Summary
PRCOM20210533
Building Permit - Commercial
Certificate of Occupancy
BRAIN DEV 3 LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR FOOD PANTRY WITH KITCHEN AND STORAGE AREAS
02/08/2021
07/06/2021
08/10/2021
02/09/2022
Locations
Contacts
STRICKLAND CONSTRUCTION CO INC, Address:720 S ROGERS RD STE B, Phone:(913) 764-7000  
MMC CONTRACTORS NATIONAL INC, Address:13800 WYANDOTTE, Phone:(816) 941-5300  
CAPITAL ELECTRIC CONSTRUCTION INC, Address:PO BOX 410079, Phone:(913) 335-1214  
MMC CONTRACTORS NATIONAL INC, Address:13800 WYANDOTTE, Phone:(816) 941-5300  
HERNLY ASSOCIATES INC, Address:1100 RHODE ISLAND STREET, Phone:(785) 749-5806  
BRAIN DEV 3 LLC, Address:300 E 39TH ST  
Jason@StricklandConstruction.com, Address:Jason@StricklandConstruction.com  
KDSM, Inc., Address:1101 Guinotte Avenue  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/27/2021 12/27/2021
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
12/27/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a test.
Building Plan Review Approved with Conditions 06/25/2021 07/02/2021
Joe Frogge
IBC 903.2.9 Fire Protection - S-1 sprinkler
Resolved
06/21/2021

2018 IBC 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing group A-2 occupancies and throughout all stories from the group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists. 1. The fire area exceeds 5,000 square feet. 2. The fire area has an occupant load of 100 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Action required: This occupancy is not allowed without a fire suppression sprinkler system.
Health Dept Review
Resolved
07/02/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 6/21/21 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
06/18/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 6/21/21 - acknowledged in letter
IPC 403.1.1 Fixture calculations
Resolved
06/21/2021

2018 IPC 403.1.1 Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 403.1. Fractional numbers resulting from applying the fixture ratios of Table 403.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall be first be summed and then rounded up to the next whole number. (see code section for exception) Action required: Additional water closet required for females. Male & female fixture counts are separate, not cumulative.
IBC 1209.2 Urinal partitions - privacy
Resolved
06/21/2021

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Partition required between urinal and sink in men's room. (fyi - this modification will conflict with turning radius)
IBC 1209.2 Finish materials
Resolved
06/21/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish material at mop sink.
Miscellaneous Correction
Resolved
06/21/2021

Inadequate information to complete review. Provide the following: - Complete grease hood design. - Roof plan to verify proximity of intakes to exhaust. - Complete natural gas piping design. - Outside air calculations and method of supply.
IBC 1606.2 Design dead load - structural
Resolved
06/21/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional roof load.
IMC 506.5.3 Grease fan mounting hinge
Corrective Action Required
06/21/2021

2018 IMC 506.5.3 Exhaust fan mounting. Up-blast fans serving Type I hoods and installed in a vertical or horizontal position shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning and shall be equipped with a means of restraint to limit the swing of the fan on its hinge. The ductwork shall extend not less than 18 inches above the roof surface. Action required: Grease hood fan to have hinged connection. To be field verified.
Health Department Review Approved 07/02/2021
Joe Frogge
Health Department Review Approved 07/02/2021
Joe Frogge
Fire Plan Review Approved with Conditions 06/25/2021 06/21/2021
Michael Weissenbach
Address numbers required
Resolved
06/21/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Address all exterior exit doors.
Type I hood - Where required
Resolved
06/21/2021

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Action Required) Provide specs on Type 1 hood system.
Group A-2 - Sprinkler system required
Resolved
06/21/2021

2018 IFC 903.2.1.2- Group A-2. An automatic sprinkler system shall be provided for Group A-2 occupancies where one of the following conditions exists: 1. The fire area exceeds 5,000 square feet (465 m2); 2. The fire area has an occupant load of 100 or more; or 3. The fire area is located on a floor other than the level of exit discharge. (Informational Purposes) This space is non-sprinklered. Due to the occupant load and the fire area exceeding 5000 sqft, a fire sprinkler system is required.
Portable fire extinguishers for commercial cooking equipment.
Resolved
06/21/2021

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Action Required) Provide a K-Class extinguisher. Placement to be made by the manual pull.
Panic and fire exit hardware
Resolved
06/21/2021

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Action Required) Provide Panic Hardware for the exit doors.
Installation acceptance testing
Corrective Action Required
06/21/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a test for the Type 1 Hood.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/21/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one additional 2A10BC Fire Extinguisher.
Door operations
Corrective Action Required
06/21/2021

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Licensed Contractors Approved 06/25/2021 06/18/2021
Joe Frogge
Licensed Contractors Approved 02/19/2021 02/11/2021
Joe Frogge
Building Plan Review Rejected 02/19/2021 02/11/2021
Joe Frogge
IBC 903.2.9 Fire Protection - S-1 sprinkler
Corrective Action Required
02/11/2021

2018 IBC 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing group A-2 occupancies and throughout all stories from the group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists. 1. The fire area exceeds 5,000 square feet. 2. The fire area has an occupant load of 100 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Action required: This occupancy is not allowed without a fire suppression sprinkler system.
Health Dept Review
Corrective Action Required
02/11/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
02/11/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
IPC 403.1.1 Fixture calculations
Corrective Action Required
02/11/2021

2018 IPC 403.1.1 Fixture calculations. To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 403.1. Fractional numbers resulting from applying the fixture ratios of Table 403.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall be first be summed and then rounded up to the next whole number. (see code section for exception) Action required: Additional water closet required for females. Male & female fixture counts are separate, not cumulative.
IBC 1209.2 Urinal partitions - privacy
Corrective Action Required
02/11/2021

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Partition required between urinal and sink in men's room. (fyi - this modification will conflict with turning radius)
IBC 1209.2 Finish materials
Corrective Action Required
02/11/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish material at mop sink.
Miscellaneous Correction
Corrective Action Required
02/11/2021

Inadequate information to complete review. Provide the following: - Complete grease hood design. - Roof plan to verify proximity of intakes to exhaust. - Complete natural gas piping design. - Outside air calculations and method of supply.
IBC 1606.2 Design dead load - structural
Corrective Action Required
02/11/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional roof load.
Fire Plan Review Rejected 02/19/2021 02/08/2021
Michael Weissenbach
Address numbers required
Corrective Action Required
02/08/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Address all exterior exit doors.
Type I hood - Where required
Corrective Action Required
02/08/2021

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Action Required) Provide specs on Type 1 hood system.
Group A-2 - Sprinkler system required
Corrective Action Required
02/08/2021

2018 IFC 903.2.1.2- Group A-2. An automatic sprinkler system shall be provided for Group A-2 occupancies where one of the following conditions exists: 1. The fire area exceeds 5,000 square feet (465 m2); 2. The fire area has an occupant load of 100 or more; or 3. The fire area is located on a floor other than the level of exit discharge. (Informational Purposes) This space is non-sprinklered. Due to the occupant load and the fire area exceeding 5000 sqft, a fire sprinkler system is required.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
02/08/2021

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Action Required) Provide a K-Class extinguisher. Placement to be made by the manual pull.
Panic and fire exit hardware
Corrective Action Required
02/08/2021

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Action Required) Provide Panic Hardware for the exit doors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $430.81 $430.81 Paid 07/06/2021
$0.00
8331507-Sewer Connection Fee $240.00 $240.00 Paid 07/06/2021
7232302-Commercial License Tax Fee $30,960.00 $30,960.00 Paid 02/11/2021
$30,960.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 8/4/2021 08/04/2021
In-wall Inspection Partial 9/14/2021 9/14/2021 09/14/2021
Misc
Corrective Action Required
09/14/2021
: PLUMBING ONLY : - PROVIDE 16 GAGE SHIELD PLATES @ DWV SUCH PLATES SHALL COVER THE AREA OF THE PIPE WHERE THE MEMBER IS NOTCHED OR BORED AND SHALL EXTEND NOT LESS THAN 2" ABOVE SOLE PLATE AND BELOW TOP PLATES ( 2018 IPC 305.6) - PROVIDE MIDPOINT SUPPORT VERTICAL DWV 2" & SMALLER ( 2018 IPC TABLE 308.5b ) - PRESSURE STEADY AT 5 PSI -
In-wall Inspection Partial 10/8/2021 10/8/2021 10/08/2021
Misc
Informational
10/08/2021
: PLUMBING : - PRESSURE STEADY AT 5 PSI - - METAL STUD FRAMING, ELECTRICAL, MECH -
Hood/Duct Inspection Partial 10/21/2021 10/21/2021 10/21/2021
Misc
Informational
10/21/2021
- WELDS APPROVED FOR 1ST LAYER WRAP -
Hood/Duct Inspection Partial 10/22/2021 10/22/2021 10/22/2021
Misc
Informational
10/21/2021
- WELDS APPROVED FOR 1ST LAYER WRAP - - 1ST LAYER WRAP APPROVED FOR 2ND LAYER -
Hood/Duct Inspection Passed 12/22/2021 12/22/2021
Misc
Informational
10/22/2021
- WELDS APPROVED FOR 1ST LAYER WRAP - - 1ST LAYER WRAP APPROVED FOR 2ND LAYER - - 2ND LAYER WRAP APPROVED -
Above Ceiling Inspection Passed 12/22/2021 12/22/2021 12/22/2021
Gas Piping Inspection - Commercial Passed 12/22/2021 12/22/2021 12/22/2021
Alternate Protection Systems Inspection Failed 1/13/2022 01/13/2022
Alarm Test Failed 01/13/2022
Corrective Action Required
01/13/2022
Duck detector need to be reported as a supervisory and not sent to fire dispatch. Make-up-air was not operational during inspection.
In-wall Inspection Passed 1/14/2022 01/14/2022
Occupancy Inspection - Codes Commercial Failed 1/14/2022 1/14/2022 01/14/2022
Miscellaneous Correction
Resolved
02/09/2022
Alarm Test Passed 2/7/2022 02/08/2022
Alternate Protection Systems Inspection Passed 2/7/2022 02/08/2022
Occupancy Inspection - Codes Commercial Full C of O 2/9/2022 2/9/2022 02/09/2022
Miscellaneous Correction
Resolved
02/09/2022
Documents & Images
Date Uploaded File Type Document Name
02/08/2021 Application Form coldwater permit application
02/08/2021 Application Form coldwater Tax application
02/08/2021 Plans CW-20210208-Archset
02/08/2021 Plans Coldwater M_P Drawings 2021_02_05
02/08/2021 Plans CE--E1- Coldwater Lease Space Permit
02/08/2021 Letter License Tax Bill
02/08/2021 Letter Fire Building Plan Review
02/11/2021 Letter DS P/R Corrections Document
06/18/2021 Drawing CE-E1- Coldwater Lease Space-Permit Rev_ 1
06/18/2021 Letter Lees Summit new engineer of record
06/18/2021 Letter Letter
06/18/2021 Letter PermitReplies_20210618
06/18/2021 Plans 21433MP-Coldwater BC
06/18/2021 Engineer Report/Study Coldwater scan
06/21/2021 Letter Fire Building Plan Review
06/22/2021 Plans CW-20210622-ARCHSET
07/02/2021 Approved Plans approved-ARCHSET
07/02/2021 Email New Food Establishment Plan Review - Approved FTG_0001399
07/06/2021 Receipt Receipt for transaction:2021-005364
07/06/2021 Letter DS Building Permit
08/04/2021 Letter INSPECTION SUMMARY
09/14/2021 Letter INSPECTION SUMMARY
09/14/2021 Letter INSPECTION SUMMARY
10/08/2021 Letter INSPECTION SUMMARY
10/21/2021 Letter INSPECTION SUMMARY
10/22/2021 Letter INSPECTION SUMMARY
12/22/2021 Letter INSPECTION SUMMARY
12/22/2021 Letter INSPECTION SUMMARY
12/22/2021 Letter INSPECTION SUMMARY
12/27/2021 Letter Fire (Alarm) Plan Review Notice
01/13/2022 Letter Fire Loss Reduction Form
01/14/2022 Letter INSPECTION SUMMARY
01/14/2022 Letter INSPECTION SUMMARY
02/09/2022 Letter Field Certificate of Occupancy
02/09/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home