Permit Application Status

PRCOM20161721


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161721
Building Permit - Commercial
Final Completion
RAVID LEE SUMMIT LLC
CHANGE OF TENANT
RESTAURANT TO EXPAND INTO ADJACENT SPACE TO PROVIDE ADDITIONAL SEATING AND BAR AREA *drawings are in plan review file
07/13/2016
08/03/2016
01/11/2017
10/07/2016
Locations
Contacts
RAVID LEE SUMMIT LLC, Address:1901 HARRISON ST FL 2ND  
THAI SPICE, Address:1192 NE DOUGLAS ST, Phone:(816) 347-9859  
ROADRUNNER REMODELING LLC, Address:9250 GLENWOOD ST STE 120, Phone:(913) 915-4827  
KMZC PLUMBING, Address:301 W WEA, Phone:(913) 238-2583  
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2016
Joe Dir
Sprinkler Plan Review Released for Construction 08/22/2016 08/22/2016
Jim Eden
Installation acceptance testing
Corrective Action Required
08/22/2016

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at the Occupancy Inspection.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/22/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action required: The existing system shall have documentation of a current annual inspection.
Licensed Contractors Approved 07/25/2016 08/03/2016
Development Center
LC - MEP Subs
Resolved
08/03/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Electrical Contractor.
Building Plan Review Approved 07/25/2016 08/03/2016
Development Center
Misc
Resolved
08/03/2016

Inadequate information. Action required: Provide detailed scopes of work for plumbing and electrical.
Fire Plan Review Approved with Conditions 07/25/2016 07/15/2016
Joe Dir
Misc
Corrective Action Required
07/15/2016

ALL EXSITING EXIT SIGNS AND EMERGENCY LIGHTING THROUGH OUT BOTH SIDES OF BUSINESS SHALL BE ADDED AS NEEDED OR REMAIN AND BE IN PROPER WORKING ORDER. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
07/15/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE ALARM SYSTEM. ADD ALARM DEVICES TO THE EXPANSION AREA AS NEEDED. (VERIFIED AT INSPECTION)
Address numbers required
Corrective Action Required
07/15/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1192 ON THE EXTERIOR OF THE FRONT AND REAR DOORS OF ALL DOORS LEADING INTO THE BUSINESS.
Construction documents - Fire protection systems
Corrective Action Required
07/15/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/15/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH THE REQUIRED ANNUAL SERVICE/MAINTENANCE WITH A CURERENT TAG ON THE RISER. THE KITCHEN HOOD SYSTEM SHALL BE CURRENT WITH CLEANING ANG THE 6 MONTH REQUIRED SERVICE WITH A CURRENT TAG ON THE MANULA PULL STATION. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
07/15/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A MINIMUM OF ONE 2A-10BC FIRE EXTINGUISHER.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/15/2016

2012IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHER ON A WALL CLOSE TO AN EXIT WITH THE TOP OF THE EXTINGUISHER NO HIGHER THAN 60" OFF OF FLOOR.
Misc
Corrective Action Required
07/15/2016

POST OCCUPANT LOADS ON BOTH SIDES (DINING AREAS) OF THE BUSINESS.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.00 $30.00 Paid 08/03/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Passed 8/18/2016 8/18/2016 08/18/2016
Underslab Plumbing Inspection - Commercial Passed 8/18/2016 08/18/2016
Occupancy Inspection - Codes Commercial Not Ready 9/16/2016 9/16/2016 09/16/2016
Misc
Corrective Action Required
09/16/2016
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
09/16/2016
ELECTRICAL RECEPTACLE BOXES AT THREE LOCATIONS NEED BOX EXTENDERS. NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES.
Misc
Corrective Action Required
09/16/2016
NEC 110 - 26 (a) (b); IRC 3305.1: DEDICATED WORKING/CLEAR SPACE AT ELECTRICAL PANEL MUST BE MINIMUM OF 30" BY 36" DEEP
Above Ceiling Inspection Failed 9/16/2016 09/16/2016
Misc
Corrective Action Required
09/16/2016
COMPLETE DEMOLITION ABOVE CEILING: - LIGHT-GAUGE STEEL BRACES - REMOVE UNTERMINATED MC CABLE AT SOUTHEAST - STRAP ALL MC ELECT CABLES WITHIN 12" OF JUNCTION BOXES - REMOVE ABANDONED BATH VENT DUCT AND INSTALL PERMANENT CLOSURE ON HARD PIPE - ENSURE ALL SPRINKLER HEADS ARE AT CEILING ELEVATION AND HAVE ESCUTCHEONS IN PLACE
Occupancy Inspection - Fire Not Ready 9/16/2016 09/16/2016
Occupancy Inspection - Fire Passed 9/21/2016 09/21/2016
Final Inspection - Commercial Passed 9/21/2016 09/21/2016
Above Ceiling Inspection Passed 9/21/2016 09/21/2016
Misc
Resolved
09/21/2016
COMPLETE DEMOLITION ABOVE CEILING: - LIGHT-GAUGE STEEL BRACES - REMOVE UNTERMINATED MC CABLE AT SOUTHEAST - STRAP ALL MC ELECT CABLES WITHIN 12" OF JUNCTION BOXES - REMOVE ABANDONED BATH VENT DUCT AND INSTALL PERMANENT CLOSURE ON HARD PIPE - ENSURE ALL SPRINKLER HEADS ARE AT CEILING ELEVATION AND HAVE ESCUTCHEONS IN PLACE
Documents & Images
Date Uploaded File Type Document Name
07/15/2016 Letter Fire Building Plan Review
07/15/2016 Letter Codes P/R Corrections Document
08/03/2016 Receipt Receipt for transaction: 2016-005185
08/03/2016 Letter Codes Building Permit
08/18/2016 Letter Inspection Summary
08/22/2016 Letter Fire (Sprinkler) Plan Review
09/16/2016 Letter Inspection Summary
09/16/2016 Letter Inspection Summary
09/21/2016 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home