Permit Application Status

PRCOM20200307


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20200307
Building Permit - Commercial
Certificate of Occupancy
THE UNITED METHODIST CHURCH OF LEES SUMM
ADDITION COMMERCIAL
ADDITION TO CHURCH FOR OFFICE AND CHAPEL USE
02/11/2020
03/31/2020
08/22/2020
11/20/2020
Locations
Contacts
THE UNITED METHODIST CHURCH OF LEES SUMM, Address:3381 NW CHIPMAN RD  
AL HUBER, Address:10770 EL MONTE, Phone:(913) 341-4880  
MANTEL TETER ARCHITECTS, INC, Address:929 WALNUT ST, SUITE 5104, Phone:(816) 931-5600  
METRO AIR CONDITIONING , Address:8151 MCCOY ST, Phone:(913) 888-3991  
ELDECON INC, Address:120 SE 30TH ST, Phone:(660) 553-1121  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
MGORACKE@ALHUBER.COM  
TERRACON CONSULTANTS INC, Address:10841 S RIDGEVIEW ROAD, Phone:(913) 599-6886  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/07/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
07/07/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816)969-1300 to schedule a hydrostatic test.
Misc
Corrective Action Required
07/07/2020

(Informational Purposes) Current annual inspection tag needed on riser.
Final Development Plan Review Approved 03/30/2020
Joe Frogge
Building Plan Review Approved with Conditions 03/19/2020 03/30/2020
Joe Frogge
Final Development Plan
Resolved
03/30/2020

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes. 3/12/20 - acknowledged in letter
IBC 1704.2 Special Inspections
Resolved
03/12/2020

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
IMC 306.5 Equipment on roofs
Resolved
03/12/2020

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide permanent means of access to roof.
IBC 503.1 - Building area
Resolved
03/12/2020

2018 IBC 503.1 General. Unless otherwise specifically modified in Chapter 4 and this chapter, building height, number of stories and building area shall not exceed the limits specified in Sections 504 and 506 based on the type of construction as determined by Section 602 and the occupancies as determined by Section 302 except as modified hereafter. Building height, number of stories and building area provisions shall be applied independently. For the purposes of determining area limitations, height limitations and type of construction, each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building. Action required: Provide calculations for frontage area increase to justify total building area that exceeds maximum area in table.
IBC 1010.1.2 Door swing - direction of swing egress travel
Resolved
03/12/2020

2018 IBC 1010.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.) 2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Door #218 out of Chapel to swing in direction of egress. (If reversed as-is you will be in violation of maneuvering clearance minimums in ICC/ANSI A117.1 Section 404.2.3.2)
IBC 1004.9 Posting of occupant load
Corrective Action Required
03/12/2020

2018 IBC 1004.9 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space for the intended configurations. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Occupant load to be posted. To be field verified at final. 3/12/20 - acknowledged in letter - field verify
Fire Plan Review Approved with Conditions 03/19/2020 03/13/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
03/12/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign in Chapel.
Construction documents for fire alarm systems
Resolved
03/13/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of PE stamped shop drawings for modifications to the alarm system.
Construction documents - Fire protection systems
Corrective Action Required
03/12/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of PE stamped shop drawings for modifications to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
03/12/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Resolved
03/13/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide plan showing fire extinguisher placement.
Duct smoke detectors
Corrective Action Required
03/12/2020

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Verified at alarm test)
Direction of swing
Resolved
03/13/2020

2018 IFC 1010.1.2.1 Direction of swing. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. (Action Required) Change door swing out of Chapel leading into corridor. (North Side)
Illumination required
Resolved
03/13/2020

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide emergency lighting in restrooms.
Special Inspections Review Approved 03/12/2020
Joe Frogge
Licensed Contractors Approved 03/19/2020 03/12/2020
Joe Frogge
Building Plan Review Rejected 02/26/2020 02/24/2020
Joe Frogge
Final Development Plan
Corrective Action Required
02/24/2020

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes.
IBC 1704.2 Special Inspections
Corrective Action Required
02/24/2020

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
IMC 306.5 Equipment on roofs
Corrective Action Required
02/24/2020

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide permanent means of access to roof.
IBC 503.1 - Building area
Corrective Action Required
02/24/2020

2018 IBC 503.1 General. Unless otherwise specifically modified in Chapter 4 and this chapter, building height, number of stories and building area shall not exceed the limits specified in Sections 504 and 506 based on the type of construction as determined by Section 602 and the occupancies as determined by Section 302 except as modified hereafter. Building height, number of stories and building area provisions shall be applied independently. For the purposes of determining area limitations, height limitations and type of construction, each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building. Action required: Provide calculations for frontage area increase to justify total building area that exceeds maximum area in table.
IBC 1010.1.2 Door swing - direction of swing egress travel
Corrective Action Required
02/24/2020

2018 IBC 1010.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.) 2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Door #218 out of Chapel to swing in direction of egress. (If reversed as-is you will be in violation of maneuvering clearance minimums in ICC/ANSI A117.1 Section 404.2.3.2)
IBC 1004.9 Posting of occupant load
Corrective Action Required
02/24/2020

2018 IBC 1004.9 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space for the intended configurations. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Occupant load to be posted. To be field verified at final.
Alarm Plan Review Released for Construction 02/13/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
02/13/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule alarm testing.
Fire Plan Review Rejected 02/26/2020 02/12/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
02/12/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign in Chapel.
Construction documents for fire alarm systems
Corrective Action Required
02/12/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of PE stamped shop drawings for modifications to the alarm system.
Construction documents - Fire protection systems
Corrective Action Required
02/12/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of PE stamped shop drawings for modifications to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
02/12/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
02/12/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide plan showing fire extinguisher placement.
Duct smoke detectors
Corrective Action Required
02/12/2020

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Verified at alarm test)
Direction of swing
Corrective Action Required
02/12/2020

2018 IFC 1010.1.2.1 Direction of swing. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. (Action Required) Change door swing out of Chapel leading into corridor. (North Side)
Illumination required
Corrective Action Required
02/12/2020

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide emergency lighting in restrooms.
Licensed Contractors Approved 02/26/2020 02/11/2020
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $3,705.00 $3,705.00 Paid 02/11/2020
$3,705.00
9110078-Valuation Fee for Addition to Commercial $7,862.26 $7,862.26 Paid 03/27/2020
8331507-Sewer Connection Fee $240.00 $240.00 Paid 03/27/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 4/15/2020 4/15/2020 04/15/2020
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
04/15/2020
AA 4.5-9 WEST -AA-SOUTH TO CORNER 2 INTERIOR PIERS
Footing Inspection - Commercial Partial 4/21/2020 4/21/2020 04/21/2020
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
04/15/2020
AA 4.5-9 WEST -AA-SOUTH TO CORNER 2 INTERIOR PIERS SW CORNER TO BUILDING, EAST SECTION. CONSTRUCTION ENTRANCE REMAINING.
Footing Inspection - Commercial Partial 4/22/2020 4/22/2020 04/22/2020
THE FOLLOWING AREAS ARE APPROVED
Resolved
11/17/2020
AA 4.5-9 WEST -AA-SOUTH TO CORNER 2 INTERIOR PIERS SW CORNER TO BUILDING, EAST SECTION. CONSTRUCTION ENTRANCE REMAINING. - AA TO AA5 FOOTING, PAD @ AA4 PER PLAN OK TO POUR -
Underslab Electrical Inspection - Commercial Partial 4/28/2020 4/28/2020 04/28/2020
Misc
Corrective Action Required
04/28/2020
FROM EXISTING BUILDING TO ADDITION MDP ON THE INTERIOR
E300.5 Underground Installations
Resolved
04/28/2020
Minimum Cover see Table 300.5
Underslab Plumbing Inspection - Commercial Failed 4/30/2020 4/30/2020 04/30/2020
Misc
Corrective Action Required
04/30/2020
install Wall clean out at west side of bath group. recall wehn complete
Underslab Electrical Inspection - Commercial Passed 5/1/2020 5/1/2020 05/01/2020
Misc
Corrective Action Required
04/28/2020
FROM EXISTING BUILDING TO ADDITION MDP ON THE INTERIOR
Underslab Plumbing Inspection - Commercial Partial 5/1/2020 5/1/2020 05/01/2020
Misc
Resolved
11/17/2020
install Wall clean out at west side of bath
All Rough Inspection - Commercial Partial 7/10/2020 7/10/2020 07/10/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
07/10/2020
- EXTERIOR STRUCTURAL METAL STUDS -
Rough Plumbing Inspection - Commercial Partial 7/17/2020 7/17/2020 07/17/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
07/17/2020
- ROOF DRAINS STEADY AT 5 PSI 3 GAUGES - - EXCEPT ONE ROOF DRAIN LINE ABOVE RESTROOMS TO CORE DRILL EXISTING WALL NEEDS INSPECTION -
In-wall Inspection Partial 8/6/2020 8/6/2020 08/06/2020
Misc
Informational
08/06/2020
- INTERIOR METAL STUD FRAMING APPROVED - - OK TO ROCK BEHIND PANELS ROOMS 215 & 216, TOP OUT FOR DUCT WORK -
All Rough Inspection - Commercial Partial 8/6/2020 08/06/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
07/10/2020
- EXTERIOR STRUCTURAL METAL STUDS - - INTERIOR METAL STUD FRAMING - - OK TO ROCK BEHIND PANELS ROOMS 215 & 216 7 TOP OUT FOR DUCT WORK -
In-wall Inspection Partial 8/12/2020 8/12/2020 08/12/2020
Misc
Informational
08/06/2020
- INTERIOR METAL STUD FRAMING APPROVED - - OK TO ROCK BEHIND PANELS ROOMS 215 & 216, TOP OUT FOR DUCT WORK -
Misc
Informational
08/12/2020
: THE FOLLOWING AREAS ARE APPROVED : ROOMS 200, 201,202,203,204,205,206,207,208,209,210,211,212, 213,214
Misc
Corrective Action Required
11/17/2020
- REAR GRAB BARS SHALL BE 6" FROM CORNER IN BOTH RESTROOMS - - COUNTERTOPS IN RESTROOMS SHALL BE 34" AFF -
In-wall Inspection Partial 8/19/2020 8/19/2020 08/19/2020
Misc
Informational
08/12/2020
- INTERIOR METAL STUD FRAMING APPROVED - - OK TO ROCK BEHIND PANELS ROOMS 215 & 216, TOP OUT FOR DUCT WORK -
Misc
Informational
08/12/2020
: THE FOLLOWING AREAS ARE APPROVED : ROOMS 200, 201,202,203,204,205,206,207,208,209,210,211,212, 213,214, 219,220, 221
Gas Piping Inspection - Commercial Passed 8/20/2020 8/20/2020 08/20/2020
Misc
Informational
08/20/2020
- GAS LINE TIED INTO EXISTING BUILDING ACROSS ROOF DOWN PARAPET TO NEW RTUS -
In-wall Inspection Passed 8/20/2020 8/20/2020 08/20/2020
Misc
Informational
08/19/2020
- INTERIOR METAL STUD FRAMING APPROVED - - OK TO ROCK BEHIND PANELS ROOMS 215 & 216, TOP OUT FOR DUCT WORK -
Misc
Informational
08/19/2020
: THE FOLLOWING AREAS ARE APPROVED : ROOMS 200, 201,202,203,204,205,206,207,208,209,210,211,212, 213,214, 219,220, 221 - CHAPEL AREA -
Above Ceiling Inspection Partial 9/25/2020 9/25/2020 09/25/2020
Misc
Corrective Action Required
09/25/2020
- HARD LIDS RM 200 VESTIBULE,RM 217 SOUND LOCK, RM 219 LOBBY -
Above Ceiling Inspection Partial 9/30/2020 9/30/2020 09/30/2020
Misc
Corrective Action Required
09/25/2020
- HARD LIDS RM 200 VESTIBULE,RM 217 SOUND LOCK, RM 219 LOBBY - - ALL EXCEPT RESTROOMS -
Above Ceiling Inspection Passed 10/8/2020 10/8/2020 10/08/2020
Misc
Informational
10/08/2020
- HARD LIDS RM 200 VESTIBULE,RM 217 SOUND LOCK, RM 219 LOBBY - - ALL EXCEPT RESTROOMS - - RESTROOMS -
Sprinkler - Hydrostatic Test Passed 10/14/2020 10/14/2020
Alarm Test Passed 11/13/2020 11/16/2020
Occupancy Inspection - Planning Passed 11/17/2020
All Rough Inspection - Commercial Passed 11/17/2020 11/17/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
08/06/2020
- EXTERIOR STRUCTURAL METAL STUDS - - INTERIOR METAL STUD FRAMING - - OK TO ROCK BEHIND PANELS ROOMS 215 & 216 7 TOP OUT FOR DUCT WORK -
Footing Inspection - Commercial Passed 11/17/2020 11/17/2020
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
04/22/2020
AA 4.5-9 WEST -AA-SOUTH TO CORNER 2 INTERIOR PIERS SW CORNER TO BUILDING, EAST SECTION. CONSTRUCTION ENTRANCE REMAINING. - AA TO AA5 FOOTING, PAD @ AA4 PER PLAN OK TO POUR -
Underslab Plumbing Inspection - Commercial Passed 11/17/2020 11/17/2020
Misc
Corrective Action Required
05/01/2020
install Wall clean out at west side of bath group. pending
Rough Plumbing Inspection - Commercial Passed 11/17/2020 11/17/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
07/17/2020
- ROOF DRAINS STEADY AT 5 PSI 3 GAUGES -
Occupancy Inspection - Engineering Passed 11/17/2020 11/17/2020
Occupancy Inspection - Codes Commercial Temporary C of O 11/17/2020 11/17/2020 11/17/2020
Misc
Corrective Action Required
11/17/2020
- BOTH RESTROOMS INSTALL REAR GRAB BARS PER CODE - - BOTH RESTROOM COUNTERTOP SHALL BE 34" AFF -
Occupancy Inspection - Fire Passed 11/17/2020 11/17/2020 11/19/2020
Occupancy Inspection - Water Utilities Passed 11/20/2020
Occupancy Inspection - Codes Commercial Full C of O 11/20/2020 11/20/2020 11/20/2020
Misc
Resolved
11/20/2020
Documents & Images
Date Uploaded File Type Document Name
02/11/2020 Letter License Tax Bill
02/12/2020 Letter Fire Building Plan Review
02/13/2020 Letter Fire (Alarm) Plan Review Notice
02/24/2020 Letter DS P/R Corrections Document
03/13/2020 Letter Fire Building Plan Review
03/30/2020 Approved set FDP- Summit church addition
03/31/2020 Letter DS Building Permit
03/31/2020 20-0316 The Summit Phase 2 - Construction Drawings (permit approved)
03/31/2020 Approved Plans Approved - 20-0316 The Summit Phase 2 - Construction Drawings (permit approved)
04/15/2020 Letter INSPECTION SUMMARY
04/21/2020 Letter INSPECTION SUMMARY
04/22/2020 Letter INSPECTION SUMMARY
04/28/2020 Letter INSPECTION SUMMARY
04/28/2020 Letter Codes Plan Review Conditions
04/30/2020 Letter INSPECTION SUMMARY
05/01/2020 Letter INSPECTION SUMMARY
05/01/2020 Letter INSPECTION SUMMARY
07/07/2020 Summit Church phase 2 hydraulic calcs 070620
07/07/2020 Summit church phase II for submittal 070620
07/07/2020 Letter Fire (Sprinkler) Plan Review
07/10/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/12/2020 Letter INSPECTION SUMMARY
08/19/2020 Letter INSPECTION SUMMARY
08/19/2020 Letter INSPECTION SUMMARY
08/20/2020 Letter INSPECTION SUMMARY
08/20/2020 Letter INSPECTION SUMMARY
09/25/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
10/08/2020 Letter INSPECTION SUMMARY
11/17/2020 Letter INSPECTION SUMMARY
11/17/2020 Letter INSPECTION SUMMARY
11/17/2020 Letter INSPECTION SUMMARY
11/17/2020 Letter INSPECTION SUMMARY
11/17/2020 Letter Codes Temporary Certificate of Occupancy
11/20/2020 Letter Field Certificate of Occupancy
11/20/2020 Letter Codes Final Certificate of Occupancy
12/02/2020 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home