Permit Application Status

PRCOM20181345


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20181345
Building Permit - Commercial
Certificate of Occupancy
MCINTOSH JAMES F & DENISE D
CHANGE OF TENANT
EXPANSION OF EXISTING BUSINESS, MEDIQUICK AESTHETICS SPA, TO PROVIDE CLIENT CONSULTATION
05/02/2018
06/22/2018
12/09/2018
08/14/2018
Locations
Contacts
MCINTOSH JAMES F & DENISE D, Address:PO BOX 820  
COUNTRYSIDE HOME REPAIRS LLC, Address:620 N FOREST AVE, Phone:(816) 588-5733  
A3G , Address:15 SOUTH MAIN ST, Phone:(816) 581-6333  
C H ELECTRIC & TECHNOLOGY, Address:PO BOX 1984, Phone:(816) 365-7650  
NICK TRIANO PLUMBING LLC, Address:1650 MADISON AVE, Phone:(816) 550-4629  
MD REPAIR, Address:7901 S PARRENT RD, Phone:(816) 690-7985  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 06/28/2018 06/21/2018
Joe Frogge
Address numbers required
Corrective Action Required
06/21/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(VERIFIED AT INSPECTION) All doors shall be addressed and be readable from the roadway
Misc
Corrective Action Required
06/21/2018

Door operations ACTION REQUIRED:(VERIIFED AT INSPECTION) No keyed locks on the egress side of an exit
Building Plan Review Approved with Conditions 06/28/2018 06/21/2018
Joe Frogge
License Tax Application
Corrective Action Required
06/21/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
06/21/2018

Insufficient information to complete review. Provide the following: - - Pipe material schedule 6/12/18 - specify NG piping - HVAC design 6/12/18 - provide design for combustion air intake and ventilation at water heater. Also, water heater specified is 6' tall - how can this be installed above mop sink? -
Licensed Contractors Approved 06/21/2018 06/21/2018
Joe Frogge
Building Plan Review Rejected 06/18/2018 06/12/2018
Joe Frogge
License Tax Application
Corrective Action Required
06/11/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Plumb - Minimum number of fixtures 403.1
Resolved
06/12/2018

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Modify design to provide mop sink which is required due to floor material. 6/12/18 - mop sink provided
Misc
Corrective Action Required
06/11/2018

Insufficient information to complete review. Provide the following: - - Pipe material schedule 6/12/18 - specify NG piping - HVAC design 6/12/18 - provide design for combustion air intake and ventilation at water heater. Also, water heater specified is 6' tall - how can this be installed above mop sink? -
Misc
Resolved
06/12/2018

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Comment is for informational purposes. Consultation rooms appear configured for possible patient care which would not be allowed without compliance to this electrical code section.
Licensed Contractors Approved 06/18/2018 06/12/2018
Joe Frogge
Fire Plan Review Approved with Conditions 06/18/2018 06/11/2018
Joe Dir
Address numbers required
Corrective Action Required
06/11/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(VERIFIED AT INSPECTION) All doors shall be addressed and be readable from the roadway
Misc
Corrective Action Required
06/11/2018

Door operations ACTION REQUIRED:(VERIIFED AT INSPECTION) No keyed locks on the egress side of an exit
Licensed Contractors Rejected 05/02/2018 05/08/2018
Joe Frogge
LC - MEP Subs
Resolved
06/11/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Mechanical contractor. (each new office requires supply and return air - seems unlikely that existing system will work without modifications)
Building Plan Review Rejected 05/14/2018 05/08/2018
Joe Frogge
License Tax Application
Corrective Action Required
05/08/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
05/08/2018

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Modify design to provide mop sink which is required due to floor material.
Misc
Corrective Action Required
05/08/2018

Insufficient information to complete review. Provide the following: - Electrical specifications - Pipe material schedule - HVAC design - Clarify use of drain pumps. (gravity drains must be used if available - even if you must cut into concrete)
Misc
Corrective Action Required
05/08/2018

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Comment is for informational purposes. Consultation rooms appear configured for possible patient care which would not be allowed without compliance to this electrical code section.
Fire Plan Review Approved with Conditions 05/14/2018 05/08/2018
Joe Dir
Address numbers required
Corrective Action Required
05/08/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: All doors shall be addressed and be readable from the roadway
Misc
Corrective Action Required
05/08/2018

Door operations ACTION REQUIRED:No keyed locks on the egress side of an exit [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $102.13 $102.13 Paid 06/22/2018
8331507-Sewer Connection Fee $180.00 $180.00 Paid 06/22/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Partial 6/19/2018 at 8:30 AM 06/19/2018
Underslab Plumbing Inspection - Commercial Passed 6/26/2018 6/26/2018 at 7:55 AM 06/26/2018
Occupancy Inspection - Codes Commercial Failed 8/13/2018 8/13/2018 at 9:30 AM 08/13/2018
Misc
Corrective Action Required
08/13/2018
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT SECURED SOLID TO BOX. ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE. CHECK ALL.
Misc
Corrective Action Required
08/13/2018
IN MECHANICAL ROOM SECURE MC ELECT CABLE TO WALL
Occupancy Inspection - Fire Passed 8/13/2018 08/13/2018
Occupancy Inspection - Codes Commercial Full C of O 8/14/2018 8/14/2018 at 10:40 AM 08/14/2018
Misc
Resolved
08/14/2018
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT SECURED SOLID TO BOX. ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE. CHECK ALL.
Misc
Resolved
08/14/2018
IN MECHANICAL ROOM SECURE MC ELECT CABLE TO WALL
Documents & Images
Date Uploaded File Type Document Name
05/08/2018 Letter Fire Building Plan Review
05/08/2018 Letter Codes P/R Corrections Document
06/11/2018 Letter Fire Building Plan Review
06/12/2018 Letter Codes P/R Corrections Document
06/21/2018 Letter Codes Plan Review Conditions
06/22/2018 Receipt Receipt for transaction: 2018-004118
06/22/2018 Letter Codes Building Permit
06/26/2018 Letter Inspection Summary
07/10/2018 Letter Inspection Summary
07/10/2018 wh letter
08/13/2018 Letter Inspection Summary
08/14/2018 Letter Field Certificate of Occupancy
08/15/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home