Summary
PRCOM20171543
Building Permit - Commercial
Certificate of Occupancy
NEWTON MARILYN S-TRUSTEE
NEW COMMERCIAL
NEW OFFICE BUILDING TO REPLACE BUILDING DESTROYED IN STORM **planning dept rqd at final to verify screening
05/15/2017
09/14/2017
03/12/2018
12/12/2017
Locations
Contacts
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
PM CONTRACTING INC, Address:4015 E 143RD ST, Phone:(816) 318-9844  
ELDECON INC, Address:120 SE 30TH ST, Phone:(660) 553-1121  
SHE DIGS IT LLC, Address:600 SE CENTRAL DR, Phone:(816) 295-1100  
CL ARCHITECTURE (CRAIG LUEBBERT), Address:396 SW WINTERGARDEN, Phone:(816) 536-3472  
NEWTON MARILYN S-TRUSTEE, Address:2013 NW N ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/13/2017 09/13/2017
Joe Frogge
Building Plan Review Approved with Conditions 09/20/2017 09/13/2017
Joe Frogge
License Tax Application
Corrective Action Required
09/13/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Misc
Corrective Action Required
09/13/2017

There is an open demolition permit for this property. Action required: Comment is for informational purposes. No type of occupancy to be granted until after the demolition permit has been closed.
Misc
Corrective Action Required
09/13/2017

2011 NEC 334.80 Ampacity. The ampacity of Types NM, NMC, and NMS cable shall be determined in accordance with 310.15. The allowable ampacity shall not exceed that of a 60degC (140degF) rated conductor. The 90degC (194degF) rating shall be permitted to be used for ampacity adjustment and correction calculations, provided the final derated ampacity does not exceed that of a 60degC (140degF) rated conductor. The ampacity of Types NM, NMC, and NMS cable installed in cable tray shall be determined in accordance with 395.80(A). (see code for additional requirements) Action required: Comment is for informational purposes. Wiring in attic must be derated for temperature. To be field verified.
Engineered truss package
Corrective Action Required
09/13/2017

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 9/5/17 - deferred per request
Misc
Corrective Action Required
09/13/2017

Rooms 102 & 105 do not have return air. Action required: Provide return air from rooms 102 & 105. 9/5/17 - return air shown to be "booted" but with no other installation direction. If the boot transfers to plenum then the gas fired appliances will not be allowed. Field verify that area above lay-in ceiling is not used as a plenum
Fire Plan Review Approved with Conditions 09/20/2017 09/13/2017
Joe Frogge
Address numbers required
Corrective Action Required
09/13/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) If not existing, address shall be readable from the roadway (Chipman Road)
Portable fire extinguishers - general
Corrective Action Required
09/13/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one (5 pound) 2A-10BC fire extinguisher to be mounted on a normal path of travel close to an exit.
Licensed Contractors Approved 08/30/2017 09/13/2017
Joe Frogge
LC - MEP Subs
Resolved
09/13/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 09/07/2017 09/11/2017
Joe Frogge
Address numbers required
Corrective Action Required
08/30/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) If not existing, address shall be readable from the roadway (Chipman Road)
Portable fire extinguishers - general
Corrective Action Required
08/30/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one (5 pound) 2A-10BC fire extinguisher to be mounted on a normal path of travel close to an exit.
Misc
Resolved
09/01/2017

Egress illumination [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. [B] 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface. ACTION REQUIRED: Provide emergency lighting to the front exterior stairs, ramp and exterior stairs from the basement.
Building Plan Review Rejected 09/07/2017 09/05/2017
Joe Frogge
License Tax Application
Corrective Action Required
08/30/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Misc
Corrective Action Required
08/30/2017

There is an open demolition permit for this property. Action required: Comment is for informational purposes. No type of occupancy to be granted until after the demolition permit has been closed.
Bldg - Safety glazing - Hazardous locations 2406.4
Resolved
09/05/2017

2012 IBC 2406.4 - Hazardous locations. The locations specified in Sections 2406.4.1 through 2406.4.7 shall be considered specific hazardous locations requiring safety glazing materials. Action required: Window out of room 102 at exterior stair must be tempered if within 60" of steps below. Field verify.
Misc
Corrective Action Required
08/30/2017

2011 NEC 334.80 Ampacity. The ampacity of Types NM, NMC, and NMS cable shall be determined in accordance with 310.15. The allowable ampacity shall not exceed that of a 60degC (140degF) rated conductor. The 90degC (194degF) rating shall be permitted to be used for ampacity adjustment and correction calculations, provided the final derated ampacity does not exceed that of a 60degC (140degF) rated conductor. The ampacity of Types NM, NMC, and NMS cable installed in cable tray shall be determined in accordance with 395.80(A). (see code for additional requirements) Action required: Comment is for informational purposes. Wiring in attic must be derated for temperature. To be field verified.
Misc
Resolved
09/05/2017

2011 NEC Article 250.24 Grounding Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor, at each service, in accordance with 250.24(A)(1) through (A)(5). (1) General. The grounding electrode conductor connection shall be made at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. Action required: Update electrical riser diagram to show grounding electrode conductors (complete with wire size) to rod and water piping.
Misc
Resolved
09/05/2017

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Receptacles in basement to be GFCI protected. (unfinished concrete areas are considered to be "wet" locations.)
Engineered truss package
Corrective Action Required
08/30/2017

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 9/5/17 - deferred per request
Bldg - Handrail extensions 1012.6
Resolved
09/13/2017

2012 IBC 1012.6 – Handrail extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight or ramp run. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continuous to slope for the depth of one tread beyond the bottom riser. At ramps where handrails are not continuous between runs, the handrails shall extend horizontally above the landing 12 inches minimum beyond the top and bottom of ramp runs. The extensions of handrails shall be in the same direction of the stair flights at stairways and the ramp runs at ramps. (See code section for possible exceptions.) Action required: Modify detail 5/A3.0 to demonstrate compliance. 9/5/17 - handrails must return to a wall or newel post.
Misc
Resolved
09/05/2017

Attic access is immediately beneath attic mounted furnace. Action required: Modify plans.
Misc
Resolved
09/05/2017

Furnaces are shown in basement and attic. Also, they are shown with 2 different BTU inputs. Action required: Modify plans to clarify.
Misc
Corrective Action Required
08/30/2017

Rooms 102 & 105 do not have return air. Action required: Provide return air from rooms 102 & 105. 9/5/17 - return air shown to be "booted" but with no other installation direction. If the boot transfers to plenum then the gas fired appliances will not be allowed. Field verify that area above lay-in ceiling is not used as a plenum
Building Plan Review Rejected 08/30/2017 08/23/2017
Joe Frogge
License Tax Application
Corrective Action Required
08/18/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Misc
Corrective Action Required
08/18/2017

There is an open demolition permit for this property. Action required: Comment is for informational purposes. No type of occupancy to be granted until after the demolition permit has been closed.
Bldg - Safety glazing - Hazardous locations 2406.4
Corrective Action Required
08/18/2017

2012 IBC 2406.4 - Hazardous locations. The locations specified in Sections 2406.4.1 through 2406.4.7 shall be considered specific hazardous locations requiring safety glazing materials. Action required: Window out of room 102 at exterior stair must be tempered if within 60" of steps below. Field verify.
Misc
Corrective Action Required
08/18/2017

2011 NEC 334.80 Ampacity. The ampacity of Types NM, NMC, and NMS cable shall be determined in accordance with 310.15. The allowable ampacity shall not exceed that of a 60degC (140degF) rated conductor. The 90degC (194degF) rating shall be permitted to be used for ampacity adjustment and correction calculations, provided the final derated ampacity does not exceed that of a 60degC (140degF) rated conductor. The ampacity of Types NM, NMC, and NMS cable installed in cable tray shall be determined in accordance with 395.80(A). (see code for additional requirements) Action required: Comment is for informational purposes. Wiring in attic must be derated for temperature. To be field verified.
Misc
Corrective Action Required
08/18/2017

2011 NEC Article 250.24 Grounding Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor, at each service, in accordance with 250.24(A)(1) through (A)(5). (1) General. The grounding electrode conductor connection shall be made at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. Action required: Update electrical riser diagram to show grounding electrode conductors (complete with wire size) to rod and water piping.
Misc
Corrective Action Required
08/18/2017

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Receptacles in basement to be GFCI protected. (unfinished concrete areas are considered to be "wet" locations.)
Engineered truss package
Corrective Action Required
08/23/2017

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral.
Bldg - Handrail extensions 1012.6
Corrective Action Required
08/23/2017

2012 IBC 1012.6 – Handrail extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight or ramp run. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continuous to slope for the depth of one tread beyond the bottom riser. At ramps where handrails are not continuous between runs, the handrails shall extend horizontally above the landing 12 inches minimum beyond the top and bottom of ramp runs. The extensions of handrails shall be in the same direction of the stair flights at stairways and the ramp runs at ramps. (See code section for possible exceptions.) Action required: Modify detail 5/A3.0 to demonstrate compliance.
Misc
Corrective Action Required
08/23/2017

Attic access is immediately beneath attic mounted furnace. Action required: Modify plans.
Misc
Corrective Action Required
08/23/2017

Furnaces are shown in basement and attic. Also, they are shown with 2 different BTU inputs. Action required: Modify plans to clarify.
Misc
Corrective Action Required
08/23/2017

Rooms 102 & 105 do not have return air. Action required: Provide return air from rooms 102 & 105.
Fire Plan Review Approved with Conditions 08/30/2017 08/23/2017
Joe Dir
Address numbers required
Corrective Action Required
08/18/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) If not existing, address shall be readable from the roadway (Chipman Road)
Portable fire extinguishers - general
Corrective Action Required
08/18/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one (5 pound) 2A-10BC fire extinguisher to be mounted on a normal path of travel close to an exit.
Misc
Corrective Action Required
08/18/2017

Egress illumination [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. [B] 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface. ACTION REQUIRED: Provide emergency lighting to the front exterior stairs, ramp and exterior stairs from the basement.
Misc
Resolved
08/23/2017

Front casement windows project into ramp. [B] 1008.1.1.1 Projections into clear width. There shall not be projections into the required clear width lower than 34 inches (864 mm) above the floor or ground. Projections into the clear opening width between 34 inches (864 mm) and 80 inches (2032 mm) above the floor or ground shall not exceed 4 inches (102 mm). [B] 1010.6 Minimum dimensions. The minimum dimensions of means of egress ramps shall comply with Sections 1010.6.1 through 1010.6.3. [B] 1010.6.1 Width. The minimum width of a means of egress ramp shall not be less than that required for corridors by Section 1018.2. The clear width of a ramp between handrails, if provided, or other permissible projections shall be 36 inches (914 mm) minimum. [B] 1010.6.2 Headroom. The minimum headroom in all parts of the means of egress ramp shall not be less than 80 inches (2032 mm). [B] 1010.6.3 Restrictions. Means of egress ramps shall not reduce in width in the direction of egress travel. Projections into the required ramp and landing width are prohibited. Doors opening onto a landing shall not reduce the clear width to less than 42 inches (1067 mm). [B] 1010.7 Landings. Ramps shall have landings at the bottom and top of each ramp, points of turning, entrance, exits and at doors. Landings shall comply with Sections 1010.7.1 through 1010.7.5. [B] 1010.7.1 Slope. Landings shall have a slope not steeper than one unit vertical in 48 units horizontal (2-percent slope) in any direction. Changes in level are not permitted. [B] 1010.7.2 Width. The landing shall be at least as wide as the widest ramp run adjoining the landing. [B] 1010.7.3 Length. The landing length shall be 60 inches (1525 mm) minimum. Exceptions: 1. In Group R-2 and R-3 individual dwelling and sleeping units that are not required to be Accessible units, Type A units or Type B units in accordance with Section 1107, landings are permitted to be 36 inches (914 mm) minimum. 2. Where the ramp is not a part of an accessible route, the length of the landing shall not be required to be more than 48 inches (1219 mm) in the direction of travel. [B] 1010.7.4 Change in direction. Where changes in direction of travel occur at landings provided between ramp runs, the landing shall be 60 inches by 60 inches (1524 mm by 1524 mm) minimum. Exception: In Group R-2 and R-3 individual dwelling or sleeping units that are not required to be Accessible units, Type A units or Type B units in accordance with Section 1107 of the International Building Code, landings are permitted to be 36 inches by 36 inches (914 mm by 914 mm) minimum. ACTION REQUIRED: Ramp has to meet requirments for access and egress.
Licensed Contractors Rejected 08/18/2017 08/18/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
08/18/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Rejected 05/30/2017 05/24/2017
Joe Frogge
License Tax Application
Corrective Action Required
05/24/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Misc
Corrective Action Required
05/24/2017

There is an open demolition permit for this property. Action required: Comment is for informational purposes. No type of occupancy to be granted until after the demolition permit has been closed.
Bldg - Safety glazing - Hazardous locations 2406.4
Corrective Action Required
05/24/2017

2012 IBC 2406.4 - Hazardous locations. The locations specified in Sections 2406.4.1 through 2406.4.7 shall be considered specific hazardous locations requiring safety glazing materials. Action required: Glazing at window 'F' must be tempered.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
05/24/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of women's restroom door #107.
Misc
Corrective Action Required
05/24/2017

Sec. 7-802. - Residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: A. Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of R-13. This requirement does not apply to doors, windows, or other openings or approved penetrations nor does it apply to basement concrete walls when the basement is not finished as a habitable space. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Garage ceilings with living area above shall comply with this requirement. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. This requirement does not apply to skylights or other approved penetrations. D. Ceilings forming portions of a building envelope shall meet or exceed an R factor rating of thirty (30) at the time of installation. E. Duct insulation. All portions of the air distribution system shall be installed in accordance with Section M1601 and be insulated to an installed R-5 when system components are located within the building but outside of conditioned space, and R-8 when located outside of the building. When located within a building envelope assembly, at least R-8 shall be applied between the duct and that portion of the assembly furthest from conditioned space. (Ord. No. 7369, § 1, 10-3-2013) Sec. 7-803. - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: Exception: The Building Official may approve a decreased R-Value for building exterior walls provided the space is normally not occupied by employees and is associated with storage/warehouse or manufacturing. A. Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or other openings or approved penetrations nor does it apply to unfinished basement concrete walls. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor 19. (Ord. No. 7369, § 1, 10-3-2013) Action required: Comment is for informational purposes. While attic mounted ductwork is not specifically addressed in commercial applications, it stands to reason that this is the intent. Insulating the attic mounted ductwork is highly recommended.
Misc
Corrective Action Required
05/24/2017

2011 NEC 334.80 Ampacity. The ampacity of Types NM, NMC, and NMS cable shall be determined in accordance with 310.15. The allowable ampacity shall not exceed that of a 60degC (140degF) rated conductor. The 90degC (194degF) rating shall be permitted to be used for ampacity adjustment and correction calculations, provided the final derated ampacity does not exceed that of a 60degC (140degF) rated conductor. The ampacity of Types NM, NMC, and NMS cable installed in cable tray shall be determined in accordance with 395.80(A). (see code for additional requirements) Action required: Comment is for informational purposes. Wiring in attic must be derated for temperature. To be field verified.
Misc
Corrective Action Required
05/24/2017

2011 NEC Article 250.24 Grounding Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor, at each service, in accordance with 250.24(A)(1) through (A)(5). (1) General. The grounding electrode conductor connection shall be made at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. Action required: Update electrical riser diagram to show grounding electrode conductors (complete with wire size) to rod and water piping.
Misc
Corrective Action Required
05/24/2017

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Receptacles in basement to be GFCI protected. (unfinished concrete areas are considered to be "wet" locations.)
Licensed Contractors Rejected 05/15/2017 05/24/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/24/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 05/30/2017 05/18/2017
Joe Dir
Address numbers required
Corrective Action Required
05/18/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) If not existing, address shall be readable from the roadway (Chipman Road)
Portable fire extinguishers - general
Corrective Action Required
05/18/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one (5 pound) 2A-10BC fire extinguisher to be mounted on a normal path of travel close to an exit.
Misc
Corrective Action Required
05/18/2017

Egress illumination [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. [B] 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface. ACTION REQUIRED: Provide emergency lighting to the front exterior stairs, ramp and exterior stairs from the basement.
Misc
Corrective Action Required
05/18/2017

Front casement windows project into ramp. [B] 1008.1.1.1 Projections into clear width. There shall not be projections into the required clear width lower than 34 inches (864 mm) above the floor or ground. Projections into the clear opening width between 34 inches (864 mm) and 80 inches (2032 mm) above the floor or ground shall not exceed 4 inches (102 mm). [B] 1010.6 Minimum dimensions. The minimum dimensions of means of egress ramps shall comply with Sections 1010.6.1 through 1010.6.3. [B] 1010.6.1 Width. The minimum width of a means of egress ramp shall not be less than that required for corridors by Section 1018.2. The clear width of a ramp between handrails, if provided, or other permissible projections shall be 36 inches (914 mm) minimum. [B] 1010.6.2 Headroom. The minimum headroom in all parts of the means of egress ramp shall not be less than 80 inches (2032 mm). [B] 1010.6.3 Restrictions. Means of egress ramps shall not reduce in width in the direction of egress travel. Projections into the required ramp and landing width are prohibited. Doors opening onto a landing shall not reduce the clear width to less than 42 inches (1067 mm). [B] 1010.7 Landings. Ramps shall have landings at the bottom and top of each ramp, points of turning, entrance, exits and at doors. Landings shall comply with Sections 1010.7.1 through 1010.7.5. [B] 1010.7.1 Slope. Landings shall have a slope not steeper than one unit vertical in 48 units horizontal (2-percent slope) in any direction. Changes in level are not permitted. [B] 1010.7.2 Width. The landing shall be at least as wide as the widest ramp run adjoining the landing. [B] 1010.7.3 Length. The landing length shall be 60 inches (1525 mm) minimum. Exceptions: 1. In Group R-2 and R-3 individual dwelling and sleeping units that are not required to be Accessible units, Type A units or Type B units in accordance with Section 1107, landings are permitted to be 36 inches (914 mm) minimum. 2. Where the ramp is not a part of an accessible route, the length of the landing shall not be required to be more than 48 inches (1219 mm) in the direction of travel. [B] 1010.7.4 Change in direction. Where changes in direction of travel occur at landings provided between ramp runs, the landing shall be 60 inches by 60 inches (1524 mm by 1524 mm) minimum. Exception: In Group R-2 and R-3 individual dwelling or sleeping units that are not required to be Accessible units, Type A units or Type B units in accordance with Section 1107 of the International Building Code, landings are permitted to be 36 inches by 36 inches (914 mm by 914 mm) minimum. ACTION REQUIRED: Ramp has to meet requirments for access and egress.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $1,137.15 $1,137.15 Paid 09/14/2017
8331507-Sewer Connection Fee $240.00 $240.00 Paid 09/14/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 9/28/2017 9/28/2017 at 9:50 AM 09/28/2017
Misc
Corrective Action Required
09/28/2017
FLOOR FRAMING ABOVE BASEMENT ONLY-OK **NOTE: THE REST OF THE FLOOR ON THE NORTH SIDE OF THE BASEMENT WILL BE INSPECTED LATER PRIOR TO INSTALLING SUBFLOOR.
All Rough Inspection - Commercial Failed 10/3/2017 10/3/2017 at 4:50 PM 10/03/2017
Misc
Corrective Action Required
09/28/2017
FLOOR FRAMING ABOVE BASEMENT ONLY-OK FLOOR ON THE NORTH SIDE OF THE BASEMENT-TOE NAIL THE JOISTS TO SILL PLATES; HAVE THE STRUCTURAL PLAN AVAILABLE ON SITE. CHECK THE TIE-DOWN STRAPS INSTALLATION
All Rough Inspection - Commercial Partial 10/4/2017 10/4/2017 at 1:10 PM 10/04/2017
Misc
Partial Correction
10/04/2017
FLOOR FRAMING ONLY, BOTH ABOVE THE BASEMENT AND SECTION NORTH OF BASEMENT-OK TO INSTALL SUBFLOOR SHEATHING
Rough Framing Inspection - Commercial Partial 10/11/2017 at 11:30 AM 10/11/2017
Misc
Partial Correction
10/11/2017
OBSERVATION OF EXTERIOR WALL SHEATHING: FASTENER PATTERN COMPLIES WITH DRAWING NOTE. HOWEVER ALL NAILS ARE OVERDRIVEN 1/8" TO 1/4".
Electrical Service Inspection Failed 10/23/2017 at 9:40 AM 10/23/2017
Misc
Corrective Action Required
10/23/2017
REMAINING KNOCKOUTS PREVENT NIPPLE FROM PROVIDING CERTAIN BONDING AT METER ENCLOSURE
Electrical Service Inspection Passed 10/23/2017 at 1:40 PM 10/23/2017
Misc
Resolved
10/23/2017
REMAINING KNOCKOUTS PREVENT NIPPLE FROM PROVIDING CERTAIN BONDING AT METER ENCLOSURE
Footing Inspection - Commercial Passed 10/25/2017 (9:00) 10/25/2017 at 9:00 AM 10/25/2017
Footing Inspection - Commercial Passed 10/26/2079 at 9:45 AM 10/26/2017
Foundation Inspection - Commercial Partial 10/26/2017 at 10:05 AM 10/26/2017
Misc
Partial Correction
10/26/2017
WALLS AT STOOP OK TO POUR INTEGRAL WITH SLAB
Foundation Inspection - Commercial Partial 10/30/2017 at 8:55 AM 10/30/2017
Misc
Partial Correction
10/27/2017
WALLS AT STOOP OK TO POUR INTEGRAL WITH SLAB
Misc
Partial Correction
10/30/2017
OK TO POUR RAMP SLAB: UPPER SLOPE AND LANDING;
Foundation Inspection - Commercial Passed 10/30/2017 at 3:50 PM 10/30/2017
Misc
Resolved
10/30/2017
WALLS AT STOOP OK TO POUR INTEGRAL WITH SLAB
Misc
Resolved
10/30/2017
OK TO POUR RAMP SLAB: UPPER SLOPE AND LANDING;
All Rough Inspection - Commercial Failed 10/30/2017 10/30/2017 at 4:15 PM 10/30/2017
Misc
Resolved
10/30/2017
FLOOR FRAMING ONLY, BOTH ABOVE THE BASEMENT AND SECTION NORTH OF BASEMENT-OK TO INSTALL SUBFLOOR SHEATHING
Misc
Corrective Action Required
10/30/2017
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Corrective Action Required
10/30/2017
IPC 905.2; IRC P3104.2 GRADING OF VENT PIPING TO DRAIN
Misc
Corrective Action Required
10/30/2017
IBC 718.2; IRC R502.13; R602.8 FIREBLOCKING: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS AND INTERSECTIONS OF VERTICAL AND HORIZONTAL CAVITIES. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES.
All Rough Inspection - Commercial Passed 10/31/2017 10/31/2017 at 8:35 AM 10/31/2017
Misc
Resolved
10/31/2017
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Resolved
10/31/2017
IPC 905.2; IRC P3104.2 GRADING OF VENT PIPING TO DRAIN
Misc
Resolved
10/31/2017
IBC 718.2; IRC R502.13; R602.8 FIREBLOCKING: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS AND INTERSECTIONS OF VERTICAL AND HORIZONTAL CAVITIES. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES.
Gas Piping Inspection - Commercial Passed 10/31/2017 at 9:15 AM 10/31/2017
Gas Service Inspection - Commercial Passed 10/31/2017 10/31/2017 at 9:20 AM 10/31/2017
Rough Framing Inspection - Commercial Passed 10/11/2017 11/30/2017
Misc
Resolved
11/30/2017
OBSERVATION OF EXTERIOR WALL SHEATHING: FASTENER PATTERN COMPLIES WITH DRAWING NOTE. HOWEVER ALL NAILS ARE OVERDRIVEN 1/8" TO 1/4".
Miscellaneous Inspection Partial 12/4/2017 at 10:50 AM 12/04/2017
Occupancy Inspection - Fire Passed 12/12/2017 12/12/2017
Occupancy Inspection - Codes Commercial Full C of O 12/12/2017 12/12/2017 at 1:20 PM 12/12/2017
Occupancy Inspection - Water Utilities Passed 12/13/2017
Documents & Images
Date Uploaded File Type Document Name
05/18/2017 Letter Fire Building Plan Review
05/18/2017 Letter Fire Building Plan Review
05/24/2017 Letter Codes P/R Corrections Document
08/23/2017 Letter Fire Building Plan Review
08/23/2017 Letter Codes P/R Corrections Document
09/01/2017 Letter Fire Building Plan Review
09/11/2017 Letter Codes P/R Corrections Document
09/13/2017 Letter Codes Plan Review Conditions
09/14/2017 Receipt Receipt for transaction: 2017-006370
09/14/2017 Letter Codes Building Permit
09/28/2017 Letter Inspection Summary
10/03/2017 Letter Inspection Summary
10/04/2017 Letter Inspection Summary
10/11/2017 Letter Inspection Summary
10/23/2017 Letter Inspection Summary
10/25/2017 Letter Inspection Summary
10/26/2017 Letter Inspection Summary
10/30/2017 Letter Inspection Summary
10/30/2017 Letter Inspection Summary
10/31/2017 Letter Inspection Summary
12/12/2017 Letter Field Certificate of Occupancy
12/13/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home