Permit Application Status

PRCOM20151379


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151379
Building Permit - Commercial
Certificate of Occupancy
CECEMEGMITSCHSQ LLC
NEW TENANT FINISH
OFFICE SPACE FOR CONSULTING COMPANY
06/18/2015
06/25/2015
08/27/2015
Locations
Contacts
JDS CONSTRUCTION SERVICES LLC, Address:1616 NW NICHOLAS DR, Phone:(816) 522-4641  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
CECEMEGMITSCHSQ LLC, Address:708 NW COMMERCE DR  
WACHTER INC, Address:16001 W 99TH ST, Phone:(913) 541-2500  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2015
Joe Dir
Sprinkler Plan Review Released for Construction 12/31/2015
Joe Dir
Building Plan Review Approved 06/30/2015 06/24/2015
Joe Frogge
Fire Plan Review Approved with Conditions 06/30/2015 06/23/2015
Jim Eden
Address numbers required
Corrective Action Required
06/23/2015

IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). All numbering on the front and rear doors shall be the same. Verified at inspection.
Misc
Corrective Action Required
06/23/2015

IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. Provide "as built" plans. Verified at inspection.
Misc
Corrective Action Required
06/23/2015

901.4.1 Required fire protection systems. Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. The building sprinkler system shall have documentation of a current annual inspection. Verified at inspection.
Misc
Corrective Action Required
06/23/2015

Extend alarm notification appliances as needed. Verified and tested at inspection.
Licensed Contractors Approved 06/30/2015 06/18/2015
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Tenent Finish $118.69 $118.69 Paid 06/25/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Not Ready 7/7/2015 7/7/2015 at 12:00 AM 07/07/2015
Misc
Corrective Action Required
07/07/2015
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
In-wall Inspection Passed 7/8/2015 7/8/2015 at 12:00 AM 07/08/2015
Misc
Resolved
07/08/2015
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Underslab Electrical Inspection - Commercial Passed 7/8/2015 at 12:00 AM 07/08/2015
Above Ceiling Inspection Failed 8/18/2015 8/18/2015 at 12:00 AM 08/18/2015
Misc
Corrective Action Required
08/18/2015
ENSURE ALL INTERIOR WALL BRACES ARE SECURELY FASTENED BOTH ENDS
Misc
Corrective Action Required
08/18/2015
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT AND INSULATION: SUPPORT FLEX DUCT TO STRUCTURE AT 5' MAXIMUM INTERVALS. CLAMPS & TAPING OF INNER AND OUTER LAYER MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS. CHECK ALL.
Misc
Corrective Action Required
08/18/2015
NEC 300-11, 330.30 & 334-10 SECURELY FASTEN MC ELECTRICAL CABLE WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]. CHECK ALL.
Misc
Corrective Action Required
08/18/2015
NEC 110-12: PLUG UNUSED OPENINGS AT JUNCTION BOXES. IF NOT BOTH PORTS OF DOUBLE SLAMMERS ARE USED REPLACE WITH SINGLE CONNECTOR. CHECK ALL.
Misc
Corrective Action Required
08/18/2015
NOTED THAT CEILING R.A. PLENUM SPACE CONTAINS PVC PLUMBING VENT PIPING CONTRARY TO IBC.
Above Ceiling Inspection Passed 8/25/2015 8/25/2015 at 12:00 AM 08/25/2015
Misc
Resolved
08/25/2015
ENSURE ALL INTERIOR WALL BRACES ARE SECURELY FASTENED BOTH ENDS
Misc
Resolved
08/25/2015
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT AND INSULATION: SUPPORT FLEX DUCT TO STRUCTURE AT 5' MAXIMUM INTERVALS. CLAMPS & TAPING OF INNER AND OUTER LAYER MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS. CHECK ALL.
Misc
Resolved
08/25/2015
NEC 300-11, 330.30 & 334-10 SECURELY FASTEN MC ELECTRICAL CABLE WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]. CHECK ALL.
Misc
Resolved
08/25/2015
NEC 110-12: PLUG UNUSED OPENINGS AT JUNCTION BOXES. IF NOT BOTH PORTS OF DOUBLE SLAMMERS ARE USED REPLACE WITH SINGLE CONNECTOR. CHECK ALL.
Occupancy Inspection - Codes Commercial Full C of O 8/27/2015 8/27/2015 at 12:00 AM 08/27/2015
Occupancy Inspection - Fire Passed 8/27/2015 at 12:00 AM 08/27/2015
Documents & Images
Date Uploaded File Type Document Name
06/24/2015 Letter Codes Plan Review Conditions
06/25/2015 Receipt Receipt for transaction: 2015-003436
06/25/2015 Letter Codes Building Permit
07/07/2015 Letter Inspection Summary
07/08/2015 Letter Inspection Summary
08/18/2015 Letter Inspection Summary
08/25/2015 Letter Inspection Summary
08/27/2015 Letter Field Certificate of Occupancy
08/28/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home