Permit Application Status

PRCOM20181348


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20181348
Building Permit - Commercial
Certificate of Occupancy
SUMMIT NORTHRIDGE LLC
CHANGE OF TENANT
TENANT FINISH FOR ICE CREAM SHOP
05/02/2018
05/24/2018
11/04/2018
08/23/2018
Locations
Contacts
SUMMIT NORTHRIDGE LLC, Address:605 W 47TH ST STE 200  
R FARNAN ARCHITECT, Address:4801 WYOMING ST, Phone:(816) 516-5071  
JC KEYS CONSTRUCTION, Address:24280 W 113TH TERR, Phone:(913) 488-6614  
THE ISLAS FAM, Address:106 S VERMONT, Phone:(816) 835-9753  
THE ISLAS FAM, Address:106 S VERMONT, Phone:(816) 835-9753  
NEEDHAM MECHANICAL, Address:PO BOX 3341, Phone:(913) 999-4030  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/30/2018
Joe Dir
Licensed Contractors Approved 05/11/2018 05/24/2018
Development Center
LC - General Contractor
Resolved
05/24/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 5/15/18 - acknowledged
LC - MEP Subs
Resolved
05/16/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 5/15/18 - acknowledged
Fire Plan Review Approved with Conditions 05/18/2018 05/23/2018
Joe Dir
Portable fire extinguishers - general
Corrective Action Required
05/23/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of one 2A-10BC fire extinguisher. Fire extinguisher to be mounted on a normal path of travel close to an exit.
Posting of occupant load
Corrective Action Required
05/23/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) post the occupant load of 48 close to the main entrance.
Construction documents for fire alarm systems
Corrective Action Required
05/23/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(acknowledged) If there are no fire alarm system devices currently existing, notification devices need to be added to the space. Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alarm system devices.
Construction documents - Fire protection systems
Corrective Action Required
05/23/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(acknowledged) Have the fire sprinkler system contractor provide shop drawings of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
05/23/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(acknowledged) In the event that any fire alarm system devices need to be relocated, disconnected or newly installed an acceptance test will be required prior to the final occupancy inspection. Contact the fire department to schedule testing.9816)969-1300
Misc
Corrective Action Required
05/23/2018

Door operations ACTION REQUIRED: (verified at inspection) No keyed locks on the egress side of an exit.
Building Plan Review Approved with Conditions 05/18/2018 05/21/2018
Joe Frogge
License Tax Application
Corrective Action Required
05/11/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 5/15/18 - acknowledged
Health Dept Review
Resolved
05/21/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 5/15/18 - acknowledged
Health Dept Inspection
Corrective Action Required
05/11/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 5/15/18 - acknowledged
Misc
Resolved
05/15/2018

2012 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Remove note referencing air chambers uses for water hammer as they are not allowed.
Health Department Review Approved 05/21/2018
Joe Frogge
Fire Plan Review Approved with Conditions 05/18/2018 05/16/2018
Joe Dir
Portable fire extinguishers - general
Corrective Action Required
05/11/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of one 2A-10BC fire extinguisher. Fire extinguisher to be mounted on a normal path of travel close to an exit.
Posting of occupant load
Corrective Action Required
05/11/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) post the occupant load of 48 close to the main entrance.
Construction documents for fire alarm systems
Corrective Action Required
05/11/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(acknowledged) If there are no fire alarm system devices currently existing, notification devices need to be added to the space. Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alarm system devices.
Construction documents - Fire protection systems
Corrective Action Required
05/11/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(acknowledged) Have the fire sprinkler system contractor provide shop drawings of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
05/11/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(acknowledged) In the event that any fire alarm system devices need to be relocated, disconnected or newly installed an acceptance test will be required prior to the final occupancy inspection. Contact the fire department to schedule testing.9816)969-1300
Misc
Corrective Action Required
05/11/2018

Door operations ACTION REQUIRED: (verified at inspection) No keyed locks on the egress side of an exit.
Building Plan Review Rejected 05/14/2018 05/08/2018
Joe Frogge
License Tax Application
Corrective Action Required
05/08/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
05/08/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
05/08/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/08/2018

2012 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Remove note referencing air chambers uses for water hammer as they are not allowed.
Licensed Contractors Rejected 10/17/2018 05/08/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
05/08/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/08/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 05/14/2018 05/08/2018
Joe Dir
Portable fire extinguishers - general
Corrective Action Required
05/08/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of one 2A-10BC fire extinguisher. Fire extinguisher to be mounted on a normal path of travel close to an exit.
Posting of occupant load
Corrective Action Required
05/08/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspection) post the occupant load of 48 close to the main entrance.
Construction documents for fire alarm systems
Corrective Action Required
05/08/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(acknowledged) If there are no fire alarm system devices currently existing, notification devices need to be added to the space. Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alarm system devices.
Construction documents - Fire protection systems
Corrective Action Required
05/08/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(acknowledged) Have the fire sprinkler system contractor provide shop drawings of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
05/08/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(acknowledged) In the event that any fire alarm system devices need to be relocated, disconnected or newly installed an acceptance test will be required prior to the final occupancy inspection. Contact the fire department to schedule testing.9816)969-1300
Misc
Corrective Action Required
05/08/2018

Door operations ACTION REQUIRED:(verified at inspection No keyed locks on the egress side of an exit.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $616.84 $616.84 Paid 05/24/2018
8331507-Sewer Connection Fee $330.00 $330.00 Paid 05/24/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Partial 6/5/2018 at 3:20 PM 06/05/2018
Miscellaneous Inspection Partial 6/8/2018 at 8:25 AM 06/11/2018
Miscellaneous Inspection Partial 6/11/2018 at 8:40 AM 06/11/2018
Miscellaneous Inspection Partial 6/12/2018 at 10:45 AM 06/12/2018
Occupancy Inspection - Water Utilities Passed 07/02/2018
Gas Piping Inspection - Commercial Not Ready 7/5/2018 7/5/2018 at 9:50 AM 07/05/2018
Misc
Corrective Action Required
07/05/2018
GAS PIPING REQUESTED FOR INSPECTION IS NOT ON THIS PERMIT PER PERSONNEL ON JOBSITE
Underslab Plumbing Inspection - Commercial Passed 7/5/2018 7/5/2018 at 10:00 AM 07/05/2018
In-wall Inspection Failed 7/5/2018 at 10:20 AM 07/05/2018
Misc
Corrective Action Required
07/05/2018
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Partial Correction
07/05/2018
CURVED BULHEAD NEEDS ADDITIONAL SUPPORT AT EAST END. OK TO COVER EXCEPT THERE.
In-wall Inspection Not Ready 7/6/2018 at 9:10 AM 07/06/2018
Misc
Corrective Action Required
07/05/2018
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Partial Correction
07/05/2018
CURVED BULKHEAD OK TO COVER
Misc
Corrective Action Required
07/06/2018
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
Above Ceiling Inspection Not Ready 7/10/2018 7/10/2018 at 8:45 AM 07/10/2018
Misc
Corrective Action Required
07/10/2018
NOT READY FOR ABOVE-CEILING INSPECTION
Misc
Corrective Action Required
07/10/2018
SOME CEILING GRID NOT AT PERMANENT ELEVATION. SEE AT RESTROOMS
Misc
Corrective Action Required
07/10/2018
FLEX DUCT NOT APPROVED: - SECURE INNER LAYER, THEN OUTER LAYER WITH LISTED MATERIAL - HANGERS NOT MINIMUM 1-1/2" WIDE - NOT BENDS TO BE CONSTRICTED
Misc
Corrective Action Required
07/10/2018
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER.
Misc
Corrective Action Required
07/10/2018
NEC 300.11: SECURING AND SUPPORTING OF ELECTRICAL CABLE ASSEMBLIES: MAY NOT BE SUPPORTED BY CEILING SUPPORT HANGER WIRES; SUPPORT FROM STRUCTURE, FROM OTHER COMPONENTS OF ELECTRICAL SYSTEM, OR FROM HANGERS INSTALLED FOR SUPPORT OF THE ELECTRICAL SYSTEM. SECURE BOTH ENDS OF INDEPENDENT SUPPORT WIRES.
Misc
Corrective Action Required
07/10/2018
Misc
Corrective Action Required
07/10/2018
SOME ELECTRICAL BOXES NOT MADE UP AND CLOSED.
In-wall Inspection Passed 7/10/2018 7/10/2018 at 8:30 AM 07/10/2018
Misc
Resolved
07/10/2018
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Resolved
07/10/2018
CURVED BULKHEAD OK TO COVER
Misc
Resolved
07/10/2018
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
Above Ceiling Inspection Failed 7/25/2018 at 10:30 AM 07/25/2018
Misc
Corrective Action Required
07/10/2018
NOT READY FOR ABOVE-CEILING INSPECTION **FIRE SPRINKLER SYSTEM NOT COMPLETED **SUPPORT DWV PIPING AT MAX 4 FT INTERVAL
Misc
Resolved
07/25/2018
SOME CEILING GRID NOT AT PERMANENT ELEVATION. SEE AT RESTROOMS
Misc
Resolved
07/25/2018
FLEX DUCT NOT APPROVED: - SECURE INNER LAYER, THEN OUTER LAYER WITH LISTED MATERIAL - HANGERS NOT MINIMUM 1-1/2" WIDE - NOT BENDS TO BE CONSTRICTED
Misc
Resolved
07/25/2018
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER.
Misc
Resolved
07/25/2018
NEC 300.11: SECURING AND SUPPORTING OF ELECTRICAL CABLE ASSEMBLIES: MAY NOT BE SUPPORTED BY CEILING SUPPORT HANGER WIRES; SUPPORT FROM STRUCTURE, FROM OTHER COMPONENTS OF ELECTRICAL SYSTEM, OR FROM HANGERS INSTALLED FOR SUPPORT OF THE ELECTRICAL SYSTEM. SECURE BOTH ENDS OF INDEPENDENT SUPPORT WIRES.
Misc
Resolved
07/25/2018
Misc
Corrective Action Required
07/10/2018
SOME ELECTRICAL BOXES NOT MADE UP AND CLOSED. **ABOVE PRE-KITCHEN AREA. INSTALL LIGHT FIXTURES
Above Ceiling Inspection Passed 8/1/2018 8/1/2018 at 10:10 AM 08/01/2018
Misc
Resolved
08/01/2018
NOT READY FOR ABOVE-CEILING INSPECTION **FIRE SPRINKLER SYSTEM NOT COMPLETED **SUPPORT DWV PIPING AT MAX 4 FT INTERVAL
Misc
Resolved
08/01/2018
SOME ELECTRICAL BOXES NOT MADE UP AND CLOSED. **ABOVE PRE-KITCHEN AREA. INSTALL LIGHT FIXTURES
Occupancy Inspection - Codes Commercial Failed 8/7/2018 8/7/2018 at 10:55 AM 08/07/2018
Misc
Carried Forward
08/07/2018
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
08/07/2018
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. CHECK ALL.
Misc
Corrective Action Required
08/07/2018
MOUNT ACCESSIBLE RESTROOM SIGNS AT 5'-0 A.F.F.TO CENTER OF SIGN
Misc
Corrective Action Required
08/07/2018
ICC A117.1 ACCESSIBLE WATER CLOSET DISTANCE FROM WALL: ALLOWABLE RANGE IS 16"-18".
Misc
Corrective Action Required
08/07/2018
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
08/07/2018
WATER CLOSETS AND JANITOR FLOOR SINK MUST BE SEALED TO FLOOR & WALL
Misc
Corrective Action Required
08/07/2018
IPC 504.6; IRC P2803.6 WATER HEATER TEMPERATURE/PRESSURE RELIEF DISCHARGE PIPING: TERMINATE <= 6" ABOVE FLOOR OR WASTE RECEPTOR.
Occupancy Inspection - Fire Passed 8/7/2018 08/07/2018
Miscellaneous Inspection Passed 8/7/2018 08/07/2018
Occupancy Inspection - Codes Commercial Temporary C of O 8/8/2018 8/8/2018 at 1:30 PM 08/08/2018
Misc
Resolved
08/08/2018
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. CHECK ALL.
Misc
Resolved
08/08/2018
MOUNT ACCESSIBLE RESTROOM SIGNS AT 5'-0 A.F.F.TO CENTER OF SIGN
Misc
Resolved
08/16/2018
ICC A117.1 ACCESSIBLE WATER CLOSET DISTANCE FROM WALL: ALLOWABLE RANGE IS 16"-18".
Misc
Resolved
08/08/2018
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Resolved
08/08/2018
WATER CLOSETS AND JANITOR FLOOR SINK MUST BE SEALED TO FLOOR & WALL
Misc
Resolved
08/08/2018
IPC 504.6; IRC P2803.6 WATER HEATER TEMPERATURE/PRESSURE RELIEF DISCHARGE PIPING: TERMINATE <= 6" ABOVE FLOOR OR WASTE RECEPTOR.
Misc
Resolved
08/16/2018
Occupancy Inspection - Codes Commercial Temporary C of O 8/16/2018 at 3:00 PM 08/16/2018
Misc
Resolved
08/16/2018
ICC A117.1 ACCESSIBLE WATER CLOSET DISTANCE FROM WALL: ALLOWABLE RANGE IS 16"-18".
Misc
Corrective Action Required
08/16/2018
WC AT WOMEN'S RR NEEDS TO BE RE-SEALED TO FLOOR AFTER CLEARANCE ADJUSTMENT.
Occupancy Inspection - Codes Commercial Full C of O 8/23/2018 at 2:15 PM 08/23/2018
Misc
Resolved
08/23/2018
WC AT WOMEN'S RR NEEDS TO BE RE-SEALED TO FLOOR AFTER CLEARANCE ADJUSTMENT.
Documents & Images
Date Uploaded File Type Document Name
05/08/2018 Letter Fire Building Plan Review
05/08/2018 Letter Codes P/R Corrections Document
05/16/2018 Letter Fire Building Plan Review
05/21/2018 New Food Establishment Plan Review - Approved FTG 0001631
05/24/2018 Receipt Receipt for transaction: 2018-003070
05/24/2018 Letter Codes Building Permit
05/24/2018 Letter Codes Plan Review Conditions
07/05/2018 Letter Inspection Summary
07/06/2018 Letter Inspection Summary
07/10/2018 Letter Inspection Summary
07/10/2018 Letter Inspection Summary
07/25/2018 Letter Inspection Summary
07/30/2018 Letter Fire (Sprinkler) Plan Review
08/01/2018 Letter Inspection Summary
08/07/2018 Letter Inspection Summary
08/08/2018 Letter Codes Temporary Certificate of Occupancy
08/16/2018 Letter Codes Temporary Certificate of Occupancy
08/23/2018 Letter Field Certificate of Occupancy
08/24/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home