Review Type |
Outcome |
Est. Completion Date |
Completed |
Alarm Plan Review
|
Released for Construction
|
|
12/31/2016
|
|
Joe Dir
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
08/22/2016
|
08/22/2016
|
|
Jim Eden
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
A visual inspection will be completed at the Occupancy Inspection.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
Action required: The existing system shall have documentation of a current annual inspection.
|
|
|
Licensed Contractors
|
Approved
|
07/25/2016
|
08/03/2016
|
|
Development Center
|
|
LC - MEP Subs
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Electrical Contractor.
|
|
|
Building Plan Review
|
Approved
|
07/25/2016
|
08/03/2016
|
|
Development Center
|
|
Misc
Inadequate information.
Action required: Provide detailed scopes of work for plumbing and electrical.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
07/25/2016
|
07/15/2016
|
|
Joe Dir
|
|
Misc
Corrective Action Required
ALL EXSITING EXIT SIGNS AND EMERGENCY LIGHTING THROUGH OUT BOTH SIDES OF BUSINESS SHALL BE ADDED AS NEEDED OR REMAIN AND BE IN PROPER WORKING ORDER. (VERIFIED AT INSPECTION)
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE ALARM SYSTEM. ADD ALARM DEVICES TO THE EXPANSION AREA AS NEEDED. (VERIFIED AT INSPECTION)
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 1192 ON THE EXTERIOR OF THE FRONT AND REAR DOORS OF ALL DOORS LEADING INTO THE BUSINESS.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH THE REQUIRED ANNUAL SERVICE/MAINTENANCE WITH A CURERENT TAG ON THE RISER. THE KITCHEN HOOD SYSTEM SHALL BE CURRENT WITH CLEANING ANG THE 6 MONTH REQUIRED SERVICE WITH A CURRENT TAG ON THE MANULA PULL STATION.
(VERIFIED AT INSPECTION)
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
PROVIDE A MINIMUM OF ONE 2A-10BC FIRE EXTINGUISHER.
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
MOUNT THE FIRE EXTINGUISHER ON A WALL CLOSE TO AN EXIT WITH THE TOP OF THE EXTINGUISHER NO HIGHER THAN 60" OFF OF FLOOR.
|
|
Misc
Corrective Action Required
POST OCCUPANT LOADS ON BOTH SIDES (DINING AREAS) OF THE BUSINESS.
|
|
|