Permit Application Status

PRCOM20173847


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20173847
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
CHANGE OF TENANT
TENANT FINISH FOR SMOOTHIE CAFE (DEMISING WALL UNDER PERMIT PRCOM20173344)
11/27/2017
01/12/2018
05/29/2018
04/24/2018
Locations
Contacts
RIVER OAK CONSTRUCTION INC, Address:3810 NE BEECHWOOD DR, Phone:(816) 525-2100  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
RES MECHANICAL, Address:475 NW 400TH RD, Phone:(816) 600-4416  
HIRST & ASSOCIATES PC, Address:3810 NE BEECHWOOD DR, Phone:(816) 225-2550  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/08/2018
Joe Dir
Installation acceptance testing
Corrective Action Required
03/08/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the isolation valves and flow valves shall be required prior to the final ocupancy inspecion. All valves shall be addressed with the suites designation, readable from the floor.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/08/2018

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(verified at inspection) The current fire sprinkler system riser shall be current with all service/maintenance. A current service tag shall be posted on the systems riser.
Licensed Contractors Approved 12/04/2017 01/12/2018
Development Center
LC - General Contractor
Resolved
01/12/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
01/12/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 12/11/2017 12/20/2017
Joe Frogge
License Tax Application
Corrective Action Required
12/04/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
12/20/2017

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
12/04/2017

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Mech - Materials within plenums 602.2.1
Resolved
12/04/2017

2012 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC is not allowed in plenums. Update spec and/or update plumbing drawings.
Misc
Resolved
12/04/2017

Inadequate information to complete review. Provide the following: - Specify water piping material. - Specify wall construction. - Specify wall blocking material.
Health Department Review Approved 12/07/2017 12/20/2017
Joe Frogge
Fire Plan Review Approved with Conditions 12/11/2017 12/06/2017
Joe Dir
Posting of occupant load
Corrective Action Required
12/04/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) Post the occupant of 19.
Construction documents for fire alarm systems
Corrective Action Required
12/04/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Any fire alarm system devices that are disconnected, relocated, installed new are required to be tested prior to the final occupancy inspection. Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
12/04/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address the front and rear doos with the suite designation. Adress shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
12/04/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(Information purposes) Demising wall and tenant finish will require fire sprinkler modification. Have the fire sprinkler system contractor provide shop drawings of any modifiaction to be done to the fire sprinkler asystem.
Installation acceptance testing
Corrective Action Required
12/04/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Testing of the fire alarm system modification will be required prior to the final occupancy inspection.
Portable fire extinguishers - general
Corrective Action Required
12/04/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide 0ne 2A-10BC fire extinguisher to be mounted on a normal path of travel close to an exit.
Fire Plan Review Approved with Conditions 12/07/2017 11/30/2017
Joe Dir
Posting of occupant load
Corrective Action Required
11/30/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) Post the occupant of 19.
Construction documents for fire alarm systems
Corrective Action Required
11/30/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Any fire alarm system devices that are disconnected, relocated, installed new are required to be tested prior to the final occupancy inspection. Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
11/30/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address the front and rear doos with the suite designation. Adress shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
11/30/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(Information purposes) Demising wall and tenant finish will require fire sprinkler modification. Have the fire sprinkler system contractor provide shop drawings of any modifiaction to be done to the fire sprinkler asystem.
Installation acceptance testing
Corrective Action Required
11/30/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Testing of the fire alarm system modification will be required prior to the final occupancy inspection.
Portable fire extinguishers - general
Corrective Action Required
11/30/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide 0ne 2A-10BC fire extinguisher to be mounted on a normal path of travel close to an exit.
Building Plan Review Rejected 12/07/2017 11/29/2017
Joe Frogge
License Tax Application
Corrective Action Required
11/29/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
11/29/2017

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
11/29/2017

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
11/29/2017

Demising wall is being installed under separate contract. Action required: Comment is for informational purposes. This permit cannot be closed until demising wall permit (PRCOM20173344) is also closed.
Mech - Materials within plenums 602.2.1
Corrective Action Required
11/29/2017

2012 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC is not allowed in plenums. Update spec and/or update plumbing drawings.
Misc
Corrective Action Required
11/29/2017

Inadequate information to complete review. Provide the following: - Specify water piping material. - Specify wall construction. - Specify wall blocking material.
Licensed Contractors Rejected 12/07/2017 11/29/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
11/29/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/29/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $163.40 $163.40 Paid 01/12/2018
8331507-Sewer Connection Fee $360.00 $360.00 Paid 01/12/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 2/9/2018 2/9/2018 at 9:10 AM 02/09/2018
Underslab Plumbing Inspection - Commercial Passed 2/12/2018 2/12/2018 at 9:05 AM 02/12/2018
Misc
Resolved
02/12/2018
NO PERMIT PRINTS ON SITE
Misc
Resolved
02/12/2018
In-wall Inspection Passed 2/22/2018 2/23/2018 at 1:40 PM 02/23/2018
Miscellaneous Inspection Partial 3/12/2018 at 9:55 AM 03/12/2018
Miscellaneous Inspection Partial 3/16/2018 at 10:15 AM 03/16/2018
Above Ceiling Inspection Failed 4/4/2018 4/4/2018 at 3:15 PM 04/04/2018
Miscellaneous Correction
Corrective Action Required
04/04/2018
DEMO INCOMPLETE: - REMOVE ABANDONED LIGHT-GAUGE STEEL FRAMING (TRACK SCREWED TIGHT TO ROOF DECK OK) - REMOVE ABANDONED STRAP HANGERS (WIRE OK)
Miscellaneous Correction
Corrective Action Required
04/04/2018
SUPPORT LOW-VOLTAGE CABLE TO STRUCTURE -- NOT TO OTHER MEP SYSTEMS
Miscellaneous Correction
Corrective Action Required
04/04/2018
MC ELECT CABLE TO BE SUPPORTED BY DEDICATED SLACK WIRES -- NO CEILING SUPPORT WIRES
Miscellaneous Correction
Corrective Action Required
04/04/2018
HVAC FLEX DUCT TO BE SUPPORTED WITH STRAP HANGERS -- NOT BY SPRINKLER PIPE OR OTHER MEP
Above Ceiling Inspection Passed 4/6/2018 at 10:25 AM 04/06/2018
Miscellaneous Correction
Resolved
04/06/2018
DEMO INCOMPLETE: - REMOVE ABANDONED LIGHT-GAUGE STEEL FRAMING (TRACK SCREWED TIGHT TO ROOF DECK OK) - REMOVE ABANDONED STRAP HANGERS (WIRE OK)
Miscellaneous Correction
Resolved
04/06/2018
SUPPORT LOW-VOLTAGE CABLE TO STRUCTURE -- NOT TO OTHER MEP SYSTEMS
Miscellaneous Correction
Resolved
04/06/2018
MC ELECT CABLE TO BE SUPPORTED BY DEDICATED SLACK WIRES -- NO CEILING SUPPORT WIRES
Miscellaneous Correction
Resolved
04/06/2018
HVAC FLEX DUCT TO BE SUPPORTED WITH STRAP HANGERS -- NOT BY SPRINKLER PIPE OR OTHER MEP
Miscellaneous Inspection Passed 4/6/2018 04/06/2018
Alarm Test Passed 4/20/2018 04/20/2018
Occupancy Inspection - Fire Passed 04/20/2018
Misc
Corrective Action Required
02/09/2018
NO PERMIT PRINTS ON SITE
Occupancy Inspection - Codes Commercial Temporary C of O 4/19/2018 4/20/2018 at 12:00 PM 04/20/2018
Misc
Corrective Action Required
04/20/2018
-ADJUST BATHROOM DOOR CLOSER -HANG ACCESSABLE BATHROOM SIGN
Occupancy Inspection - Codes Commercial Full C of O 4/24/2018 4/24/2018 at 9:45 AM 04/24/2018
Misc
Resolved
04/24/2018
-ADJUST BATHROOM DOOR CLOSER -HANG ACCESSABLE BATHROOM SIGN
Documents & Images
Date Uploaded File Type Document Name
11/30/2017 Letter Codes P/R Corrections Document
11/30/2017 Letter Fire Building Plan Review
12/06/2017 Letter Fire Building Plan Review
12/20/2017 New Food Establishment Plan Review - Approved FTG 0001817
01/12/2018 Letter Codes Plan Review Conditions
01/12/2018 Receipt Receipt for transaction: 2018-000136
01/12/2018 Letter Codes Building Permit
02/09/2018 Letter Inspection Summary
02/12/2018 Letter Inspection Summary
02/23/2018 Letter Inspection Summary
03/08/2018 Letter Fire (Sprinkler) Plan Review
03/09/2018 Letter Fire (Alarm) Plan Review Notice
04/04/2018 Letter Inspection Summary
04/06/2018 Letter Inspection Summary
04/20/2018 Letter Codes Temporary Certificate of Occupancy
04/24/2018 Letter Field Certificate of Occupancy
04/25/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home