Permit Application Status

PRCOM20162931


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20162931
Building Permit - Commercial
Certificate of Occupancy
SUMMIT WOODS SPE LLC
CHANGE OF TENANT
TENANT FINISH FOR MASSAGE THERAPY CLINIC
11/10/2016
02/22/2017
05/10/2017
04/27/2017
Locations
Contacts
ED MOORE CONSTRUCTION COMPANY, INC., Address:413 EAST MAIN ST, Phone:(913) 856-2300  
CHIEF HEATING & COOLING INC, Address:920 NW TECHNOLOGY DR, Phone:(816) 246-4646  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
FIVE STAR MECHANICAL CONTRACT INC, Address:P O BOX 11964, Phone:(816) 358-4444  
THE MCINTOSH GROUP INC, Address:1850 S BOULDER AVE, Phone:(918) 585-8555  
SUMMIT WOODS SPE LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/30/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
03/30/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the fire alarm system notification and activation devices will be required prior to the final occupancy inspection. to schedule a test contact the fire department ant 816-969-1300.
Sprinkler Plan Review Released for Construction 03/01/2017
Joe Dir
Misc
Corrective Action Required
03/01/2017

PLANS INDICATE THE LOCATION OF FOUR PENDANTS IN THE NORTH CORRIDOR ARE IN OR UP AGAINST THE CORRIDOR WALL. RELOCATION REQUIRED TO BE CENTERED IN THE CORRIDOR OR TO BE A MINIMUM OF 4 INCHES AWAY FROM A WALL. (VERIFIED AT INSPECTION)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/01/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING SPRINKLER SYSTEM RISER SHALL BE CURRENT WITH ALL REQUIRED SERVICE AND MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE RISER. (VERIFIED AT INSPECTION)
Licensed Contractors Approved 12/01/2016 02/15/2017
Joe Frogge
LC - General Contractor
Resolved
02/15/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
02/14/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 12/08/2016 01/13/2017
Joe Dir
Misc
Corrective Action Required
01/13/2017

DOOR LOCKS/LATCHES: NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
01/13/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM. (INFORMATION PURPOSES)
Address numbers required
Corrective Action Required
01/13/2017

2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1748 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR TO THE BACKGROUND. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
01/13/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
01/13/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF ANY MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM WILL NEED TO BE TESTED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. (INFORMATION PURPOSES)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
01/13/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
01/13/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE FIRE EXTINGUISHERS ACCORDING TO PLANS (information purposes)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
01/13/2017

2012IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHERS ACCORDING TO PLANS. (information purposes)
Building Plan Review Approved with Conditions 12/08/2016 12/05/2016
Joe Frogge
License Tax Application
Corrective Action Required
12/01/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 12/5/16 - acknowledged
Misc
Resolved
12/05/2016

Lee's Summit Code of Ordinances Section 28-63(C) 3. No massage facility business license shall be approved by the Director of Finance unless the facility complies with each of these minimum requirements: a. The walls shall be clean and painted with washable, mold-resistant paint in all rooms where massage is provided. Floors shall be free from any accumulation of dust, dirt or refuse. All equipment used in the business operation shall be maintained in a clean and sanitary condition. Towels, linens and items for personal use of massage therapists, employees and patrons shall be in sufficient quantity so that none is used for more than one (1) person. Heavy, white paper may be substituted for sheets if such paper is changed for each patron. No cubicle, room, booth or any area within the facility where service is to be provided patrons shall be fitted with a door capable of being locked. b. Toilet facilities shall be provided in convenient locations. When the facility is designed to accommodate any combination of five (5) or more massage therapists, employees and patrons of different sexes on the premises at the same time, separate toilet facilities shall be provided. A single water closet per sex shall be provided for any combination of twenty (20) or more massage therapists, employees or patrons that the establishment is designed to accommodate on the premises at any one time. Urinals may be substituted for water closets after one (1) water closet has been provided. Toilets shall be designated as to the sex accommodated therein. c. Lavatories or wash basins provided with both hot and cold running water shall be installed in either the toilet room or vestibule. Lavatories or wash basins shall be provided with soap in a dispenser and with sanitary towels. Actions required: - Specify mold resistant paint at all massage rooms. - Provide non-lockable door hardware at all massage rooms. - Specify gender specific signage at restrooms.
Misc
Resolved
12/05/2016

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Modify plans to designate correct construction type which is IIB.
Bldg - Toilet room wall finish 1210.2.2
Resolved
12/05/2016

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Modify plans to show compliant wall finish materials surrounding mop sink.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Resolved
12/05/2016

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Front service counter specified to be ADA compliant but no dimensional information provided. This will be field verified during inspections.
Misc
Resolved
12/05/2016

Lee's Summit Code of Ordinances Section 28-65 - Operating Procedures. (F) Sanitation of massage therapists and employees. All massage therapists shall be clean and wear clean clothes. Provisions for a separate massage therapist/employee dressing room for each sex must be available on the premises with individual lockers for each massage therapist and employee. Doors to such dressing rooms shall open inward. Action required: Modify plans to demonstrate compliance.
Accessibility - Flush controls 604.6
Resolved
12/05/2016

ICC A117.1-2009 604.6 – Flush controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet. Action required: Modify drawings to demonstrate compliance. (both are specified as left handed)
Misc
Resolved
12/05/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. (including at steamer cabinet)
Fire Plan Review Approved with Conditions 12/08/2016 12/02/2016
Joe Dir
01/13/2017

01/13/2017

01/13/2017

Construction documents for fire alarm systems
Corrective Action Required
12/01/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE FIRE ALARM CONTRACTOR PROVIDE ENGINEERED SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM. (INFORMATION PURPOSES)
Construction documents - Fire protection systems
Corrective Action Required
12/01/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE FIRE SPRINKLER SYSTEM CONTRACTOR PROVIDE ENGINEERED SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
12/01/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF ANY MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM IS REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. (INFORMATION PURPOSES)
Portable fire extinguishers - general
Corrective Action Required
12/01/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE FIRE EXTINGUISHERS ACCORDING TO PLANS (information purposes)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
12/01/2016

2012IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHERS ACCORDING TO PLANS. (information purposes)
Misc
Corrective Action Required
01/13/2017

THE RESUB CODE ANALYSIS COMMENTS STATE THAT THE FIRE ALARM SYSTEM IS NOT REQUIRED TO BE MONITORED. THAT IS NOT ACCURATE. THE SYSTEM IS REQUIRED TO BE MONIOTORED. ALL FIRE ALARM SYSTEM DEVICES INSTALLED WILL BE WIRED INTO THE BUILDINGS MAIN FIRE ALARM PANEL AND WILL BE MONITORED. (INFORMATION PURPOSES)
Building Plan Review Rejected 11/22/2016 11/11/2016
Joe Frogge
License Tax Application
Corrective Action Required
11/11/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
11/11/2016

Lee's Summit Code of Ordinances Section 28-63(C) 3. No massage facility business license shall be approved by the Director of Finance unless the facility complies with each of these minimum requirements: a. The walls shall be clean and painted with washable, mold-resistant paint in all rooms where massage is provided. Floors shall be free from any accumulation of dust, dirt or refuse. All equipment used in the business operation shall be maintained in a clean and sanitary condition. Towels, linens and items for personal use of massage therapists, employees and patrons shall be in sufficient quantity so that none is used for more than one (1) person. Heavy, white paper may be substituted for sheets if such paper is changed for each patron. No cubicle, room, booth or any area within the facility where service is to be provided patrons shall be fitted with a door capable of being locked. b. Toilet facilities shall be provided in convenient locations. When the facility is designed to accommodate any combination of five (5) or more massage therapists, employees and patrons of different sexes on the premises at the same time, separate toilet facilities shall be provided. A single water closet per sex shall be provided for any combination of twenty (20) or more massage therapists, employees or patrons that the establishment is designed to accommodate on the premises at any one time. Urinals may be substituted for water closets after one (1) water closet has been provided. Toilets shall be designated as to the sex accommodated therein. c. Lavatories or wash basins provided with both hot and cold running water shall be installed in either the toilet room or vestibule. Lavatories or wash basins shall be provided with soap in a dispenser and with sanitary towels. Actions required: - Specify mold resistant paint at all massage rooms. - Provide non-lockable door hardware at all massage rooms. - Specify gender specific signage at restrooms.
Misc
Corrective Action Required
11/11/2016

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Modify plans to designate correct construction type which is IIB.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
11/11/2016

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Modify plans to show compliant wall finish materials surrounding mop sink.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
11/11/2016

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Front service counter specified to be ADA compliant but no dimensional information provided. This will be field verified during inspections.
Misc
Corrective Action Required
11/11/2016

Lee's Summit Code of Ordinances Section 28-65 - Operating Procedures. (F) Sanitation of massage therapists and employees. All massage therapists shall be clean and wear clean clothes. Provisions for a separate massage therapist/employee dressing room for each sex must be available on the premises with individual lockers for each massage therapist and employee. Doors to such dressing rooms shall open inward. Action required: Modify plans to demonstrate compliance.
Accessibility - Flush controls 604.6
Corrective Action Required
11/11/2016

ICC A117.1-2009 604.6 – Flush controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet. Action required: Modify drawings to demonstrate compliance. (both are specified as left handed)
Misc
Corrective Action Required
11/11/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. (including at steamer cabinet)
Misc
Resolved
11/29/2016

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Skin treatment rooms must comply with cited code section. Provide additional information as to what types of skin procedures will be available as well as what tools and equipment will be used. 11/29/16 - resolved per clarification letter from engineer. skin treatment rooms are for cosmetic, non-medical uses.
Zoning Review Approved 11/22/2016 11/11/2016
Joe Frogge
Licensed Contractors Rejected 11/11/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
11/11/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/11/2016

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 11/22/2016 11/11/2016
Joe Dir
Misc
Corrective Action Required
11/11/2016

DOOR LOCKS/LATCHES B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
11/11/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM. (INFORMATION PURPOSES)
Address numbers required
Corrective Action Required
11/11/2016

2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1748 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR TO THE BACKGROUND. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
11/11/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
11/11/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF ANY MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM WILL NEED TO BE TESTED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. (INFORMATION PURPOSES)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
11/11/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
11/11/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A MINIMUM OF TWO 2A-10BC FIRE EXTINGUISHERS. (VERIFIED AT INSPECTION)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/11/2016

2012IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHERS ON A NORMAL PATH OF TRAVEL CLOSE TO AN EXIT WITH A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANTWHERE WITHIN THE BUSINESS. (VERIFIED AT INSPECTION)
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $827.62 $827.62 Paid 02/22/2017
8331507-Sewer Connection Fee $360.00 $360.00 Paid 02/22/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 3/6/2017 3/6/2017 03/06/2017
Underslab Electrical Inspection - Commercial Passed 3/6/2017 3/6/2017 03/06/2017
In-wall Inspection Partial 3/14/2017 3/14/2017 03/14/2017
Misc
Corrective Action Required
03/14/2017
II-B OCCUPANCY REQUIRES IN-WALL BLOCKING TO BE STAMPED "FIRE-TREATED"
In-wall Inspection Passed 3/15/2017 03/15/2017
Misc
Resolved
03/15/2017
II-B OCCUPANCY REQUIRES IN-WALL BLOCKING TO BE STAMPED "FIRE-TREATED"
Above Ceiling Inspection Partial 3/21/2017 03/21/2017
Misc
Partial Correction
03/21/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES/LOCATIONS: SOFFIT/FACIA AT 101; CEILING AT 104;
In-wall Inspection Partial 3/21/2017 03/21/2017
Misc
Partial Correction
03/21/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES/LOCATIONS: THREE COLUMN WRAPS AT SOUTH CORRIDOR; CLOSETS 103; 132;
Above Ceiling Inspection Partial 3/22/2017 04/11/2017
Misc
Partial Correction
03/21/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES/LOCATIONS: SOFFIT/FACIA AT 101; CEILING AT 104; THE HARD-LID CEILING ABOVE THE TWO RESTROOMS
Above Ceiling Inspection Not Ready 4/11/2017 04/11/2017
Misc
Partial Correction
04/11/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES/LOCATIONS: SOFFIT/FACIA AT 101; CEILING AT 104; THE HARD-LID CEILING ABOVE THE TWO RESTROOMS
ELECTRICAL
Corrective Action Required
04/11/2017
NOT ALL BOXES MADE UP
Above Ceiling Inspection Passed 4/12/2017 4/12/2017 04/12/2017
Misc
Resolved
04/12/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES/LOCATIONS: SOFFIT/FACIA AT 101; CEILING AT 104; THE HARD-LID CEILING ABOVE THE TWO RESTROOMS
ELECTRICAL
Resolved
04/12/2017
NOT ALL BOXES MADE UP
In-wall Inspection Passed 3/21/2017 04/12/2017
Misc
Resolved
04/12/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES/LOCATIONS: THREE COLUMN WRAPS AT SOUTH CORRIDOR; CLOSETS 103; 132;
Alarm Test Passed 4/25/2017 04/25/2017
Miscellaneous Inspection Passed 4/25/2017 04/25/2017
Occupancy Inspection - Fire Passed 4/26/2017 04/26/2017
Occupancy Inspection - Codes Commercial Partial 4/26/2017 4/26/2017 04/26/2017
Misc
Corrective Action Required
04/26/2017
IDENTITY/LABEL MAIN DISCONNECT FOR ELECTRICAL POWER
Misc
Corrective Action Required
04/26/2017
ENSURE GAS SERVICE IS LABELED
Misc
Corrective Action Required
04/26/2017
LABEL ELECTRICAL PANEL LP6
Misc
Corrective Action Required
04/26/2017
AFFIX ACCESSIBLE RESTROOM SIGNS
Misc
Corrective Action Required
04/26/2017
ELECTRICAL FLOOR BOXES TO BE INSTALLED AT THERAPY ROOMS 112 & 113
Misc
Corrective Action Required
04/26/2017
Occupancy Inspection - Codes Commercial Full C of O 4/27/2017 04/27/2017
Misc
Resolved
04/27/2017
IDENTITY/LABEL MAIN DISCONNECT FOR ELECTRICAL POWER
Misc
Resolved
04/27/2017
ENSURE GAS SERVICE IS LABELED
Misc
Resolved
04/27/2017
LABEL ELECTRICAL PANEL LP6
Misc
Resolved
04/27/2017
AFFIX ACCESSIBLE RESTROOM SIGNS
Misc
Resolved
04/27/2017
ELECTRICAL FLOOR BOXES TO BE INSTALLED AT THERAPY ROOMS 112 & 113
Misc
Resolved
04/27/2017
Documents & Images
Date Uploaded File Type Document Name
11/11/2016 Letter Fire Building Plan Review
11/11/2016 Letter Codes P/R Corrections Document
11/11/2016 Letter Codes P/R Corrections Document
11/29/2016 RE Massage Envy - plan review
12/02/2016 Letter Fire Building Plan Review
01/13/2017 Letter Fire Building Plan Review
02/15/2017 Letter Codes Plan Review Conditions
02/22/2017 Receipt Receipt for transaction: 2017-000575
02/22/2017 Letter Codes Building Permit
03/01/2017 Letter Fire (Sprinkler) Plan Review
03/06/2017 Letter Inspection Summary
03/14/2017 Letter Inspection Summary
03/15/2017 Letter Inspection Summary
03/21/2017 Letter Inspection Summary
03/22/2017 Letter Inspection Summary
03/30/2017 Letter Fire (Alarm) Plan Review Notice
04/11/2017 Letter Inspection Summary
04/12/2017 Letter Inspection Summary
04/26/2017 Letter Inspection Summary
04/27/2017 Letter Field Certificate of Occupancy
04/28/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home