Permit Application Status

PRCOM20192320


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192320
Building Permit - Commercial
Final Completion
KINGSPORT LLC
ALTERATION COMMERCIAL
PAINT BOOTH FOR AUTO RESTORATION BUSINESS
08/22/2019
10/31/2019
04/25/2020
03/02/2020
Locations
Contacts
KINGSPORT LLC, Address:9809 STONEHAUS DR  
THE RESTO MOD STORE , Address:1510 SE KINGSPOINT DR, Phone:(816) 291-4979  
HIRST & ASSOCIATES PC, Address:3810 NE BEECHWOOD DR, Phone:(816) 225-2550  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
BLUE SPRINGS ELECTRICAL SERVICE, Address:3402 LAKE SHORE DR, Phone:(816) 224-9911  
MIKE MCLIN, Address:29812 E MAJOR RD, Phone:(816) 813-9884  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 11/04/2019 10/30/2019
Joe Frogge
Misc
Resolved
10/30/2019

Inadequate information to complete review. Provide the following: - Complete electrical design including materials and methods to comply with 2017 NEC Article 500 for Class 1, Division 1 locations. - Locate equipment on floor plan - Locate exhaust distribution ductwork and terminations. - Demonstrate compliance with 2018 IMC 502.7 & 510.2. - Provide make-up air design if provided. - Provide contact information for engineer of record. (Mr. Hirst did not seal drawings)
Licensed Contractors Approved 11/04/2019 10/30/2019
Joe Frogge
LC - MEP Subs
Resolved
10/30/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed mechanical contractor. Dowell Construction does not have a LS business license.
Fire Plan Review Approved 11/04/2019 10/29/2019
Michael Weissenbach
Installation acceptance testing
Resolved
10/29/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - general
Resolved
10/29/2019

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Action Required) Provide a 40B extinguisher within 30 feet of the booth.
Miscellaneous Correction
Resolved
10/29/2019

(Action Required) The booth will need an approved automatic fire-extinguishing system. 2018 IFC 2404.4 Provide plans showing protection
Sprinkler Plan Review Released for Construction 10/01/2019 10/01/2019
Michael Weissenbach
Building Plan Review Rejected 09/04/2019 08/28/2019
Joe Frogge
Misc
Corrective Action Required
08/28/2019

Inadequate information to complete review. Provide the following: - Complete electrical design including materials and methods to comply with 2017 NEC Article 500 for Class 1, Division 1 locations. - Locate equipment on floor plan - Locate exhaust distribution ductwork and terminations. - Demonstrate compliance with 2018 IMC 502.7 & 510.2. - Provide make-up air design if provided. - Provide contact information for engineer of record. (Mr. Hirst did not seal drawings)
Licensed Contractors Rejected 09/04/2019 08/28/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
08/28/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed mechanical contractor. Dowell Construction does not have a LS business license.
Fire Plan Review Rejected 09/04/2019 08/28/2019
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
08/28/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - general
Corrective Action Required
08/28/2019

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Action Required) Provide a 40B extinguisher within 30 feet of the booth.
Miscellaneous Correction
Corrective Action Required
08/28/2019

(Action Required) The booth will need an approved automatic fire-extinguishing system. 2018 IFC 2404.4 Provide plans showing protection
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $39.20 $39.20 Paid 10/31/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Passed 3/3/2020 3/3/2020 03/03/2020
Documents & Images
Date Uploaded File Type Document Name
08/28/2019 Letter Fire Building Plan Review
08/28/2019 Letter DS P/R Corrections Document
10/01/2019 Letter Fire (Sprinkler) Plan Review
10/29/2019 Letter Fire Building Plan Review
10/31/2019 Receipt Receipt for transaction: 2019-007100
10/31/2019 Letter DS Building Permit
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home