Permit Application Status

PRCOM20160836


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20160836
Building Permit - Commercial
Certificate of Occupancy
MARION RIDGE SAFETY STORAGE LLC
NEW COMMERCIAL
NEW OFFICE BUILDING FOUNDATION PERMIT - PRCOM20161018
04/13/2016
09/01/2016
10/17/2016
11/06/2017
Locations
Contacts
WARD DEVELOPMENT & INVESTMENT CO, Address:1120 NW EAGLE RIDGE BLVD, Phone:(816) 229-8115  
DONALDSON MECHANICAL INC, Address:934 SE 7TH TER, Unit B, Phone:(816) 246-9500  
MARK ONE ELECTRIC CO INC, Address:1414 GENESSEE ST, Phone:(816) 842-7023  
STINE-NICHOLS PLUMBING INC, Address:318 E 16TH AVE, Phone:(816) 348-3481  
CL ARCHITECTURE (CRAIG LUEBBERT), Address:396 SW WINTERGARDEN, Phone:(816) 536-3472  
MARION RIDGE SAFETY STORAGE LLC, Address:1101 C NW PAMELA BLVD  
ALPHA-OMEGA GEOTECH, Address:1701 STATE AVE, Phone:(913) 371-0000  
SILVER BULLET LLC, Address:1120 NW EAGLE RIDGE BLVD STE A  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 05/06/2016 07/17/2017
Joe Dir
Misc
Corrective Action Required
07/17/2017

NO KEYED CYLINDER LOCKS ON THE EGRESS SIDE OF A MARKED EXIT
Construction documents for fire alarm systems
Corrective Action Required
07/17/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE CHOOSEN CONTRATOR PROIVDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Address numbers required
Corrective Action Required
07/17/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS 0F 2641 ON THE BUILDING READABLE FROM THE ROADWAY
Knox box required
Resolved
07/17/2017

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. A KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com OR CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Construction documents - Fire protection systems
Resolved
07/17/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CHOOSEN CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Resolved
07/17/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS. ALL TESTING SHOULD BE CONCLUDED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Resolved
07/17/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PLANS SHOW 10 POUND FIRE EXTINGUISHERS. THIS TYPE OF OCCUPANCY REQUIRES ONLY 2A-10BC MINIMUM RATED AT (5 POUND) FIRE EXTINGUISHERS.
Portable fire extinguishers - conspicuous locations
Resolved
07/17/2017

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. RELOCATED THE FIRE EXTINGUISHER FROM INSIDE THE BREAKROOM TO BE IN THE EAST HALLWAY CENTRALLY LOCATED RELOCATE THE FIRE EXTINGUISHER IN THE SAFE ROOM TO BE IN THE WEST HALLWAY CENTRALLY LOCATED. FIRE EXTINGUISHERS SHOULD BE LOCATED TO HAVE A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANTWHERE WITHIN THE BUILDING. (VERIFIED AT INSPECTION)
Misc
Resolved
07/17/2017

WATERFLOW ALARM WILL BE A WEATHER RESISTANT HORN STROBE NOT A ELECTRICAL BELL THE FIRE DEPARTMENT CONNECTION FOR THE FIRE SPRINKLER SYSTEM SHALL BE 4" STORTZ CONNECTION WITH A 30 DEGREE TURNDOWN. (INFORMATION PURPOSES)
Hazardous material identification
Corrective Action Required
07/17/2017

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. ACTION REQUIRED: Post a NFPA 704 placard on the generator with the SDS hazrad listings for the fuel in the fuel cell. Label the fuel cell with the name of the fuel being stored. (GASOLINE) (DIESEL)
Alarm Plan Review Released for Construction 02/10/2017
Joe Dir
Misc
Corrective Action Required
02/10/2017

SYSTEM OVERVIEW OUTLINE: FIRE ALARM MATRIX REMOVE SMOKE DETECTORS AND MANUAL PULLS FROM THE EXTERIOR HORN/STROBE COLUMN. THE ONLY THING TO ACTIVATE THE EXTERIOR HORN/STROBE WILL BE THE WATER FLOW SWITCH. (VERIFIED AT INSPECTION)
Installation acceptance testing
Corrective Action Required
02/10/2017

2012IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE TESTING OF THE FIRE ALARM SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300 (INFROMATION PURPOSES)
Sprinkler Plan Review Released for Construction 12/28/2016
Joe Dir
Misc
Corrective Action Required
12/28/2016

Provide updated drawings showing the location of the dry system inspectors test. NW corner of the building.
Installation acceptance testing
Corrective Action Required
12/28/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING OF THE SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Final Development Plan Review Approved 05/06/2016 10/26/2016
Joe Frogge
Building Plan Review Approved with Conditions 05/06/2016 05/11/2016
Joe Frogge
Engineered truss package
Corrective Action Required
04/29/2016

Copies of the engineered roof truss package were not provided at the time of permit application. Action required: Provide truss package or request deferral. 5/4/16 - deferred
License Tax Application
Corrective Action Required
04/29/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Resolved
08/30/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Resolved
05/03/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Plan Submittal 2012 Codes
Resolved
05/04/2016

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update code analysis to reflect correct year of ANSI A117.1. (2009)
Bldg - Accessibility - Where required 1103.1
Resolved
05/11/2016

2012 IBC 1103.1 – Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. (See Section 1103.2 of the 2012 IBC for exceptions.) Action required: Modify drawings to demonstrate compliance at all coffee bars. Layouts to comply with ICC/ANSI-2009 Section 902 for maximum counter height, ICC/ANSI-2009 Section 305 for clear floor space, ICC/ANSI-2009 Section 404.2.3.2 for door configurations.
Misc
Resolved
05/04/2016

Missing information. Action required: Provide door to access room near column line 3J.
Misc
Resolved
05/04/2016

2012 IBC 2308.9.3 Bracing. Braced wall lines shall consist of braced wall panels that meet the requirements for location, type and amount of bracing as shown in Figure 2308.9.3, specified in Table 2308.9.3(1) and are in line or offset from each other by not more than 4 feet (1219 mm). Braced wall panels shall start not more than 121/2 feet (3810 mm) from each end of a braced wall line. Braced wall panels shall be clearly indicated on the plans. Construction of braced wall panels shall be by one of the following methods: (see code for methods and other additional information) Action required: Provide information or design to demonstrate compliance with brace wall requirements.
Bldg - Landings at doors 1008.1.6
Resolved
05/04/2016

2012 IBC 1008.1.6 – Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches. Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches. Action required: Provide landing at all exterior doors including door at far north of building.
Bldg - Attic access 1209.2
Resolved
05/04/2016

2012 IBC 1209.2 – Attic spaces. An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. Clear headroom of not less than 30 inches shall be provided in the attic space at or above the access opening. Action required: Provide attic access.
Misc
Resolved
05/04/2016

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior of front exit.
Misc
Corrective Action Required
04/29/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section. 5/11/16 - deferred. building owner is investigating alternate equipment 8/30/16 - to be field verified
Misc
Resolved
05/04/2016

Sec. 7-802. - Residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: A. Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of R-13. This requirement does not apply to doors, windows, or other openings or approved penetrations nor does it apply to basement concrete walls when the basement is not finished as a habitable space. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Garage ceilings with living area above shall comply with this requirement. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. This requirement does not apply to skylights or other approved penetrations. D. Ceilings forming portions of a building envelope shall meet or exceed an R factor rating of thirty (30) at the time of installation. E. Duct insulation. All portions of the air distribution system shall be installed in accordance with Section M1601 and be insulated to an installed R-5 when system components are located within the building but outside of conditioned space, and R-8 when located outside of the building. When located within a building envelope assembly, at least R-8 shall be applied between the duct and that portion of the assembly furthest from conditioned space. (Ord. No. 7369, § 1, 10-3-2013) Action required: Provide minimum R-5 insulation on all ductwork in attic including return air. (our ordinance is silent on ductwork R values for commercial applications. Residential R values represent intent of the code)
Misc
Resolved
05/04/2016

2012 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision ins made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Specify method of protecting water pipes from freezing. 5/4/16 - no piping in attic
Misc
Corrective Action Required
04/29/2016

2011 NEC 410.116 Clearance and Installation. (A) Clearance. (1) Non-Type IC. A recessed luminaries that is not identified for contact with insulation shall have all recessed parts spaced not less than ½” from combustible materials. The points of support and the trim finishing off the openings in the ceiling, wall, or other finished surface shall be permitted to be in contact with combustible materials. (2) Type IC. A recessed luminaries that is identified for contact with insulation, Type IC, shall be permitted to be in contact with combustible materials at recessed parts, points of support, and portions passing through or finishing off the opening in the building structure. Action required: Specify recessed light fixtures as Type IC or provide details as to how to protect from insulation and other combustibles. 5/4/16 - per letter from architect, the ceiling contractor must construct boxes to protect the fixtures. field verify
Miscellaneous Correction
Resolved
05/04/2016

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25 feet of exterior condensing units.
Licensed Contractors Approved 04/29/2016 05/04/2016
Joe Frogge
LC - General Contractor
Resolved
05/04/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
05/04/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Special Inspections Review Approved 05/03/2016
Joe Frogge
Fire Plan Review Approved with Conditions 05/06/2016 05/03/2016
Joe Dir
05/03/2016

Misc
Corrective Action Required
04/29/2016

NO KEYED CYLINDER LOCKS ON THE EGRESS SIDE OF A MARKED EXIT
Construction documents for fire alarm systems
Corrective Action Required
04/29/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE CHOOSEN CONTRATOR PROIVDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Address numbers required
Corrective Action Required
04/29/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS 0F 2641 ON THE BUILDING READABLE FROM THE ROADWAY
Knox box required
Corrective Action Required
04/29/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. A KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com OR CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Construction documents - Fire protection systems
Corrective Action Required
04/29/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CHOOSEN CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
04/29/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS. ALL TESTING SHOULD BE CONCLUDED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
04/29/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PLANS SHOW 10 POUND FIRE EXTINGUISHERS. THIS TYPE OF OCCUPANCY REQUIRES ONLY 2A-10BC MINIMUM RATED AT (5 POUND) FIRE EXTINGUISHERS.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
04/29/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. RELOCATED THE FIRE EXTINGUISHER FROM INSIDE THE BREAKROOM TO BE IN THE EAST HALLWAY CENTRALLY LOCATED RELOCATE THE FIRE EXTINGUISHER IN THE SAFE ROOM TO BE IN THE WEST HALLWAY CENTRALLY LOCATED. FIRE EXTINGUISHERS SHOULD BE LOCATED TO HAVE A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANTWHERE WITHIN THE BUILDING. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
04/29/2016

WATERFLOW ALARM WILL BE A WEATHER RESISTANT HORN STROBE NOT A ELECTRICAL BELL THE FIRE DEPARTMENT CONNECTION FOR THE FIRE SPRINKLER SYSTEM SHALL BE 4" STORTZ CONNECTION WITH A 30 DEGREE TURNDOWN. (INFORMATION PURPOSES)
Building Plan Review Rejected 04/27/2016 04/20/2016
Joe Frogge
Engineered truss package
Corrective Action Required
04/20/2016

Copies of the engineered roof truss package were not provided at the time of permit application. Action required: Provide truss package or request deferral.
License Tax Application
Corrective Action Required
04/20/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
04/20/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
04/20/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Plan Submittal 2012 Codes
Corrective Action Required
04/20/2016

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update code analysis to reflect correct year of ANSI A117.1. (2009)
Bldg - Accessibility - Where required 1103.1
Corrective Action Required
04/20/2016

2012 IBC 1103.1 – Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. (See Section 1103.2 of the 2012 IBC for exceptions.) Action required: Modify drawings to demonstrate compliance at all coffee bars. Layouts to comply with ICC/ANSI-2009 Section 902 for maximum counter height, ICC/ANSI-2009 Section 305 for clear floor space, ICC/ANSI-2009 Section 404.2.3.2 for door configurations.
Misc
Corrective Action Required
04/20/2016

Missing information. Action required: Provide door to access room near column line 3J.
Misc
Corrective Action Required
04/20/2016

2012 IBC 2308.9.3 Bracing. Braced wall lines shall consist of braced wall panels that meet the requirements for location, type and amount of bracing as shown in Figure 2308.9.3, specified in Table 2308.9.3(1) and are in line or offset from each other by not more than 4 feet (1219 mm). Braced wall panels shall start not more than 121/2 feet (3810 mm) from each end of a braced wall line. Braced wall panels shall be clearly indicated on the plans. Construction of braced wall panels shall be by one of the following methods: (see code for methods and other additional information) Action required: Provide information or design to demonstrate compliance with brace wall requirements.
Bldg - Landings at doors 1008.1.6
Corrective Action Required
04/20/2016

2012 IBC 1008.1.6 – Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches. Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches. Action required: Provide landing at all exterior doors including door at far north of building.
Bldg - Attic access 1209.2
Corrective Action Required
04/20/2016

2012 IBC 1209.2 – Attic spaces. An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. Clear headroom of not less than 30 inches shall be provided in the attic space at or above the access opening. Action required: Provide attic access.
Misc
Corrective Action Required
04/20/2016

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior of front exit.
Misc
Corrective Action Required
04/20/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Misc
Corrective Action Required
04/20/2016

Sec. 7-802. - Residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: A. Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of R-13. This requirement does not apply to doors, windows, or other openings or approved penetrations nor does it apply to basement concrete walls when the basement is not finished as a habitable space. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Garage ceilings with living area above shall comply with this requirement. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. This requirement does not apply to skylights or other approved penetrations. D. Ceilings forming portions of a building envelope shall meet or exceed an R factor rating of thirty (30) at the time of installation. E. Duct insulation. All portions of the air distribution system shall be installed in accordance with Section M1601 and be insulated to an installed R-5 when system components are located within the building but outside of conditioned space, and R-8 when located outside of the building. When located within a building envelope assembly, at least R-8 shall be applied between the duct and that portion of the assembly furthest from conditioned space. (Ord. No. 7369, § 1, 10-3-2013) Action required: Provide minimum R-5 insulation on all ductwork in attic including return air. (our ordinance is silent on ductwork R values for commercial applications. Residential R values represent intent of the code)
Misc
Corrective Action Required
04/20/2016

2012 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision ins made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Specify method of protecting water pipes from freezing.
Misc
Corrective Action Required
04/20/2016

2011 NEC 410.116 Clearance and Installation. (A) Clearance. (1) Non-Type IC. A recessed luminaries that is not identified for contact with insulation shall have all recessed parts spaced not less than ½” from combustible materials. The points of support and the trim finishing off the openings in the ceiling, wall, or other finished surface shall be permitted to be in contact with combustible materials. (2) Type IC. A recessed luminaries that is identified for contact with insulation, Type IC, shall be permitted to be in contact with combustible materials at recessed parts, points of support, and portions passing through or finishing off the opening in the building structure. Action required: Specify recessed light fixtures as Type IC or provide details as to how to protect from insulation and other combustibles.
Miscellaneous Correction
Corrective Action Required
04/20/2016

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25 feet of exterior condensing units.
Licensed Contractors Rejected 04/27/2016 04/18/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
04/18/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
04/18/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 04/27/2016 04/14/2016
Joe Dir
Misc
Corrective Action Required
04/14/2016

NO KEYED CYLINDER LOCKS ON THE EGRESS SIDE OF A MARKED EXIT
Construction documents for fire alarm systems
Corrective Action Required
04/14/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE CHOOSEN CONTRATOR PROIVDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Address numbers required
Corrective Action Required
04/14/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS 0F 2641 ON THE BUILDING READABLE FROM THE ROADWAY
Knox box required
Corrective Action Required
04/14/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. A KNOX BOX CAN BE OBTAINED ON LINE AT knoxbox.com OR CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Construction documents - Fire protection systems
Corrective Action Required
04/14/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CHOOSEN CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
04/14/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS. ALL TESTING SHOULD BE CONCLUDED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
04/14/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PLANS SHOW 10 POUND FIRE EXTINGUISHERS. THIS TYPE OF OCCUPANCY REQUIRES ONLY 2A-10BC MINIMUM RATED AT (5 POUND) FIRE EXTINGUISHERS.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
04/14/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. RELOCATED THE FIRE EXTINGUISHER FROM INSIDE THE BREAKROOM TO BE IN THE EAST HALLWAY CENTRALLY LOCATED RELOCATE THE FIRE EXTINGUISHER IN THE SAFE ROOM TO BE IN THE WEST HALLWAY CENTRALLY LOCATED. FIRE EXTINGUISHERS SHOULD BE LOCATED TO HAVE A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANTWHERE WITHIN THE BUILDING. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
04/14/2016

ADDTIONAL EXIT SIGNAGE REQUIRED WHERE THE (WEST) NORTH/SOUTH HALLWAY INTERSECTS AT THE SOUTH END WITH THE EAST/ WEST HALLWAY. INDICATING A OPTIONAL TRAVEL TO THE EAST OR WEST EXIT
Misc
Corrective Action Required
04/14/2016

WATERFLOW ALARM WILL BE A WEATHER RESISTANT HORN STROBE NOT A ELECTRICAL BELL THE FIRE DEPARTMENT CONNECTION FOR THE FIRE SPRINKLER SYSTEM SHALL BE 4" STORTZ CONNECTION WITH A 30 DEGREE TURNDOWN. (INFORMATION PURPOSES)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $6,000.88 $6,000.88 Paid 08/10/2016
$6,000.89
8350015-Water Meter Fee $2,816.73 $2,816.73 Paid 08/10/2016
8331507-Sewer Connection Fee $780.00 $780.00 Paid 08/10/2016
8331401-Water Tap Fee $21,427.00 $21,427.00 Paid 08/10/2016
8331506-EFHB Maybrook, Full $1,107.86 $1,107.86 Paid 08/10/2016
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 08/10/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Passed 10/12/2016 10/12/2016 10/12/2016
Underslab Electrical Inspection - Commercial Passed 10/12/2016 10/12/2016
Above Ceiling Inspection Not Ready 2/22/2017 2/22/2017 02/22/2017
In-wall Inspection Not Ready 2/22/2017 2/22/2017 02/22/2017
Gas Piping Inspection - Commercial Passed 03/02/2017
Gas Service Inspection - Commercial Passed 03/02/2017
All Rough Inspection - Commercial Failed 03/02/2017
Misc
Corrective Action Required
03/02/2017
-FIRESTOP PENETRATIONS IN TOP PLATE TO ATTIC AREA. -FIREBLOCK AT FIREPLACE AND SOUTH EAST BATH DOUBLE WALL. -INSTALL STRUCTURAL STRAPS AT EXTERIOR WALLS WHERE 50% OF THE TOP PLATES HAVE BEEN DRILLED OR NOTCHED. -INSTALL PLUMBING PROTECTION AT TOP AND BOTTOM PLATES. OKAY TO ROCK THE LIDS OF THE HALLWAYS AND ONE SIDE OF THE HALLWAYS
All Rough Inspection - Commercial Passed 3/10/2017 03/10/2017
Misc
Resolved
03/10/2017
-FIRESTOP PENETRATIONS IN TOP PLATE TO ATTIC AREA. -FIREBLOCK AT FIREPLACE AND SOUTH EAST BATH DOUBLE WALL. -INSTALL STRUCTURAL STRAPS AT EXTERIOR WALLS WHERE 50% OF THE TOP PLATES HAVE BEEN DRILLED OR NOTCHED. -INSTALL PLUMBING PROTECTION AT TOP AND BOTTOM PLATES. OKAY TO ROCK THE LIDS OF THE HALLWAYS AND ONE SIDE OF THE HALLWAYS
Water Service Inspection Passed 3/21/2017 (1:45) 3/21/2017 03/21/2017
Above Ceiling Inspection Passed 4/11/2017 04/11/2017
Sprinkler - Hydrostatic Test Passed 5/9/2017 05/09/2017
Underground Electrical Inspection - Commercial Partial 5/31/2017 5/31/2017 05/31/2017
Misc
Corrective Action Required
05/31/2017
-4 LIGHT POLE PIERS OK; HOWEVER, THE UNDERGROUND RACEWAY MUST BE MIN. 24" BELOW THE DRIVEWAY&PARKING LOT
Electrical Service Inspection Failed 6/27/2017 6/27/2017 06/27/2017
Misc
Corrective Action Required
06/27/2017
-SUBMIT NEW ELECTRICAL SERVICE DIAGRAM THAT INCLUDES THE GENERATOR AND TRANSFER SWITCH/SERVICE DISCONNECT TO THE CITY FOR APPROVAL -PROVIDE MIN. 3 FT WORKING CLEARANCE IN FRONT OF THE SERVICE EQUIPMENTS -INSTALL EQUIPMENT GROUNDING CONDUCTOR FOR EACH PARALLEL FEEDER RACEWAY SIZED PER 250.122 -INSTALL BUSHINGS
Underground Electrical Inspection - Commercial Passed 7/5/2017 07/05/2017
Misc
Resolved
07/05/2017
-4 LIGHT POLE PIERS OK; HOWEVER, THE UNDERGROUND RACEWAY MUST BE MIN. 24" BELOW THE DRIVEWAY&PARKING LOT
Electrical Service Inspection Passed 7/5/2017 07/05/2017
Misc
Resolved
07/05/2017
-SUBMIT NEW ELECTRICAL SERVICE DIAGRAM THAT INCLUDES THE GENERATOR AND TRANSFER SWITCH/SERVICE DISCONNECT TO THE CITY FOR APPROVAL -PROVIDE MIN. 3 FT WORKING CLEARANCE IN FRONT OF THE SERVICE EQUIPMENTS -INSTALL EQUIPMENT GROUNDING CONDUCTOR FOR EACH PARALLEL FEEDER RACEWAY SIZED PER 250.122 -INSTALL BUSHINGS
Alarm Test Passed 7/26/2017 07/26/2017
Sprinkler - Flow Test Passed 7/26/2017 07/26/2017
Occupancy Inspection - Water Utilities Passed 07/27/2017
Occupancy Inspection - Fire Temporary C of O 7/27/2017 07/27/2017
Occupancy Inspection - Planning Failed 07/27/2017
Occupancy Inspection - Planning Temporary C of O 08/01/2017
Corrective Action Required
08/01/2017
General site clean up is needed.
Corrective Action Required
08/01/2017
Additional landscape screening is needed for the ground mounted units (GMU), located on the rear (east elevation) of the building and located on the north side of building. The screening of the GMU located on the north side of the building was discussed with the owner suggesting to locate a couple of evergreen trees on the north green space area of the side yard to screen the visual of the GMU from I-470 and any future tenants to the north.
Occupancy Inspection - Codes Commercial Temporary C of O 08/02/2017
Misc
Corrective Action Required
07/28/2017
-OBTAIN APPROVAL FROM OTHER DEVELOPMENT DIVISIONS: PLANNING, FIRE, WATER, AND ENGINEERING. OUTSTANING ISSUES UNDER SEPARATE COVER. -SUBMIT CODE MODIFICATION FOR WORKING CLEARANCE IN FRONT OF TRANSFORMER TRANSFER SWITCH. -ALL EXTERIOR RECEPTACLES REQUIRED TO BE SUITABLE FOR WET LOCATIONS. -INSTALL PERMANANT ADDRESS VISABLE FROM PUBLIC WAY. (TEMP ADDRESS INSTALLED) -COMPLETE ALL BATHROOMS, INSTALL KNEE GUARDS FOR SINKS
Occupancy Inspection - Codes Commercial Temporary C of O 08/02/2017
Misc
Corrective Action Required
08/02/2017
-OBTAIN APPROVAL FROM OTHER DEVELOPMENT DIVISIONS: PLANNING, FIRE, WATER, AND ENGINEERING. OUTSTANING ISSUES UNDER SEPARATE COVER. -SUBMIT CODE MODIFICATION FOR WORKING CLEARANCE IN FRONT OF TRANSFORMER TRANSFER SWITCH. -ALL EXTERIOR RECEPTACLES REQUIRED TO BE SUITABLE FOR WET LOCATIONS. -INSTALL PERMANANT ADDRESS VISABLE FROM PUBLIC WAY. (TEMP ADDRESS INSTALLED) -COMPLETE ALL BATHROOMS, INSTALL KNEE GUARDS FOR SINKS
Occupancy Inspection - Fire Passed 8/3/2017 08/03/2017
Occupancy Inspection - Planning Passed 10/18/2017
Occupancy Inspection - Codes Commercial Full C of O 11/6/2017 11/06/2017
Misc
Resolved
11/06/2017
-OBTAIN APPROVAL FROM OTHER DEVELOPMENT DIVISIONS: PLANNING, FIRE, WATER, AND ENGINEERING. OUTSTANING ISSUES UNDER SEPARATE COVER. -SUBMIT CODE MODIFICATION FOR WORKING CLEARANCE IN FRONT OF TRANSFORMER TRANSFER SWITCH. -ALL EXTERIOR RECEPTACLES REQUIRED TO BE SUITABLE FOR WET LOCATIONS. -INSTALL PERMANANT ADDRESS VISABLE FROM PUBLIC WAY. (TEMP ADDRESS INSTALLED) -COMPLETE ALL BATHROOMS, INSTALL KNEE GUARDS FOR SINKS
Documents & Images
Date Uploaded File Type Document Name
04/14/2016 Letter Fire Building Plan Review
04/20/2016 Letter Codes P/R Corrections Document
05/03/2016 Letter Fire Building Plan Review
05/03/2016 Special Inspections letter
08/10/2016 Receipt Receipt for transaction: 2016-005376
08/30/2016 Letter Codes Plan Review Conditions
09/01/2016 Letter Codes Building Permit
10/12/2016 Letter Inspection Summary
12/28/2016 Letter Fire (Sprinkler) Plan Review
02/10/2017 Letter Fire (Alarm) Plan Review Notice
02/22/2017 Letter Inspection Summary
03/02/2017 Letter Inspection Summary
03/10/2017 Letter Inspection Summary
03/21/2017 Letter Inspection Summary
04/11/2017 Letter Inspection Summary
04/11/2017 Letter Inspection Summary
05/31/2017 Letter Inspection Summary
06/27/2017 Letter Inspection Summary
07/05/2017 Letter Inspection Summary
07/17/2017 Letter Fire Building Plan Review
07/28/2017 Letter Inspection Summary
08/02/2017 Letter Codes Temporary Certificate of Occupancy
08/02/2017 Letter Codes Temporary Certificate of Occupancy
11/06/2017 Letter Field Certificate of Occupancy
11/07/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home