Permit Application Status

PRCOM20150781


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150781
Building Permit - Commercial
Certificate of Occupancy
LBC INVESTMENTS LLC
NEW TENANT FINISH
TENANT FINISH FOR INDOOR TRAMPOLINE GYMNASIUM WITH PARTY ROOMS AND FOOD SERVICE
04/13/2015
08/05/2015
10/14/2015
02/05/2016
Locations
Contacts
LITTLE DIXIE CONSTRUCTION LLC, Address:1431 CINNAMON HILL LN STE 209, Phone:(573) 449-7200  
TEMP-CON LLC, Address:15670 S KEELER ST, Phone:(913) 768-4888  
S & S ELECTRICAL CONTRACTING LLC, Address:574 NW 1921 RD, Phone:(816) 847-2433  
SUMMIT MECHANICAL INC, Address:5324 ALGOA RD, Phone:(573) 636-4050  
ABELN & ASSOCIATES ARCHITECTS, Address:11827 W 112TH ST, SUITE 220, Phone:(913) 345-8833  
LBC INVESTMENTS LLC, Address:302 CAMPUSVIEW DR STE 211  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 09/11/2015
Jim Eden
DE Corps of Engineers
Corrective Action Required
09/11/2015

Provide an exterior horn/strobe over the fire department connection (FDC). Activated by waterflow only. Verified at inspection.
Misc
Corrective Action Required
09/11/2015

2012 IFC 907.1.3 Equipment. Systems and components shall be listed and approved for the purpose for which they are installed. Action required: Provide equipment specifications. Verified at inspection.
Installation acceptance testing
Corrective Action Required
09/11/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 9691303 to schedule testing.
Misc
Corrective Action Required
09/11/2015

IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1.The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2.In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. Action required; Duct detection signals shall be supervisory only. Verified at testing.
Fire Plan Review Approved 05/12/2015 08/05/2015
Joe Dir
Knox box required
Corrective Action Required
08/05/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. Knox box is to be located over the FDC and under the outside horn/strobe. 5-6-15 resolved
Construction documents - Fire protection systems
Corrective Action Required
08/05/2015

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval 5-6-15 Acknowledged
Construction documents for fire alarm systems
Corrective Action Required
08/05/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans, also show alarm matrix to include duct detection. 5-6-15 Acknowledged
Posting of occupant load
Corrective Action Required
08/05/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Provide and post an occupancy sign for the building. To be located near the main entry 5-6-15 Resolved
Misc
Corrective Action Required
08/05/2015

Drive lanes around the building shall be marked as "Fire Lane- No Parking" 5-6-15 Resolved
Portable fire extinguishers - general
Corrective Action Required
08/05/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. provide 5lb ABC type extinguishers 5-6-15 Acknowledged
Licensed Contractors Approved 05/05/2015 07/16/2015
Mike Weisenborn
LC - General Contractor
Resolved
07/16/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
07/16/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Sprinkler Plan Review Released for Construction 07/09/2015
Joe Dir
Misc
Corrective Action Required
07/09/2015

Hydrostatic test required, call 816-969-1300 to schedule a test
Installation acceptance testing
Corrective Action Required
07/09/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Flow test required call 816-969-1300 to schedule a test
Building Plan Review Approved with Conditions 05/12/2015 05/13/2015
Joe Frogge
Health Dept Inspection
Corrective Action Required
05/05/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: This comment is for informational purposes.
Health Dept Review
Resolved
05/13/2015

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: This comment is for informational purposes. received 5/12/15
Bldg - Occupant load posting 1004.3
Corrective Action Required
05/05/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: This comment is for informational purposes. To be verified at inspections.
Misc
Resolved
05/08/2015

2012 IBC 1103.1 (Accessibility) Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Demonstrate how waiver station will be accessible. 5/8/15 - design altered
Miscellaneous Correction
Corrective Action Required
05/05/2015

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide access to roof hatch. Provide extendable handrail at hatch. (both deferred from shell project) 5/8/15 - access provided. Handrail extension to be verified during inspections.
Plumb - Minimum number of fixtures 403.1
Resolved
05/08/2015

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be co ber of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide additional water closet for women. 6 required. 5/8/15 - original square footage numbers were incorrect. corrected figures are low enough to not require additional fixtures
Health Department Review Approved 04/22/2015 05/13/2015
Joe Frogge
Fire Plan Review Approved with Conditions 05/12/2015 05/06/2015
Brian Austerman
Misc
Corrective Action Required
05/05/2015

Drive lanes around the building shall be marked as "Fire Lane- No Parking" 5-6-15 Resolved
Posting of occupant load
Corrective Action Required
05/05/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Provide and post an occupancy sign for the building. To be located near the main entry 5-6-15 Resolved
Construction documents for fire alarm systems
Corrective Action Required
05/05/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans, also show alarm matrix to include duct detection. 5-6-15 Acknowledged
Knox box required
Corrective Action Required
05/05/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. Knox box is to be located over the FDC and under the outside horn/strobe. 5-6-15 resolved
Construction documents - Fire protection systems
Corrective Action Required
05/05/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval 5-6-15 Acknowledged
Portable fire extinguishers - general
Corrective Action Required
05/05/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. provide 5lb ABC type extinguishers 5-6-15 Acknowledged
Building Plan Review Rejected 04/22/2015 04/17/2015
Joe Frogge
Final Development Plan
Resolved
05/05/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. Permit cannot be issued until FDP is approved. Also, occupancy cannot be granted until shell building permit is closed. received 5/5/15
Health Dept Inspection
Corrective Action Required
04/17/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: This comment is for informational purposes.
Health Dept Review
Corrective Action Required
04/17/2015

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: This comment is for informational purposes.
Bldg - Occupant load posting 1004.3
Corrective Action Required
04/17/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: This comment is for informational purposes. To be verified at inspections.
Misc
Corrective Action Required
04/17/2015

2012 IBC 1103.1 (Accessibility) Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Demonstrate how waiver station will be accessible.
Miscellaneous Correction
Corrective Action Required
04/17/2015

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide access to roof hatch. Provide extendable handrail at hatch. (both deferred from shell project)
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
04/17/2015

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide additional water closet for women. 6 required.
r
Licensed Contractors Rejected 04/22/2015 04/17/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
04/17/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
04/17/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 04/22/2015 04/15/2015
Brian Austerman
Misc
Corrective Action Required
04/15/2015

Drive lanes around the building shall be marked as "Fire Lane- No Parking"
Posting of occupant load
Corrective Action Required
04/15/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Provide and post an occupancy sign for the building. To be located near the main entry
Construction documents for fire alarm systems
Corrective Action Required
04/15/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans, also show alarm matrix to include duct detection.
Knox box required
Corrective Action Required
04/15/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. Knox box is to be located over the FDC and under the outside horn/strobe.
Construction documents - Fire protection systems
Corrective Action Required
04/15/2015

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Portable fire extinguishers - general
Corrective Action Required
04/15/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. provide 5lb ABC type extinguishers
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,648.50 $1,648.50 Paid 08/05/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Failed 8/26/2015 8/26/2015 at 12:00 AM 08/26/2015
Misc
Corrective Action Required
08/26/2015
***NO FURTHER INSPECTIONS UNTIL ALL ISSUES BELOW ARE RESOLVED. *** -UNDERSLAB PLUMBING AND ELECTRICAL WERE NOT INSPECTED -SOME PART OF EXTERIOR WALLS ARE ALREADY INSULATED -PROTECT PLUMBING PER CODE THROUGHOUT. TOP AND BOTTOM WALL PLATES SHALL BE PROTECTED WITH PLATES THAT PROVIDE MINIMUM 2" OF EXTRA PROTECTION BEYOND THE WALL PLATES. -ALL PVC SHALL BE GLUED TOGETHER WITH ICC-APPROVED PRIMER&GLUE. PROVIDE DOCUMENTATION -COMPLETE ALL IN-WALL ELECTRICAL -SUPPORT IN-WALL ELECTRICAL BOXES. USE PROPER SUPPORT BRACKETS TO ATTACH THE BOXES TO THE STUDS -SCREW STUDS TO HEADER -FASTEN STUDS TO GIRTS WITH 3-#10 SCREWS -BRIDGE STUDS PER PLAN -HAVE ENGINEER SPECIFY THE FASTENING SCHEDULE OF EXTERIOR WALL BOTTOM TRACK TO FLOOR
In-wall Inspection Partial 8/27/2015 8/27/2015 at 12:00 AM 08/27/2015
Misc
Corrective Action Required
08/27/2015
*OK TO COVER WEST AND NORTH EXTERIOR WALLS ONLY
In-wall Inspection Partial 8/27/2015 8/28/2015 at 12:00 AM 08/28/2015
Misc
Corrective Action Required
08/27/2015
*OK TO COVER EAST, WEST, AND NORTH EXTERIOR WALLS ONLY
Rough Framing Inspection - Commercial Partial 9/4/2015 9/4/2015 at 12:00 AM 09/04/2015
Misc
Corrective Action Required
09/04/2015
PARTIAL-MID-BUILDING PLATFORM OK TO ROCK AS PROGRESSED
In-wall Inspection Failed 9/9/2015 9/9/2015 at 12:00 AM 09/09/2015
Misc
Corrective Action Required
08/28/2015
EXTERIOR WALLS-OK INTERIOR WALLS: -PROTECT PLUMBING WITHIN 1.5" OF STUD SURFACE AT SINK , RM 106 . PROTECT PLUMBING AT BOTTOM WALL TRACK WITH GUARD PLATES THAT PROVIDE MINIMUM 2" OF EXTRA PROTECTION BEYOND THE WALL TRACK. -ALL PVC SHALL BE GLUED TOGETHER WITH ICC-APPROVED PRIMER. PROVIDE DOCUMENTATION FOR THE PRIMER. PROVIDE PRIMER&GLUE SAMPLE ON SITE -SUBMIT SIGNED LETTERS FROM BOTH ELECTRICIAN AND PLUMBER STATING UNDERSLAB WORKS ARE IN COMPLIANCE WITH THE APPROVED PLAN AND CODE. -2ND FL NOT COMPLETED.
Electrical Service Inspection Passed 9/16/2015 at 12:00 AM 09/16/2015
In-wall Inspection Partial 9/17/2015 9/17/2015 at 12:00 AM 09/17/2015
Misc
Corrective Action Required
09/09/2015
EXTERIOR WALLS-OK INTERIOR WALLS: -OK TO COVER 1ST FLOOR IN-WALL AND 2ND FL IN-WALL, EXCEPT THE IT CLOSET (NOT COMPLETED).
Rough Framing Inspection - Commercial Passed 10/14/2015
Misc
Resolved
10/14/2015
PARTIAL-MID-BUILDING PLATFORM OK TO ROCK AS PROGRESSED
In-wall Inspection Passed 10/14/2015 10/14/2015 at 12:00 AM 10/14/2015
Misc
Resolved
10/14/2015
EXTERIOR WALLS-OK INTERIOR WALLS: -OK TO COVER 1ST FLOOR IN-WALL AND 2ND FL IN-WALL, EXCEPT THE IT CLOSET (NOT COMPLETED).
Underground Electrical Inspection - Commercial Failed 10/14/2015 at 12:00 AM 10/14/2015
Misc
Corrective Action Required
10/14/2015
-LIGHT POLE PIERS AND GROUNDING WERE NOT INSPECTED
Gas Service Inspection - Commercial Passed 10/14/2015 10/14/2015 at 12:00 AM 10/14/2015
Gas Piping Inspection - Commercial Failed 10/14/2015 10/14/2015 at 12:00 AM 10/14/2015
Misc
Corrective Action Required
10/14/2015
-SUPPORT GAS LINE ON ROOF TOP PER CODE. MAXIMUM INTERVAL 0F 8 FT FOR 3/4" PIPE AND 10 FT FOR LARGER THAN 1" PIPE
Above Ceiling Inspection Failed 10/14/2015 at 12:00 AM 10/14/2015
Misc
Corrective Action Required
10/14/2015
-COMPLETE ALL MECHANICAL DUCTING TO CEILING -SUPPORT GRID EVERY 4 FT THROUGHOUT -SECURELY FASTEN ALL MC WIRING, OTHER THAN THE ONE DIRECTLY GOING TO THE CEILING LIGHTS, WITHIN 12" OF BOXES; SECURELY FASTEN ALL EMT WITHIN 3 FT OF JUNCTION BOXES -SUPPORT CEILING LIGHTS. TWO WIRE SUPPORT AT OPPOSITE CORNERS -COMPLETE FIRE SPRINKLER INSTALLATION
Occupancy Inspection - Codes Commercial Not Ready 10/15/2015 10/15/2015 at 12:00 AM 10/15/2015
Misc
Corrective Action Required
10/14/2015
**NOT READY FOR INSPECTION. OK TO STOCK BUILDING BUT NO OCCUPANCY
Alarm Test Passed 10/15/2015 at 12:00 AM 10/15/2015
Sprinkler - Flow Test Passed 10/15/2015 at 12:00 AM 10/15/2015
Sprinkler - Hydrostatic Test Passed 10/15/2015 at 11:00 AM 10/15/2015
Occupancy Inspection - Fire Temporary C of O 10/15/2015 10/15/2015 at 12:00 AM 10/15/2015
Occupancy Inspection - Codes Commercial Failed 10/19/2015 10/19/2015 at 12:00 AM 10/19/2015
Misc
Corrective Action Required
10/15/2015
-OBTAIN APPROVAL FROM: PLANNING & DEVELOPMENT; WATER DEPT; PUBLIC WORKS; HEALTH DEPT -UNDERGROUND ELECTRICAL NOT FULLY APPROVED. ALL THE LIGHT POLE PIERS WERE NEVER INSPECTED, AS WELL AS THE UNDERGROUND ELECTRICAL TO THE NORTH LIGHT POLE -SUBMIT 3RD PARTY SPECIAL INSPECTION APPROVAL -PATCH EXTERIOR WALL HOLE NEAR CT CABINET -RAISE THE WATER SERVICE METER TO GRADE LEVEL -PAINT EXTERIOR GAS LINE FOR PROTECTION -INSTALL SIDEWALK AT NW END OF BUILDING -COMPLETE TRASH ENCLOSURE -BEVEL FLOOR ELEVATION CHANGE AT RESTROOM DOOR -INSTALL SAFETY GLAZING AT PARTY RM WALL&DOOR -RESTROOMS ARE NOT COMPLETED. INSTALL GRAB BARS AND PARTITIONS AS REQUIRED -COMPLETE CLOSING OF OPEN SIDE OF PLATFORM AND FLOOR GAPS AND PLATFORM FLOORING -SECURE ALL EMT WITHIN 3 FT OF GUTTER BOX ABOVE SERVICE PANEL -LABEL ALL MDP BREAKERS -PROVIDE GUARDRAIL OR BARRIER AT STAIR WHERE THE VERTICAL CLEARANCE IS LESS THAN 80" ABOVE THE FLOOR. THE BARRIER OR GUARDRAIL SHALL BE MAXIMUM 27" IN HEIGHT -COMPLETE MECHANICAL ABOVE IT RM -SECURE ALL LFNC RACEWAY WITHIN 12" OF SIGN LED SUPPLY BOXES. LFNC LONGER THAN 6 FT SHALL BE SECURELY FASTEN EVERY 3 FT
Above Ceiling Inspection Passed 10/19/2015
Occupancy Inspection - Fire Passed 10/19/2015 at 12:00 AM 10/20/2015
Underground Electrical Inspection - Commercial Passed 10/21/2015
Occupancy Inspection - Codes Commercial Failed 10/21/2015 10/21/2015 at 12:00 AM 10/21/2015
Misc
Corrective Action Required
10/19/2015
-OBTAIN APPROVAL FROM: PLANNING & DEVELOPMENT; WATER DEPT; PUBLIC WORKS; HEALTH DEPT -SUBMIT 3RD PARTY SPECIAL INSPECTION APPROVAL -INSTALL SAFETY GLAZING AT PARTY RM WALL&DOOR -RESTROOMS ARE NOT COMPLETED. INSTALL GRAB BARS AND PARTITIONS AS REQUIRED **THE PRIVACY PARTITION AT THE URINAL MUST BEGIN AT THE HEIGHT NOT MORE THAN 12" ABOVE THE FLOOR AND EXTEND MINIMUM 60 INCHES ABOVE THE FLOOR. IBC 1210.3.2 -PROVIDE GUARDRAIL OR BARRIER AT STAIR WHERE THE VERTICAL CLEARANCE IS LESS THAN 80" ABOVE THE FLOOR. THE BARRIER OR GUARDRAIL SHALL BE MAXIMUM 27" IN HEIGHT
Occupancy Inspection - Codes Commercial Temporary C of O 10/22/2015 at 12:00 AM 10/22/2015
Misc
Corrective Action Required
10/21/2015
-OBTAIN APPROVAL FROM: PLANNING & DEVELOPMENT; WATER DEPT; PUBLIC WORKS -SUBMIT 3RD PARTY SPECIAL INSPECTION APPROVAL -INSTALL SAFETY GLAZING AT PARTY RM WALL&DOOR -RESTROOMS ARE NOT COMPLETED. INSTALL GRAB BARS AND PARTITIONS AS REQUIRED **THE PRIVACY PARTITION AT THE URINAL MUST BEGIN AT THE HEIGHT NOT MORE THAN 12" ABOVE THE FLOOR AND EXTEND MINIMUM 60 INCHES ABOVE THE FLOOR. IBC 1210.3.2 -PROVIDE GUARDRAIL OR BARRIER AT STAIR WHERE THE VERTICAL CLEARANCE IS LESS THAN 80" ABOVE THE FLOOR. THE BARRIER OR GUARDRAIL SHALL BE MAXIMUM 27" IN HEIGHT
Occupancy Inspection - Codes Commercial Failed 12/21/2015 12/21/2015 12/21/2015
Misc
Corrective Action Required
10/22/2015
-SUBMIT 3RD PARTY SPECIAL INSPECTION APPROVAL **3RD PARTY NOT FULLY APPROVED, STILL UNRESOLVED STEEL FRAMING ISSUES **ADDENUM: THE TERMINATIONS OF THE LIGHT POLE WIRINGS INSIDE THE HANDHOLES MUST BE INSIDE BOXES; THE TERMINATIONS SHALL BE RATED FOR WET LOCATION
Occupancy Inspection - Codes Commercial Full C of O 2/5/2016 02/05/2016
Misc
Resolved
02/05/2016
THE TERMINATIONS OF THE LIGHT POLE WIRINGS INSIDE THE HANDHOLES MUST BE INSIDE BOXES; THE TERMINATIONS SHALL BE RATED FOR WET LOCATION
Documents & Images
Date Uploaded File Type Document Name
04/15/2015 Letter Fire Building Plan Review
04/17/2015 Letter Codes P/R Corrections Document
05/06/2015 Letter Fire Building Plan Review
05/08/2015 Letter Codes P/R Corrections Document
07/09/2015 Letter Fire (Sprinkler) Plan Review
07/16/2015 Letter Codes Plan Review Conditions
08/05/2015 Letter Fire Building Plan Review
08/05/2015 Receipt Receipt for transaction: 2015-004592
08/05/2015 Letter Codes Building Permit
08/26/2015 Letter Inspection Summary
08/27/2015 Letter Inspection Summary
08/28/2015 Letter Inspection Summary
09/04/2015 Letter Inspection Summary
09/09/2015 Letter Inspection Summary
09/16/2015 Letter Inspection Summary
09/17/2015 Letter Inspection Summary
10/14/2015 Letter Inspection Summary
10/19/2015 Letter Inspection Summary
10/21/2015 Letter Inspection Summary
10/22/2015 Letter Codes Temporary Certificate of Occupancy
12/21/2015 Letter Inspection Summary
02/05/2016 Letter Field Certificate of Occupancy
02/08/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home