Permit Application Status

PRCOM20151744


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151744
Building Permit - Commercial
Certificate of Occupancy
MARION RIDGE SAFETY STORAGE LLC
NEW SHELL BUILDING
NEW SHELL BUILDING
08/03/2015
10/15/2015
02/10/2016
10/09/2017
Locations
Contacts
WARD DEVELOPMENT & INVESTMENT CO, Address:1120 NW EAGLE RIDGE BLVD, Phone:(816) 229-8115  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
A & A ELECTRICAL INC, Address:705 SQUIRE CT, Phone:(816) 847-1902  
R2 PLUMBING LLC, Address:1705 A SE COUNTY RD AA, Phone:(816) 215-8098  
DAVIDSON ARCHITECTURE & ENGINEERING - PAUL MILLER, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
MARION RIDGE SAFETY STORAGE LLC, Address:1101 C NW PAMELA BLVD  
DAVID WARD, Address:1120 NW EAGLE RIDGE BLVD, Phone:(816) 229-8115  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 08/05/2016
Joe Dir
Misc
Corrective Action Required
08/05/2016

905.1 General. Standpipe systems shall be provided in new buildings and structures in accordance with this section and as required by the code official. Fire hose threads used in connection with standpipe systems shall be approved and shall be compatible with fire department hose threads. The location of fire department hose connections shall be approved. In buildings used for high-piled combustible storage, fire protection shall be in accordance with Chapter 32. 3206.8 Fire department hose connections. Where exit passageways are required by the International Building Code for egress, a Class I standpipe system shall be provided in accordance with Section 905. INSTALL A CLASS 1 STANDPIPE CONNECTION AT A NORTH SIDE MAN DOOR AND ONE AT A SOUTH SIDE MAN DOOR.
Installation acceptance testing
Corrective Action Required
08/05/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Misc
Corrective Action Required
08/05/2016

Section 903.3.7 Fire department connections. The location of the fire department connections shall be approved by the fire code official. Connections shall be a 4 inch stortz fitting and located within 100 feet of a fire hydrant or as approved by the code official. (INCLUDE A 30 DEGREE ELBOW)
Alarm Plan Review Released for Construction 12/31/2015
Joe Dir
Building Plan Review Approved with Conditions 08/27/2015 09/18/2015
Joe Frogge
Final Development Plan
Resolved
09/18/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Code analysis required
Resolved
08/21/2015

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update drawings to include complete code analysis. 8/21/15 - provided and approved
Mech - Equipment and appliances on roofs or elevated structures 306.5
Corrective Action Required
09/18/2015

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Provide permanent means of access for roof mounted equipment. (This may be deferred to tenant finish projects) 8/21/15 - deferred to tenant finish
Misc 12
Resolved
09/10/2015

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 8/21/15 - acknowledged - pending 9/10/15 - received
Misc 13
Corrective Action Required
09/18/2015

Note: this review is for a shell structure only. Additional plan reviews required for all future tenant finishes.
Final Development Plan Review Approved 10/16/2015 09/18/2015
Joe Frogge
Special Inspections Review Approved 09/10/2015
Joe Frogge
Licensed Contractors Approved 08/20/2015 09/01/2015
Joe Frogge
LC - MEP Subs
Resolved
09/01/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Plumbing Contractor. Arrow Plumbing is not currently licensed to work in Lee's Summit.
Fire Plan Review Approved with Conditions 08/27/2015 08/25/2015
Joe Dir
Misc
Corrective Action Required
08/20/2015

Construction documents for fire alarm systems
Corrective Action Required
08/20/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for the alarm system. Acknowledged in letter from Davidson A&E.
Knox box required
Corrective Action Required
08/20/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Knox box to be mounted approximately 6' off finish grade above the FDC. To obtain an application for a knox box call 816-969-1300. Acknowledged in letter from Davidson A&E
Construction documents - Fire protection systems
Corrective Action Required
08/20/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for the fire supression sprinkler system. Acknowledged in letter from Davidson A&E
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/20/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Mounted on a wall within a 75 foot travel distance. One for every 6000 sq feet. Corrected on resub drawings.
Misc
Corrective Action Required
08/20/2015

Plans to include a door schedule. Addressed in letter from Davidson A&E
Misc
Corrective Action Required
08/20/2015

Plans to include a site plan
Misc
Corrective Action Required
08/20/2015

Review is for a shell building, modification to building may be required according to use of building. Submitt tenant finish plans as applicable
Building Plan Review Rejected 08/17/2015 08/14/2015
Joe Frogge
Final Development Plan
Corrective Action Required
08/14/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Code analysis required
Corrective Action Required
08/14/2015

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update drawings to include complete code analysis.
Mech - Equipment and appliances on roofs or elevated structures 306.5
Corrective Action Required
08/14/2015

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Provide permanent means of access for roof mounted equipment. (This may be deferred to tenant finish projects)
Misc 12
Corrective Action Required
08/14/2015

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Misc 13
Corrective Action Required
08/14/2015

Note: this review is for a shell structure only. Additional plan reviews required for all future tenant finishes.
Licensed Contractors Rejected 08/17/2015 08/14/2015
Joe Frogge
LC - MEP Subs
Corrective Action Required
08/14/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Plumbing Contractor. Arrow Plumbing is not currently licensed to work in Lee's Summit.
Fire Plan Review Rejected 08/17/2015 08/06/2015
Joe Dir
Misc
Corrective Action Required
08/06/2015

Provide code analysis, building shall comply with 2012 IFC.
Construction documents for fire alarm systems
Corrective Action Required
08/06/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for the alarm system.
Knox box required
Corrective Action Required
08/06/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Knox box to be mounted approximately 6' off finish grade above the FDC. To obtain an application for a knox box call 816-969-1300
Construction documents - Fire protection systems
Corrective Action Required
08/06/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for the fire supression sprinkler system
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/06/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Mounted on a wall within a 75 foot travel distance. One for every 6000 sq feet.
Misc
Corrective Action Required
08/06/2015

Plans to include a door schedule.
Misc
Corrective Action Required
08/06/2015

Plans to include a site plan
Misc
Corrective Action Required
08/06/2015

Review is for a shell building, modification to building may be required according to use of building. Submitt tenant finish plans as applicable
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Shell Building $8,747.50 $8,747.50 Paid 10/15/2015
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 10/15/2015
8331401-Water Tap Fee $9,642.00 $9,642.00 Paid 10/15/2015
8350015-Water Meter Fee $1,131.54 $1,131.54 Paid 10/15/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 4/12/2016 (8:00) 4/12/2016 04/12/2016
Misc
Corrective Action Required
04/12/2016
PERIMETER FOOTING OK FROM 4/A CLOCKWISE TO SW CORNER OF BUILDING
Footing Inspection - Commercial Not Ready 4/13/2016 (8:00) 4/13/2016 04/13/2016
Misc
Partial Correction
04/13/2016
PERIMETER FOOTING OK FROM 4/A CLOCKWISE TO SW CORNER OF BUILDING
Misc
Corrective Action Required
04/13/2016
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: NONE READY -- TOP MAT REQUIRED.
Footing Inspection - Commercial Partial 4/13/2016 (10:00) 4/13/2016 04/13/2016
Misc
Partial Correction
04/13/2016
PERIMETER FOOTING OK FROM 4/A CLOCKWISE TO SW CORNER OF BUILDING
Misc
Partial Correction
04/13/2016
OK TO POUR WHEN READY TWELVE INTERIOR ISOLATED FOOTINGS
Underslab Plumbing Inspection - Commercial Partial 4/14/2016 4/14/2016 04/14/2016
Misc
Corrective Action Required
04/14/2016
UNDERSLAB PLUMBING OK: -WHOLE EAST SIDE 4" BUILDING DRAIN; WEST SIDE BUILDING DRAIN ENDS A LITTLE PASS THE FLOOR CLEANOUT NEAR D LINE
Underslab Plumbing Inspection - Commercial Partial 4/18/2016 4/18/2016 04/18/2016
Misc
Corrective Action Required
04/14/2016
UNDERSLAB PLUMBING OK: -BUILDING DRAIN: WHOLE EAST SIDE, WEST SIDE ENDS AT SPRINKLER RM, AND SOUTH SIDE ENDS AT MID CLEANOUT
Underslab Electrical Inspection - Commercial Partial 4/21/2016 4/21/2016 04/21/2016
Misc
Partial Correction
04/21/2016
UE OK FOR NORTHERN HALF OF BUILDING
Underslab Plumbing Inspection - Commercial Partial 4/22/2016 4/22/2016 04/22/2016
Misc
Corrective Action Required
04/18/2016
UNDERSLAB PLUMBING OK: -BUILDING DRAIN: WHOLE EAST AND SOUTH BUILDING DRAIN; WEST BUILDING DRAIN FROM NORTH END TO SPRINKLER RM
Underslab Plumbing Inspection - Commercial Partial 4/25/2016 4/25/2016 04/25/2016
Misc
Corrective Action Required
04/22/2016
UNDERSLAB PLUMBING OK: -BUILDING DRAIN: WHOLE EAST AND SOUTH BUILDING DRAIN; WEST BUILDING DRAIN FROM NORTH END TO SPRINKLER RM, ~40 FT SOUTH FROM SPRINKLER RM
Underslab Electrical Inspection - Commercial Passed 5/3/2016 5/3/2016 05/03/2016
Misc
Resolved
05/03/2016
UE OK FOR NORTHERN HALF OF BUILDING
Footing Inspection - Commercial Partial 5/6/2016 (8:00) 5/6/2016 05/06/2016
Misc
Partial Correction
04/13/2016
PERIMETER FOOTING OK, EXCEPT THE WEST SIDE FROM SW CORNER TO C GRID LINE
Misc
Partial Correction
04/13/2016
OK TO POUR WHEN READY TWELVE INTERIOR ISOLATED FOOTINGS
Footing Inspection - Commercial Partial 5/31/2016 (10:00) 5/31/2016 05/31/2016
Misc
Partial Correction
05/06/2016
PERIMETER FOOTING OK, EXCEPT AT FOOTING JUMP LOCATIONS
Misc
Partial Correction
05/06/2016
OK TO POUR WHEN READY TWELVE INTERIOR ISOLATED FOOTINGS
Footing Inspection - Commercial Partial 6/2/2016 (2:30) 6/2/2016 06/02/2016
Misc
Partial Correction
05/31/2016
PERIMETER FOOTING OK, EXCEPT AT SW FOOTING JUMP LOCATION
Misc
Resolved
06/02/2016
OK TO POUR WHEN READY TWELVE INTERIOR ISOLATED FOOTINGS
Underslab Plumbing Inspection - Commercial Partial 6/10/2016 06/10/2016
Misc
Corrective Action Required
04/25/2016
UNDERSLAB PLUMBING OK: -BUILDING DRAIN: WHOLE EAST, SOUTH , AND WEST BUILDING DRAIN
Underground Electrical Inspection - Commercial Partial 8/15/2016 8/15/2016 08/15/2016
Misc
Partial Correction
08/15/2016
4 4" COUNDUITS FROM TRANSFORMER TO GEAR AT WEST SIDE OF BUILIDING APPROVED.
Electrical Service Inspection Failed 9/28/2016 9/27/2016 09/27/2016
Misc
Corrective Action Required
09/27/2016
-EXPOSE THE WIRING&GROUNDING CONNECTION INSIDE TRANSFORMER. -ISOLATE THE GROUNDED FROM THE GROUNDING CONDUCTORS INSIDE THE 120/240V PANEL. THE SYSTEM BONDING CONNECTION IS ALLOWED ONLY AT THE ENCLOSURE WHERE THE GROUNDING CONNECTION FOR THE SEPARATELY DERIVED SYSTEM IS MADE, EITHER AT THE SOURCE OR THE 1ST DISCONNECTING MEAN
Electrical Service Inspection Passed 9/30/2016 9/30/2016 09/30/2016
Misc
Resolved
09/30/2016
-EXPOSE THE WIRING&GROUNDING CONNECTION INSIDE TRANSFORMER. -ISOLATE THE GROUNDED FROM THE GROUNDING CONDUCTORS INSIDE THE 120/240V PANEL. THE SYSTEM BONDING CONNECTION IS ALLOWED ONLY AT THE ENCLOSURE WHERE THE GROUNDING CONNECTION FOR THE SEPARATELY DERIVED SYSTEM IS MADE, EITHER AT THE SOURCE OR THE 1ST DISCONNECTING MEAN
Underslab Plumbing Inspection - Commercial Partial 10/17/2016 10/17/2016 10/17/2016
Misc
Corrective Action Required
06/10/2016
UNDERSLAB PLUMBING OK: -BUILDING DRAIN: WHOLE EAST, SOUTH , AND WEST BUILDING DRAIN -SPRINKLER RM UNDERSLAB PLUMBING OK
Underground Electrical Inspection - Commercial Not Ready 4/25/2017 4/25/2017 04/25/2017
Misc
Partial Correction
08/15/2016
4 4" COUNDUITS FROM TRANSFORMER TO GEAR AT WEST SIDE OF BUILIDING APPROVED. APR-25-SUPERINTENDANT NOT ON SITE. INSPECTION CANCELED AS NOT READY
Underground Electrical Inspection - Commercial Partial 4/26/2017 4/26/2017 04/26/2017
Misc
Partial Correction
04/25/2017
4 4" COUNDUITS FROM TRANSFORMER TO GEAR AT WEST SIDE OF BUILIDING APPROVED. -LIGHT POLE PIER AT SOUTH SIDE OF BUILDING-OK
Sprinkler - Hydrostatic Test Passed 5/4/2017 05/04/2017
Water Service Inspection Passed 5/18/2017 (8:00) 5/18/2017 05/18/2017
Electrical Service Inspection Failed 6/7/2017 6/7/2017 06/07/2017
Misc
Corrective Action Required
06/07/2017
-GROUND THE TRANSFORMER
Electrical Service Inspection Passed 6/12/2017 6/12/2017 06/12/2017
Misc
Resolved
06/12/2017
-GROUND THE TRANSFORMER
Gas Service Inspection - Commercial Partial 7/25/2017 7/25/2017 07/25/2017
Misc
Corrective Action Required
07/25/2017
PARTIAL GAS TEST OK-THREE GAS LINES FROM ROOF TO INDOOR FURNACES
Underground Electrical Inspection - Commercial Passed 08/11/2017
Misc
Resolved
08/11/2017
4 4" COUNDUITS FROM TRANSFORMER TO GEAR AT WEST SIDE OF BUILIDING APPROVED. -LIGHT POLE PIER AT SOUTH SIDE OF BUILDING-OK
Underslab Plumbing Inspection - Commercial Passed 08/11/2017
Misc
Resolved
08/11/2017
UNDERSLAB PLUMBING OK: -BUILDING DRAIN: WHOLE EAST, SOUTH , AND WEST BUILDING DRAIN -SPRINKLER RM UNDERSLAB PLUMBING OK
Footing Inspection - Commercial Passed 08/11/2017
Misc
Resolved
08/11/2017
PERIMETER FOOTING OK, EXCEPT AT SW FOOTING JUMP LOCATION
Gas Service Inspection - Commercial Passed 08/11/2017
Misc
Resolved
08/11/2017
PARTIAL GAS TEST OK-THREE GAS LINES FROM ROOF TO INDOOR FURNACES
Occupancy Inspection - Codes Commercial Temporary C of O 8/11/2017 8/11/2017 08/11/2017
Misc
Corrective Action Required
08/11/2017
-SUBMIT SPECIAL INSPECTION APPROVAL -APPROVAL FROM THE FOLLOWING DEPTS REQUIRED: FIRE, PUBLIC WORKS, PLANNING, WATER -INSTALL LADDER TO ROOFTOP -PAINT RUSTED ROOFTOP GAS PIPING
Occupancy Inspection - Water Utilities Passed 08/11/2017
Occupancy Inspection - Planning Temporary C of O 08/15/2017
Corrective Action Required
08/15/2017
The accessible signage does not meet the type of accessible signage for Lee's Summit. The sign shall be a white background with a green border.
Corrective Action Required
08/15/2017
The roof ladder shall be painted to blend in with the building.
Occupancy Inspection - Planning Passed 10/06/2017
Occupancy Inspection - Codes Commercial Full C of O 10/9/2017 10/09/2017
Misc
Resolved
10/09/2017
-APPROVAL FROM THE FOLLOWING DEPTS REQUIRED: FIRE
Sprinkler - Hydrostatic Test Failed 3/1/2018 03/01/2018
Sprinkler - Hydrostatic Test Passed 3/2/2018 03/02/2018
Documents & Images
Date Uploaded File Type Document Name
08/06/2015 Letter Fire Building Plan Review
08/14/2015 Letter Codes P/R Corrections Document
08/25/2015 Letter Fire Building Plan Review
08/25/2015 Letter Codes P/R Corrections Document
09/10/2015 Statement of Spec. Insp.
09/18/2015 Letter Codes Plan Review Conditions
10/15/2015 Receipt Receipt for transaction: 2015-005774
10/15/2015 Letter Codes Building Permit
04/12/2016 Letter Inspection Summary
04/13/2016 Letter Inspection Summary
04/14/2016 Letter Inspection Summary
04/18/2016 Letter Inspection Summary
04/21/2016 Letter Inspection Summary
04/22/2016 Letter Inspection Summary
04/25/2016 Letter Inspection Summary
05/03/2016 Letter Inspection Summary
05/06/2016 Letter Inspection Summary
05/31/2016 Letter Inspection Summary
06/02/2016 Letter Inspection Summary
06/10/2016 Letter Inspection Summary
08/05/2016 Letter Fire (Sprinkler) Plan Review
09/27/2016 Letter Inspection Summary
09/30/2016 Letter Inspection Summary
10/17/2016 Letter Inspection Summary
04/25/2017 Letter Inspection Summary
04/26/2017 Letter Inspection Summary
05/18/2017 Letter Inspection Summary
06/07/2017 Letter Inspection Summary
06/12/2017 Letter Inspection Summary
07/25/2017 Letter Inspection Summary
08/11/2017 Letter Inspection Summary
10/09/2017 Letter Field Certificate of Occupancy
10/13/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home