Permit Application Status

PRCOM20160737


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20160737
Building Permit - Commercial
Certificate of Occupancy
RMT INVESTMENTS INC
CHANGE OF TENANT
CHANGE OF TENANT FOR CHILD/PARENT PLAY ** drawings are in plan review file
04/06/2016
07/08/2016
11/21/2016
08/04/2016
Locations
Contacts
ALLIANCE MECHANICAL CONTRACTORS, Address:305 W CEDAR , Phone:(913) 553-2600  
SULLIVAN PALMER ARCHITECTS, Address:8849 LONG, Phone:(913) 888-8540  
RMT INVESTMENTS INC, Address:444 RIVERFRONT PLZ APT 604  
COMPLETE CONSTRUCTION SERVICE, Address:5919 BARTON DR, Phone:(913) 387-4796  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 06/07/2016 07/08/2016
Mike Weisenborn
LC - General Contractor
Resolved
07/08/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
07/08/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
Building Plan Review Approved with Conditions 06/14/2016 06/10/2016
Joe Frogge
Bldg - Panic and fire exit hardware 1008.1.10
Resolved
06/10/2016

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Provide panic hardware at exits. 5/24/16 - not found on plans. To be field verified
Bldg - Occupant load posting 1004.3
Corrective Action Required
06/07/2016

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. Posting to be field verified.
Misc
Resolved
06/10/2016

Additional information required to complete review. Action required: Provide plumbing and electrical designs or detailed scopes of work that covers all methods and materials. 5/24/16 - Specify pipe materials. (is there a planum return?) Specify types and sizes of wiring.
Code analysis required
Resolved
06/10/2016

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis complete occupant load. Change construction type to IIB and occupancy to A3. 5/24/16 - provide calcs/justification for listed occupant load. Must be calculated by use of spaces, not business plan.
License Tax Application
Corrective Action Required
06/07/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Fire Plan Review Approved with Conditions 06/14/2016 06/09/2016
Joe Dir
Address numbers required
Corrective Action Required
06/07/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 430 ON THE EXTERIOR OF THE FRONT NAD REAR DOORS READABLE FROM THE ROADWAY.
Misc
Partial Correction
06/07/2016

ANY EXSITING EXIT LIGHTS AND EMERGENCY LIGHTING SHALL BE FUNCTIONAL
Misc
Corrective Action Required
06/07/2016

All existing conditions subject to inspection and correction for occupancy.
Fire Plan Review Approved with Conditions 06/01/2016 05/24/2016
Jim Eden
Portable fire extinguishers - conspicuous locations
Resolved
05/24/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT FIRE EXTINGUISHERS SO THERE WILL BE A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANYWHERE WITHIN THE BUSINESS.
Portable fire extinguishers - general
Resolved
05/24/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE TWO 2A-10BC FIRE EXTINGUISHERS
Misc
Resolved
05/24/2016

No information about if an alarm system will be installed, occupancy load, electronic locks
Address numbers required
Corrective Action Required
05/24/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 430 ON THE EXTERIOR OF THE FRONT NAD REAR DOORS READABLE FROM THE ROADWAY.
Misc
Partial Correction
05/24/2016

ANY EXSITING EXIT LIGHTS AND EMERGENCY LIGHTING SHALL BE FUNCTIONAL
Misc
Corrective Action Required
05/24/2016

All existing conditions subject to inspection and correction for occupancy.
Building Plan Review Rejected 06/01/2016 05/24/2016
Joe Frogge
Plumb - Drinking fountain substitution 410.3
Resolved
05/24/2016

2012 IPC 410.3 – Substitution. Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those restaurants. In other occupancies, where drinking fountains are required, water coolers, bottled water dispensers or break rooms with a kitchen sink shall be permitted to be substituted for the required drinking fountains. (As amended by the City of Lee’s Summit.) Action required: Provide drinking fountain or provide a letter stating that bottled water will be provided to occupants. 5/24/16 - added to plan
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
05/24/2016

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Provide panic hardware at exits. 5/24/16 - not found on plans. To be field verified
Bldg - Occupant load posting 1004.3
Corrective Action Required
05/24/2016

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. Posting to be field verified.
Mech - Outdoor air required 403.2
Resolved
05/24/2016

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Provide outside air calculations and method of delivery. 5/24/16 - duct with control damper added to plan
Misc
Corrective Action Required
05/24/2016

Additional information required to complete review. Action required: Provide plumbing and electrical designs or detailed scopes of work that covers all methods and materials. 5/24/16 - Specify pipe materials. (is there a planum return?) Specify types and sizes of wiring.
Code analysis required
Corrective Action Required
05/24/2016

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis complete occupant load. Change construction type to IIB and occupancy to A3. 5/24/16 - provide calcs/justification for listed occupant load. Must be calculated by use of spaces, not business plan.
License Tax Application
Corrective Action Required
05/24/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Licensed Contractors Rejected 05/24/2016 05/24/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
05/24/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/24/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
Building Plan Review Rejected 04/18/2016 04/15/2016
Joe Frogge
License Tax Application
Corrective Action Required
04/15/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Code analysis required
Corrective Action Required
04/15/2016

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis complete occupant load. Change construction type to IIB and occupancy to A3.
Misc
Corrective Action Required
04/15/2016

Additional information required to complete review. Action required: Provide plumbing and electrical designs or detailed scopes of work that covers all methods and materials.
Mech - Outdoor air required 403.2
Corrective Action Required
04/15/2016

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Provide outside air calculations and method of delivery.
Bldg - Occupant load posting 1004.3
Corrective Action Required
04/15/2016

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. Posting to be field verified.
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
04/15/2016

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Provide panic hardware at exits.
Plumb - Drinking fountain substitution 410.3
Corrective Action Required
04/15/2016

2012 IPC 410.3 – Substitution. Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those restaurants. In other occupancies, where drinking fountains are required, water coolers, bottled water dispensers or break rooms with a kitchen sink shall be permitted to be substituted for the required drinking fountains. (As amended by the City of Lee’s Summit.) Action required: Provide drinking fountain or provide a letter stating that bottled water will be provided to occupants.
Licensed Contractors Rejected 04/18/2016 04/15/2016
Joe Frogge
LC - MEP Subs
Corrective Action Required
04/15/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
LC - General Contractor
Corrective Action Required
05/16/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Fire Plan Review Rejected 04/18/2016 04/15/2016
Joe Dir
Misc
Corrective Action Required
04/07/2016

ANY EXSITING EXIT LIGHTS AND EMERGENCY LIGHTING SHALL BE FUNCTIONAL
Address numbers required
Corrective Action Required
04/07/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 430 ON THE EXTERIOR OF THE FRONT NAD REAR DOORS READABLE FROM THE ROADWAY.
Misc
Corrective Action Required
04/15/2016

No information about if an alarm system will be installed, occupancy load, electronic locks
Portable fire extinguishers - general
Corrective Action Required
04/15/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE TWO 2A-10BC FIRE EXTINGUISHERS
Portable fire extinguishers - conspicuous locations
Corrective Action Required
04/15/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT FIRE EXTINGUISHERS SO THERE WILL BE A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANYWHERE WITHIN THE BUSINESS.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.64 $30.64 Paid 07/08/2016
8331507-Sewer Connection Fee $60.00 $60.00 Paid 07/08/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rated Assembly Inspection Not Ready 7/11/2016 7/11/2016 07/11/2016
Misc
Corrective Action Required
07/11/2016
NO ACCESS- PROVIDE LOCK BOX AND CODE OR BUILDING NEED TO BE OPEN DAY OF INSPECTION. RECALL WHEN READY POST PERMIT AT FRONT DOOR
Underslab Plumbing Inspection - Commercial Not Ready 7/11/2016 7/11/2016 07/11/2016
Rated Assembly Inspection Failed 7/12/2016 7/12/2016 07/12/2016
Misc
Corrective Action Required
07/11/2016
-RATED WALL- INSTALLED 1" ROCK WITHOUT INSTALLING 1"X2" L STRIP ON FACE OF EXISTING WALL. CHANGE UL LISTING TO MATCH WHAT IS ON SITE OR REMOVE AND RECALL FOR "L" STRIP FRAMING INSPECTION. REVISE PLANS .
Underslab Plumbing Inspection - Commercial Passed 7/12/2016 7/12/2016 07/12/2016
All Rough Inspection - Commercial Partial 7/19/2016 7/19/2016 07/19/2016
Misc
Corrective Action Required
07/19/2016
PARTIAL WALL FRAMING INSPECTION RESTROOM WALLS OK TO COVER PENDING APPROVAL OF FIREWALL AND UL LISTING.
Above Ceiling Inspection Failed 7/29/2016 7/29/2016 07/29/2016
Misc
Corrective Action Required
07/29/2016
ABOVE-CEILING INSPECTION REQUESTED AT RESTROOMS ONLY: VENT FANS NOT DUCTED TO EXTERIOR. DO NOT COVER. REQUEST RE-INSPECTION WHEN READY.
Rated Assembly Inspection Passed 8/1/2016 8/1/2016 08/01/2016
Misc
Corrective Action Required
08/01/2016
As per email attached to CV and Conversation with the Engineer of record & Joe Frogge they feel it meets the intent of the code.
Occupancy Inspection - Codes Commercial Full C of O 8/4/2016 8/4/2016 08/04/2016
Above Ceiling Inspection Passed 08/04/2016
Misc
Resolved
08/04/2016
ABOVE-CEILING INSPECTION REQUESTED AT RESTROOMS ONLY: VENT FANS NOT DUCTED TO EXTERIOR. DO NOT COVER. REQUEST RE-INSPECTION WHEN READY.
Occupancy Inspection - Fire Passed 8/4/2016 08/04/2016
Documents & Images
Date Uploaded File Type Document Name
04/07/2016 Letter Fire Building Plan Review
04/15/2016 Letter Fire Building Plan Review
04/15/2016 Letter Codes P/R Corrections Document
05/25/2016 Letter Codes P/R Corrections Document
06/09/2016 Letter Fire Building Plan Review
06/10/2016 Letter Codes P/R Corrections Document
07/08/2016 Letter Codes Plan Review Conditions
07/08/2016 Receipt Receipt for transaction: 2016-004670
07/08/2016 Letter Codes Building Permit
07/11/2016 Letter Inspection Summary
07/12/2016 Letter Inspection Summary
07/19/2016 Letter Inspection Summary
07/27/2016 LS Play 2hr wall
07/29/2016 Letter Inspection Summary
08/01/2016 Letter Inspection Summary
08/04/2016 Letter Field Certificate of Occupancy
08/04/2016 Letter Codes Final Certificate of Occupancy
08/05/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home