Summary
PRCOM20200261
Building Permit - Commercial
Certificate of Occupancy
PINE TREE PLAZA LLC
CHANGE OF TENANT
TENANT FINISH FOR GOLF EQUIPMENT RETAILER
02/04/2020
03/26/2020
08/04/2020
12/03/2020
Locations
Contacts
PINE TREE PLAZA LLC, Address:601 E SOUTH ST  
KATHERINE GUYON ARCHITECT, Address:67 INVERNESS DR E, SUITE 175, Phone:(720) 261-5802  
A & D HEATING AND COOLING INC, Address:2006 W MAIN ST, Phone:(816) 537-7952  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
  
IDEAL CONSTRUCTION INC, Address:P O BOX 241339, Phone:(402) 639-7199  
PIERPOINT PLUMBING, Address:7706 S OUTER BELT RD, Phone:(816) 922-0829  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 03/12/2020 03/11/2020
Joe Frogge
LC - General Contractor
Resolved
03/11/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 3/6/20 - Ideal Constr. not currently licensed
LC - MEP Subs
Resolved
03/11/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/6/20 - Pierpoint Plumbing does not have a plumbing license with us.
Building Plan Review Approved 03/12/2020 03/06/2020
Joe Frogge
Resolved
03/06/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Gen - Plan submittals 2018 codes
Resolved
03/06/2020

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code analysis to show correct year for ICC/ANSI which is 2017.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
03/06/2020

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of door D1 out of coaches office.
IBC 1209.2 Finish materials
Resolved
03/06/2020

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish materials in toilet rooms. If paint, it must be epoxy based.
ICC A117.1 604.6 Flush Controls
Resolved
03/06/2020

ICC A117.1 Section 604.6 Flush Controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet. Exception: In ambulatory accessible compartments complying with Section 604.10, flush controls shall be permitted to be located on either side of the water closet. Action required: Water closet flush control handle must be on open side. Ref: plumbing riser.
IMC 602.2.1 Materials within plenums
Resolved
03/06/2020

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC not allowed in plenum. Revise mechanical or plumbing design accordingly.
IBC 1008.3 Emergency power for illumination - at exit discharge
Resolved
03/06/2020

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exits.
Fire Plan Review Approved with Conditions 03/12/2020 03/06/2020
Michael Weissenbach
Address numbers required
Resolved
03/06/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address front and rear exit doors.
Portable fire extinguishers - conspicuous locations
Resolved
03/06/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher
Door operations
Resolved
03/06/2020

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Emergency power for illumination
Resolved
03/06/2020

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. (Action Required) Provide exterior emergency lighting.
Building Plan Review Rejected 02/14/2020 02/06/2020
Joe Frogge
Corrective Action Required
02/06/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Gen - Plan submittals 2018 codes
Corrective Action Required
02/06/2020

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code analysis to show correct year for ICC/ANSI which is 2017.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
02/06/2020

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of door D1 out of coaches office.
IBC 1209.2 Finish materials
Corrective Action Required
02/06/2020

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish materials in toilet rooms. If paint, it must be epoxy based.
ICC A117.1 604.6 Flush Controls
Corrective Action Required
02/06/2020

ICC A117.1 Section 604.6 Flush Controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet. Exception: In ambulatory accessible compartments complying with Section 604.10, flush controls shall be permitted to be located on either side of the water closet. Action required: Water closet flush control handle must be on open side. Ref: plumbing riser.
IMC 602.2.1 Materials within plenums
Corrective Action Required
02/06/2020

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC not allowed in plenum. Revise mechanical or plumbing design accordingly.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
02/06/2020

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exits.
Licensed Contractors Rejected 02/14/2020 02/06/2020
Joe Frogge
LC - General Contractor
Corrective Action Required
02/06/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
02/06/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 02/14/2020 02/05/2020
Michael Weissenbach
Address numbers required
Corrective Action Required
02/05/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address front and rear exit doors.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
02/05/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher
Door operations
Corrective Action Required
02/05/2020

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Emergency power for illumination
Corrective Action Required
02/05/2020

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. (Action Required) Provide exterior emergency lighting.
Fees
Paid Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $12,975.00 $12,975.00 Paid 02/04/2020
$12,975.00
8331507-Sewer Connection Fee $120.00 $120.00 Paid 03/26/2020
9110078-Valuation Fee for Change of Tenant $340.00 $340.00 Paid 03/26/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Failed 9/22/2020 9/22/2020 09/22/2020
Miscellaneous Correction
Resolved
09/30/2020
All Rough Inspection - Commercial Failed 9/30/2020 9/30/2020 09/30/2020
Misc
Resolved
10/01/2020
All Rough Inspection - Commercial Passed 10/1/2020 10/01/2020
Rough Plumbing Inspection - Commercial Passed 10/1/2020 10/1/2020 10/01/2020
Miscellaneous Correction
Corrective Action Required
09/22/2020
Above Ceiling Inspection Passed 11/12/2020 11/12/2020 11/12/2020
Rough Mechanical Inspection - Commercial Passed 10/1/2020 11/12/2020
Rough Electrical Inspection - Commercial Passed 10/1/2020 11/12/2020
In-wall Inspection Passed 10/1/2020 11/12/2020
Occupancy Inspection - Codes Commercial Failed 12/2/2020 12/2/2020 12/02/2020
Misc
Corrective Action Required
12/02/2020
- PROVIDE MIRROR RESTROOM 40" TO REFLECTIVE SURFACE - - INSULATE PIPES UNDER VANITY IN RESTROOM - - PROVIDE ADDRESS REAR DOOR - - PROVIDE ADDRESS METER CAN /DISCONNECT - - MOUNT FIRE EXTINGUISHER -
Occupancy Inspection - Fire Passed 12/2/2020 12/2/2020 12/02/2020
Occupancy Inspection - Codes Commercial Full C of O 12/3/2020 12/3/2020 12/03/2020
Misc
Resolved
12/03/2020
Documents & Images
Date Uploaded File Type Document Name
02/04/2020 Email RE LT - is this ever easy - PRCOM20200261
02/05/2020 Letter Fire Building Plan Review
02/06/2020 Letter DS P/R Corrections Document
03/06/2020 Letter Fire Building Plan Review
03/18/2020 Plans GOLFTEC Permit Resubmittal Dwgs
03/26/2020 Receipt Receipt for transaction: 2020-001302
03/26/2020 Letter DS Building Permit
03/26/2020 signed - DS Building Permit
03/26/2020 Plans Approved - GOLFTEC Permit Resubmittal Dwgs
09/22/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
10/01/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
12/02/2020 Letter INSPECTION SUMMARY
12/02/2020 Letter INSPECTION SUMMARY
12/03/2020 Letter INSPECTION SUMMARY
12/03/2020 Letter Field Certificate of Occupancy
12/03/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home