Review Type |
Outcome |
Est. Completion Date |
Completed |
Building Plan Review
|
Approved with Conditions
|
03/04/2021
|
02/25/2021
|
|
Joe Frogge
|
|
Misc
Inadequate information to complete review.
Provide the following:
-
- Foundation/pier design (frost protection required)
2/18/21 - not found in submittal
-
- Complete wiring diagram
2/18/21 - After discussions with electrician it is now apparent that new 2,000 amp switchgear is being installed. Complete design by licensed electrical engineer required.
|
|
Gen - Plan submittals 2018 codes
Corrective Action Required
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit.
Action required: Update code references to correct years.
2/18/21 - Piers and tie-downs to be per 2018 codes.
2/25/21 - Project has been reviewed and will be inspected per 2018 I-series codes
|
|
|
Fire Plan Review
|
Approved with Conditions
|
03/04/2021
|
02/25/2021
|
|
Joe Frogge
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
(Action Required)
Provide classroom numbers on the exterior of the mobiles.
|
|
Misc
Corrective Action Required
(Informational Purposes)
During the final inspection for occupancy, the smoke alarms with horn strobes will be tested.
|
|
|
Licensed Contractors
|
Approved
|
02/25/2021
|
02/25/2021
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Rejected
|
02/17/2021
|
02/18/2021
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Inadequate information to complete review.
Provide the following:
-
- Foundation/pier design (frost protection required)
2/18/21 - not found in submittal
-
- Complete wiring diagram
2/18/21 - After discussions with electrician it is now apparent that new 2,000 amp switchgear is being installed. Complete design by licensed electrical engineer required.
|
|
Gen - Plan submittals 2018 codes
Corrective Action Required
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit.
Action required: Update code references to correct years.
2/18/21 - Piers and tie-downs to be per 2018 codes.
|
|
|
Licensed Contractors
|
Approved
|
02/17/2021
|
02/09/2021
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/17/2021
|
02/09/2021
|
|
Michael Weissenbach
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
(Action Required)
Provide classroom numbers on the exterior of the mobiles.
|
|
Misc
Corrective Action Required
(Informational Purposes)
During the final inspection for occupancy, the smoke alarms with horn strobes will be tested.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/19/2021
|
02/04/2021
|
|
Michael Weissenbach
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
(Action Required)
Provide classroom numbers on the exterior of the mobiles.
|
|
Misc
Corrective Action Required
(Informational Purposes)
During the final inspection for occupancy, the smoke alarms with horn strobes will be tested.
|
|
|
Building Plan Review
|
Rejected
|
02/19/2021
|
02/04/2021
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Inadequate information to complete review.
Provide the following:
- Detailed method of constructing ramps for accessibility
- Foundation/pier design (frost protection required)
- Tie-down strap and anchor design
- Complete wiring diagram
- Is new switchgear mounted outside? Nema rating? Is there a new meter? (I was under the impression that these were feeders off of an existing switchgear)
|
|
Gen - Plan submittals 2018 codes
Corrective Action Required
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit.
Action required: Update code references to correct years.
|
|
|