Permit Application Status

PRCOM20150658


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150658
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
NEW HANGAR WITH OFFICES FOUNDATION PERMIT - PRCOM20150850 Mike Weisenborn 11/23/2015 9:36 AM - CHANGED STATUS TO TCO PER KHANH NGUYEN
03/31/2015
06/22/2015
12/05/2015
04/08/2016
Locations
Contacts
THOMPSON BUILDERS LLC, Address:4559 GROVE ST, Phone:(913) 915-2836  
ELKINS A/C & HTG INC, Address:30808 E LITCHFORD RD, Phone:(816) 847-4700  
PREMIER ELECTRIC & LIGHTING DESIGN, Address:PO BOX 1311, Phone:(816) 564-7660  
R & R PLUMBING INC, Address:2001 GASLIGHT DR, Phone:(816) 772-5431  
CASTROP DESIGN GROUP, Address:4318 WEST 54TH ST, Phone:(913) 515-7664  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 06/15/2015 06/15/2015
Joe Frogge
Misc
Corrective Action Required
06/08/2015

No further FD comments
Miscellaneous Correction
Corrective Action Required
06/08/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The complex is addressed of the main airport address, however hangar identification will be required. Verified at inspection
Miscellaneous Correction
Corrective Action Required
06/08/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection
Building Plan Review Approved 06/15/2015 06/11/2015
Joe Frogge
Accessibility - Fixed sidewall grab bars 604.5.1
Resolved
06/11/2015

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide details that describe how all accessible portions of restroom will be located and mounted including, but not limited to, grab bars, mirror, dispensers, fixtures, etc. 4/21/15 - provide side wall vertical grab bar. 5/27/15 - no noticable alteration to restroom grab bars
Engineered truss package
Resolved
06/11/2015

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide I-joist package or request deferral in writing. 4/21/15 - neither provided 5/27/15 - neither provided 6/11/15 - provided
Licensed Contractors Approved 06/08/2015 06/08/2015
Development Center
Fire Plan Review Approved with Conditions 05/27/2015 05/29/2015
Mike Weisenborn
Misc
Corrective Action Required
05/26/2015

No further FD comments
Miscellaneous Correction
Corrective Action Required
05/26/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The complex is addressed of the main airport address, however hangar identification will be required. Verified at inspection
Miscellaneous Correction
Corrective Action Required
05/26/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection
Building Plan Review Rejected 04/22/2015 05/27/2015
Joe Frogge
Final Development Plan
Resolved
05/05/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Accessibility - Fixed sidewall grab bars 604.5.1
Corrective Action Required
04/15/2015

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide details that describe how all accessible portions of restroom will be located and mounted including, but not limited to, grab bars, mirror, dispensers, fixtures, etc. 4/21/15 - provide side wall vertical grab bar. 5/27/15 - no noticable alteration to restroom grab bars
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Resolved
04/21/2015

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Provide details that show that kitchenette counter will be accessible including, but not limited to, counter height, turning space, etc. 4/21/15 - updated drawings
Screening - Ground mounted equipment
Resolved
05/27/2015

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Screen ground mounted mechanical equipment to the satisfaction of our Planning Department. 4/21/15 - screening materials must be per ordinance. 5/27/15 - to be landscaped per drawing
Plumb - Freezing 305.4
Resolved
04/21/2015

2012 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision ins made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Provide information as to how water service entry piping will be protected from freezing. If located in hangar area, is it the intent that entire hangar is heated continually through winter? 4/21/15 - note provided stating that hangar will be heated year round.
Misc
Resolved
05/27/2015

Wall construction information. Action required: Provide section detail through office area. How are walls constructed? Which are load bearing? Locate and specify grade beam or equivalent at load bearing wall(s). For the purpose of this comment, the upper platform and subsequent joists must bear on load bearing walls or equivalent. Also detail how floor joists attach to exterior wall. 4/21/15 - provide footing or grade beam beneath load bearing walls or provide letter from structural engineer stating that slab as specified is designed for this load. 5/27/15 - letter from engineer provided. no footing required.
Engineered truss package
Corrective Action Required
04/15/2015

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide I-joist package or request deferral in writing. 4/21/15 - neither provided 5/27/15 - neither provided
Plumb - Minimum number of fixtures 403.1
Resolved
04/21/2015

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide mop/utility sink. 4/21/15 - shown on updated drawing
NEC - Receptacles - Other than dwelling units 210.8(B)
Resolved
04/21/2015

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in hangar (garage/service bay) will by GFCI protected. (or clarify - it is not clear that the 4-plexes will be protected) 4/21/15 - drawing updated
Misc
Resolved
05/27/2015

Additional information required to complete review. Provide the following: - Electrical scope of work that include wire insulation type, sizing, conduit type and sizing, etc. - Electrical service wiring diagram. (power and grounding) - Completion of electrical design. (power to hangar heaters, furnace, etc.) - Plumbing scope of work that includes methods and materials. - Propane system design that includes piping and venting. 4/21/15: - update electrical riser diagram to show all sources of ground including building steel and water piping (unless service is also pex as indicated for interior piping) - specify wiring to unit heaters (fan motor is not propane powered) 5/27/15: - multiple drawings updated.
Licensed Contractors Approved 05/26/2015 05/27/2015
Joe Frogge
Final Development Plan Review Approved 05/05/2015 05/05/2015
Joe Frogge
Fire Plan Review Approved with Conditions 04/22/2015 04/21/2015
Joe Frogge
Misc
Corrective Action Required
04/17/2015

No further FD comments
Miscellaneous Correction
Corrective Action Required
04/21/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The complex is addressed of the main airport address, however hangar identification will be required. Verified at inspection
Miscellaneous Correction
Corrective Action Required
04/21/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection
Licensed Contractors Approved 04/22/2015 04/21/2015
Joe Frogge
LC - MEP Subs
Resolved
04/21/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Mechanical Contractor.
Building Plan Review Rejected 04/14/2015 04/07/2015
Joe Frogge
Final Development Plan
Corrective Action Required
04/07/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Accessibility - Fixed sidewall grab bars 604.5.1
Corrective Action Required
04/07/2015

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide details that describe how all accessible portions of restroom will be located and mounted including, but not limited to, grab bars, mirror, dispensers, fixtures, etc.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Corrective Action Required
04/07/2015

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Provide details that show that kitchenette counter will be accessible including, but not limited to, counter height, turning space, etc.
Screening - Ground mounted equipment
Corrective Action Required
04/07/2015

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Screen ground mounted mechanical equipment to the satisfaction of our Planning Department.
Plumb - Freezing 305.4
Corrective Action Required
04/07/2015

2012 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision ins made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Provide information as to how water service entry piping will be protected from freezing. If located in hangar area, is it the intent that entire hangar is heated continually through winter?
Misc
Corrective Action Required
04/07/2015

Wall construction information. Action required: Provide section detail through office area. How are walls constructed? Which are load bearing? Locate and specify grade beam or equivalent at load bearing wall(s). For the purpose of this comment, the upper platform and subsequent joists must bear on load bearing walls or equivalent. Also detail how floor joists attach to exterior wall.
Engineered truss package
Corrective Action Required
04/07/2015

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide I-joist package or request deferral in writing.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
04/07/2015

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide mop/utility sink.
NEC - Receptacles - Other than dwelling units 210.8(B)
Corrective Action Required
04/07/2015

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in hangar (garage/service bay) will by GFCI protected. (or clarify - it is not clear that the 4-plexes will be protected)
Misc
Corrective Action Required
04/07/2015

Additional information required to complete review. Provide the following: - Electrical scope of work that include wire insulation type, sizing, conduit type and sizing, etc. - Electrical service wiring diagram. (power and grounding) - Completion of electrical design. (power to hangar heaters, furnace, etc.) - Plumbing scope of work that includes methods and materials. - Propane system design that includes piping and venting.
Licensed Contractors Rejected 04/14/2015 04/07/2015
Joe Frogge
LC - MEP Subs
Corrective Action Required
04/07/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Mechanical Contractor.
Fire Plan Review Approved 04/14/2015 04/06/2015
Brian Austerman
Address numbers required
Corrective Action Required
04/06/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The complex is addressed of the main airport address, however hangar identification will be required. Verified at inspection
Portable fire extinguishers - general
Corrective Action Required
04/06/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $1,083.00 $1,083.00 Paid 06/22/2015
8331401-Water Tap Fee $3,198.00 $3,198.00 Paid 06/22/2015
8350015-Water Meter Fee $354.05 $354.05 Paid 06/22/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection Passed 7/14/2015 (11:15) 7/14/2015 at 12:00 AM 07/14/2015
Electrical Service Inspection Passed 9/9/2015 at 12:00 AM 09/09/2015
All Rough Inspection - Commercial Partial 9/9/2015 9/9/2015 at 12:00 AM 09/09/2015
Misc
Corrective Action Required
09/09/2015
BLOCK TJI ENDS AT EXTERIOR SIDE
Occupancy Inspection - Fire Passed 10/16/2015 at 12:00 AM 10/16/2015
Gas Piping Inspection - Commercial Passed 10/16/2015 at 12:00 AM 10/16/2015
All Rough Inspection - Commercial Passed 10/16/2015
Misc
Resolved
10/16/2015
BLOCK TJI ENDS AT EXTERIOR SIDE
Occupancy Inspection - Codes Commercial Temporary C of O 10/16/2015 10/16/2015 at 12:00 AM 10/16/2015
Misc
Corrective Action Required
10/16/2015
-WATER DEPT APPROVAL REQUIRED -INSTALL SEWER CLEANOUT PLUG -VENT PLUMBING TO OUTDOOR -SECURE RACEWAY AT FRONT EXTERIOR DOOR PER CODE -BOND BUILDING STEEL TO THE SERVICE GROUNDING BUS BAR OR ENCLOSURE WITH #4 COPPER -GFCI AT WET BAR NOT TRIPPING -STAIR GUARDRAIL (MIN 42") AND HANDRAIL ON BOTH SIDES
Occupancy Inspection - Planning Passed 11/17/2015
Occupancy Inspection - Codes Commercial Failed 11/19/2015 11/19/2015 at 12:00 AM 11/19/2015
Misc
Corrective Action Required
10/16/2015
-WATER DEPT APPROVAL REQUIRED **INSTALL BACKFLOW DEVICE FOR WATER SERVICE -STAIR GUARDRAIL (MIN 42") REQUIRED
Occupancy Inspection - Codes Commercial Temporary C of O 12/3/2015 12/3/2015 at 12:00 AM 12/03/2015
Misc
Corrective Action Required
11/19/2015
**SOD/SEED DISTURBED AREA BEHIND HANGER
Occupancy Inspection - Codes Commercial Full C of O 04/08/2016
Misc
Resolved
04/08/2016
**SOD/SEED DISTURBED AREA BEHIND HANGER
Documents & Images
Date Uploaded File Type Document Name
04/06/2015 Letter Fire Building Plan Review
04/09/2015 Letter Codes P/R Corrections Document
04/17/2015 Letter Fire Building Plan Review
04/21/2015 Letter Codes P/R Corrections Document
05/27/2015 Letter Codes P/R Corrections Document
05/27/2015 Letter Fire Building Plan Review
06/15/2015 Letter Codes Plan Review Conditions
06/15/2015 Letter Fire Building Plan Review
06/22/2015 Letter Codes Building Permit
06/22/2015 Receipt Receipt for transaction: 2015-003193
07/14/2015 Letter Inspection Summary
09/09/2015 Letter Inspection Summary
10/16/2015 Letter Inspection Summary
10/20/2015 CMR - stair risers
11/19/2015 Letter Inspection Summary
04/08/2016 Letter Field Certificate of Occupancy
04/11/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home