Permit Application Status

PRCOM20180443


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20180443
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEV INC
CHANGE OF TENANT
TENANT FINISH FOR BAKERY *drawing is in plan review file
02/27/2018
03/12/2018
08/27/2018
04/13/2018
Locations
Contacts
COOKIE JAR BAKERY, Address:1005 SE 2ND TER , Phone:(816) 347-9147  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
JJJ'S ELECTRICAL INC, Address:P O BOX 1811, Phone:(816) 853-6625  
PROLINE PLUMBING, Address:2020 SW HUNTBROOK TER, Phone:(816) 442-9653  
LANGSFORD DEV INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 03/14/2018 03/12/2018
Joe Frogge
Misc
Resolved
03/07/2018

2012 IBC 1103.1 (Accessibility) Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Existing restroom to be as accessible as practical. At a minimum, provide grab bars, adjust toilet & sink heights, protect piping under sink, etc. (this is not an all-inclusive list - reference 2009 ICC/ANSI A117.1) To be field verified during inspections.
Health Dept Inspection
Corrective Action Required
03/07/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Plumb - Indirect/Special Waste - Where required 802.1
Resolved
03/07/2018

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Provide indirect drains at 3-compartment sink. To be field verified.
Misc
Corrective Action Required
03/07/2018

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: All receptacles in kitchen area and within 6' of sinks (or similar) to be GFCI protected. 3/7/18 - some, but not all receptacles have been designated as GFCI. To be field verified.
Mech - Commercial kitchen hoods - Where required 507.2
Resolved
03/12/2018

2012 IMC 507.2 Where Required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. Action required: Provide verification that oven does not require a hood. 3/12/18 - This oven was approved under previous project.
Misc
Resolved
03/07/2018

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Exception: Public toilet facilities shall not be required for: 1. Parking garages where operated without parking attendants. 2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet. Action required: Modify design to demonstrate that public access area is less than or equal to 300 square feet in order to qualify for the exception that allows you to not provide restroom to patrons. (fyi - access through kitchen wouldn't be allowed either per 2902.3.1)
Misc
Corrective Action Required
03/07/2018

MEP (hvac, electrical, plumbing) designs not provided. Action required: Provide complete MEP design or detailed scopes of work from licensed professionals. 3/7/18 - not completely addressed. - provide pipe material schedule. To be field verified.
Misc
Corrective Action Required
03/12/2018

2012 IBC 1210.4 Toilet room location. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public. Action required: toilet room is not allowed to open into kitchen. 2/12/18 - CMR will be applied for.
Fire Plan Review Approved with Conditions 03/14/2018 03/08/2018
Joe Dir
Address numbers required
Corrective Action Required
03/07/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Numeric (120) address shall be readable from the roadway
Portable fire extinguishers - general
Corrective Action Required
03/07/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of one 2A-10BC fire extinguisher. Extinguisher to be mounted on a wall on a normal path of travel close to an exit.
Misc
Corrective Action Required
03/07/2018

Door operation ACTION REQUIRED:(verified at inspection) No keyed locks on the egress side of an exit [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Resolved
03/08/2018

Baking oven ACTION REQUIRED: Provide manufacturers information on the type of baking oven to be utilized.
Misc
Resolved
03/08/2018

Health Dept ACTION REQUIRED: Helath Dept inspection will be required prior to opening to the public.
Licensed Contractors Approved 03/07/2018 03/07/2018
Joe Frogge
LC - MEP Subs
Resolved
03/07/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Rejected 03/09/2018 02/28/2018
Joe Frogge
Mech - Outdoor air required 403.2
Resolved
02/28/2018

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action Required: Revise drawings to show outside air calculations as well as method of delivery. (this can be provided by your mechanical contractor)
Misc
Corrective Action Required
02/28/2018

2012 IBC 1103.1 (Accessibility) Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Existing restroom to be as accessible as practical. At a minimum, provide grab bars, adjust toilet & sink heights, protect piping under sink, etc. (this is not an all-inclusive list - reference 2009 ICC/ANSI A117.1) To be field verified during inspections.
Health Dept Review
Corrective Action Required
02/28/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required: This comment is for information purposes.
Plumb - Indirect/Special Waste - Where required 802.1
Corrective Action Required
02/28/2018

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Provide indirect drains at 3-compartment sink. To be field verified.
Misc
Corrective Action Required
02/28/2018

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: All receptacles in kitchen area and within 6' of sinks (or similar) to be GFCI protected.
Mech - Commercial kitchen hoods - Where required 507.2
Corrective Action Required
02/28/2018

2012 IMC 507.2 Where Required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. Action required: Provide verification that oven does not require a hood.
Misc
Corrective Action Required
02/28/2018

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Exception: Public toilet facilities shall not be required for: 1. Parking garages where operated without parking attendants. 2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet. Action required: Modify design to demonstrate that public access area is less than or equal to 300 square feet in order to qualify for the exception that allows you to not provide restroom to patrons. (fyi - access through kitchen wouldn't be allowed either per 2902.3.1)
Misc
Corrective Action Required
02/28/2018

MEP (hvac, electrical, plumbing) designs not provided. Action required: Provide complete MEP design or detailed scopes of work from licensed professionals.
Fire Plan Review Rejected 03/09/2018 02/28/2018
Joe Dir
Address numbers required
Corrective Action Required
02/28/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Numeric (120) address shall be readable from the roadway
Portable fire extinguishers - general
Corrective Action Required
02/28/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of one 2A-10BC fire extinguisher. Extinguisher to be mounted on a wall on a normal path of travel close to an exit.
Misc
Corrective Action Required
02/28/2018

Door operation ACTION REQUIRED:No keyed locks on the egress side of an exit [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Corrective Action Required
02/28/2018

Baking oven ACTION REQUIRED: Provide manufacturers information on the type of baking oven to be utilized.
Misc
Corrective Action Required
02/28/2018

Health Dept ACTION REQUIRED: Helath Dept inspection will be required prior to opening to the public.
Licensed Contractors Rejected 02/27/2018 02/27/2018
Joe Frogge
LC - MEP Subs
Corrective Action Required
02/27/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Health Department Review Approved 02/27/2018
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.00 $30.00 Paid 03/12/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Not Ready 3/20/2018 3/20/2018 at 8:25 AM 03/20/2018
In-wall Inspection Passed 3/20/2018 at 1:05 PM 03/20/2018
Occupancy Inspection - Fire Passed 4/13/2018 04/13/2018
Occupancy Inspection - Codes Commercial Full C of O 4/13/2018 4/13/2018 04/13/2018
Documents & Images
Date Uploaded File Type Document Name
02/27/2018 New Food Establishment Plan Review - Approved FTG 0001469
02/28/2018 Letter Fire Building Plan Review
02/28/2018 Letter Codes P/R Corrections Document
03/08/2018 Letter Fire Building Plan Review
03/12/2018 Letter Codes Plan Review Conditions
03/12/2018 Receipt Receipt for transaction: 2018-000892
03/12/2018 Letter Codes Building Permit
03/13/2018 CMR
03/20/2018 Letter Inspection Summary
04/13/2018 Letter Codes Final Certificate of Occupancy
04/13/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home