Summary
PRCOM20210492
Building Permit - Commercial
Certificate of Occupancy
NEW OTHER (COMMERCIAL)
10 MOBILE CLASSROOMS
02/04/2021
02/26/2021
08/22/2021
11/08/2021
Locations
Contacts
STACO ELECTRIC CONSTRUCTION COMPANY INC, Address:11030 HICKMAN MILLS DR, Phone:(816) 765-7112  
matthew.tillman@lsr7.net  
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 03/04/2021 02/25/2021
Joe Frogge
Misc
Resolved
02/25/2021

Inadequate information to complete review. Provide the following: - - Foundation/pier design (frost protection required) 2/18/21 - not found in submittal - - Complete wiring diagram 2/18/21 - After discussions with electrician it is now apparent that new 2,000 amp switchgear is being installed. Complete design by licensed electrical engineer required.
Gen - Plan submittals 2018 codes
Corrective Action Required
02/25/2021

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code references to correct years. 2/18/21 - Piers and tie-downs to be per 2018 codes. 2/25/21 - Project has been reviewed and will be inspected per 2018 I-series codes
Fire Plan Review Approved with Conditions 03/04/2021 02/25/2021
Joe Frogge
Address numbers required
Corrective Action Required
02/25/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Provide classroom numbers on the exterior of the mobiles.
Misc
Corrective Action Required
02/25/2021

(Informational Purposes) During the final inspection for occupancy, the smoke alarms with horn strobes will be tested.
Licensed Contractors Approved 02/25/2021 02/25/2021
Joe Frogge
Building Plan Review Rejected 02/17/2021 02/18/2021
Joe Frogge
Misc
Corrective Action Required
02/09/2021

Inadequate information to complete review. Provide the following: - - Foundation/pier design (frost protection required) 2/18/21 - not found in submittal - - Complete wiring diagram 2/18/21 - After discussions with electrician it is now apparent that new 2,000 amp switchgear is being installed. Complete design by licensed electrical engineer required.
Gen - Plan submittals 2018 codes
Corrective Action Required
02/09/2021

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code references to correct years. 2/18/21 - Piers and tie-downs to be per 2018 codes.
Licensed Contractors Approved 02/17/2021 02/09/2021
Joe Frogge
Fire Plan Review Approved with Conditions 02/17/2021 02/09/2021
Michael Weissenbach
Address numbers required
Corrective Action Required
02/09/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Provide classroom numbers on the exterior of the mobiles.
Misc
Corrective Action Required
02/09/2021

(Informational Purposes) During the final inspection for occupancy, the smoke alarms with horn strobes will be tested.
Fire Plan Review Approved with Conditions 02/19/2021 02/04/2021
Michael Weissenbach
Address numbers required
Corrective Action Required
02/04/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Provide classroom numbers on the exterior of the mobiles.
Misc
Corrective Action Required
02/04/2021

(Informational Purposes) During the final inspection for occupancy, the smoke alarms with horn strobes will be tested.
Building Plan Review Rejected 02/19/2021 02/04/2021
Joe Frogge
Misc
Corrective Action Required
02/04/2021

Inadequate information to complete review. Provide the following: - Detailed method of constructing ramps for accessibility - Foundation/pier design (frost protection required) - Tie-down strap and anchor design - Complete wiring diagram - Is new switchgear mounted outside? Nema rating? Is there a new meter? (I was under the impression that these were feeders off of an existing switchgear)
Gen - Plan submittals 2018 codes
Corrective Action Required
02/04/2021

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code references to correct years.
Licensed Contractors Approved 02/04/2021 02/04/2021
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $900.00 $900.00 Paid 02/25/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Partial 3/2/2021 (8:00) 3/2/2021 03/02/2021
Misc
Corrective Action Required
03/02/2021
PIERS SE OF BUILDING BETWEEN PARKING LOT FOR TEMP TRAILERS
Underground Electrical Inspection - Commercial Passed 3/5/2021 03/05/2021
THE FOLLOWING AREAS ARE APPROVED
Informational
03/05/2021
UNDERGROUND CONDUIT SE PARKING LOT FOR MOBILE CLASSROOM UNITS
Occupancy Inspection - Fire Passed 4/2/2021 04/02/2021
Final Inspection - Commercial Partial 4/2/2021 04/02/2021
Misc
Corrective Action Required
04/02/2021
label main MDP for trailers Install permanent landings and stairs. Connect smokes in 3-4 (west trailers) mount all fire extinguisher. Ok for class on Monday April 5th with temp stairs and landings.
Final Inspection - Commercial Partial 4/7/2021 4/7/2021 04/07/2021
Misc
Resolved
11/08/2021
Piers/Caissons Inspection - Commercial Passed 05/12/2021
Misc
Resolved
05/12/2021
PIERS SE OF BUILDING BETWEEN PARKING LOT FOR TEMP TRAILERS
Electrical Service Inspection Passed 05/12/2021
Occupancy Inspection - Codes Commercial Failed 5/12/2021 5/12/2021 05/12/2021
Misc
Corrective Action Required
05/12/2021
Install permanent landings and stairs. Ok for class on Monday April 5th with temp stairs and landings. - NO CITY APPROVED PLANS ON SITE -
Final Inspection - Commercial Passed 11/8/2021 11/08/2021
Occupancy Inspection - Codes Commercial Full C of O 11/8/2021 11/08/2021
Misc
Resolved
11/08/2021
Documents & Images
Date Uploaded File Type Document Name
02/04/2021 Application Form LS MO Commercial Permit Application 2021 LSHS
02/04/2021 Plans 2464 Dry Classroom - Approved - Missouri 7-2
02/04/2021 Plot Plan LSHS Mobile electrical layout
02/04/2021 Letter Fire Building Plan Review
02/05/2021 Letter DS P/R Corrections Document
02/09/2021 Plans LSHS mobiles code questions
02/09/2021 Letter LSHS mobiles response to plan review_
02/09/2021 Letter Fire Building Plan Review
02/10/2021 Plans Mobile classroom TIE-DOWN info (1)
02/11/2021 Letter LSR7 - LSHS MV Gear for Temporary Classrooms
02/11/2021 Drawing LSHS trailer Temp
02/18/2021 Letter DS P/R Corrections Document
02/18/2021 Email RE LSHS mobiles response to plan review_ pdf
02/24/2021 Plans Mobile Classroom Electrical Drawings
02/24/2021 Plans Concrete Footing Design
02/24/2021 Plans Stamped Electrical Drawings
02/25/2021 Approved Plans approved - Stamped Electrical Drawings
02/25/2021 Approved Plans approved - Concrete Footing Design
02/25/2021 Approved Plans approved - LSHS mobiles code questions
02/25/2021 Approved Plans approved - 2464 Dry Classroom - Approved - Missouri 7-2
02/25/2021 Receipt Receipt for transaction:2021-000937
02/26/2021 Letter DS Building Permit
03/02/2021 Letter INSPECTION SUMMARY
03/05/2021 Letter INSPECTION SUMMARY
04/02/2021 Letter Fire Loss Reduction Form
04/02/2021 Letter INSPECTION SUMMARY
04/07/2021 Letter INSPECTION SUMMARY
05/12/2021 Letter INSPECTION SUMMARY
11/08/2021 Letter INSPECTION SUMMARY
11/08/2021 Letter Field Certificate of Occupancy
11/08/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home