022
Misc
Resolved
11/14/2022
6/15/22 - IN WALL BATH 103,104, DINING 101 OK TO COVER
Occupancy Inspection - Codes Commercial Failed 11/15/2022 11/15/2022 11/15/2022
Misc
Corrective Action Required
11/15/2022
-PROVIDE PLUMBING PROTECTION AT BATHROOMS -PROVIDE ADA COMPLIANT BATHROOM SIGNS -GFCI PROTECTION ALL KITCHEN OUTLETS -ANTI SIPHON DEVICE AT MOP SINK SPIGOT -SECURE MC AT SERVICE PANEL MECH ROOM -PROVIDE DOCUMENTATION ON BACKFLOW CERT AT SOFT DRINK FOUNTAIN, DEVICE ASTM 1022 COMPLIANT
Occupancy Inspection - Codes Commercial Full C of O 11/16/2022 11/16/2022
Misc
Resolved
11/16/2022
Documents & Images
Date Uploaded File Type Document Name
11/24/2021 Application Form Commercial Permit Application (TOKYO GRILLE)
11/24/2021 Plans Toyko grille Sealed 11-24-21-2
11/29/2021 Letter Fire Building Plan Review
12/06/2021 Letter DS P/R Corrections Document
12/14/2021 Letter DS P_R Corrections Document tokyo grille-1
12/14/2021 Plans Tokyo grille Sealed 12-14-21
12/14/2021 Letter Fire Building Plan Review
12/15/2021 Letter License Tax Bill
12/15/2021 Letter DS P/R Corrections Document
01/13/2022 Engineer Report/Study tokyo grille engineering letter for roof top support-sealed
01/13/2022 Plans Tokyo grille Sealed 12-20-21
01/13/2022 Letter tokyo grille response letter
01/20/2022 Letter Fire Building Plan Review
01/24/2022 Letter DS P/R Corrections Document
01/28/2022 Email New Food Establishment Plan Review - Approved FTG_0001288
01/28/2022 Letter Response to Corrections for Tokyo Grille1
01/28/2022 Plans Tokyo grille Sealed 1-28-22-1
01/28/2022 Letter Fire Building Plan Review
01/31/2022 Approved Plans approved - Tokyo grille Sealed 1-28-22-2
02/16/2022 Letter code response to comments made 12-15-21
02/16/2022 Plans Tokyo grille Sealed 1-28-22
02/18/2022 Approved Plans approved - Tokyo grille Sealed 1-28-22
02/18/2022 Receipt Receipt for transaction: 2022-000891
02/18/2022 Letter DS Building Permit
02/25/2022 Letter INSPECTION SUMMARY
03/22/2022 Letter INSPECTION SUMMARY
03/24/2022 Letter INSPECTION SUMMARY
06/13/2022 Letter INSPECTION SUMMARY
06/14/2022 Letter INSPECTION SUMMARY
06/14/2022 Letter INSPECTION SUMMARY
06/15/2022 Letter INSPECTION SUMMARY
06/15/2022 Letter INSPECTION SUMMARY
06/16/2022 Letter INSPECTION SUMMARY
06/17/2022 Letter INSPECTION SUMMARY
06/20/2022 Letter INSPECTION SUMMARY
06/22/2022 Letter INSPECTION SUMMARY
09/09/2022 Letter INSPECTION SUMMARY
09/09/2022 Letter INSPECTION SUMMARY
09/09/2022 Letter INSPECTION SUMMARY
09/09/2022 Letter INSPECTION SUMMARY
09/14/2022 Letter INSPECTION SUMMARY
09/14/2022 Letter INSPECTION SUMMARY
10/13/2022 Letter Fire Building Plan Review
10/13/2022 TOKYO LEE SUMMITPRINT SPECS
10/24/2022 Tokyo Grille - 3528 SW Market St. - Fire Alarm Plans
11/01/2022 Letter Fire (Alarm) Plan Review Notice
11/14/2022 Letter INSPECTION SUMMARY
11/15/2022 Letter INSPECTION SUMMARY
11/16/2022 Letter HEALTH_DEPT_INSPECTION
11/16/2022 Receipt Receipt for transaction:2022-008970
11/16/2022 Letter Field Certificate of Occupancy
11/16/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home