Permit Application Status

PRCOM20122702


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20122702
Building Permit - Commercial
Certificate of Occupancy
STANLEY EVENT SPACE LLC, THE
NEW COMMERCIAL
STANLEY EVENT CENTER COMMERCIAL BUILDING fdtn - PRCOM20122279
12/11/2012
03/13/2013
10/15/2014
09/19/2013
Locations
Contacts
STANLEY EVENT SPACE LLC, THE, Address:308 SE DOUGLAS ST  
TXR ARCHITECTS & CONSTRUCTORS, Address:685 GRAND VIEW DR  
MD REPAIR, Address:7901 S PARRENT RD, Phone:(816) 690-7985  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
KANSAS CITY PLUMBING COMPANY LLC, Address:107 W 63RD ST, STE 285, Phone:(816) 591-4433  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 04/15/2013
Brian Austerman
Misc
Corrective Action Required
04/15/2013

Duct detection not shown on plans, to be added per our discussion on 4/15/2013
Misc
Corrective Action Required
04/15/2013

Add manual pull station to 3rd floor stairwell, per our discussion
Building Plan Review Rejected 12/25/2012 04/03/2013
Mike Weisenborn
Misc
Corrective Action Required
04/03/2013

Details for construction of the stairs, handrails and guards have not been provided. Action required - Provide additional information. Mike Weisenborn 03/05/2013 2:38 PM - Per the re-submittal letter this information will be provided as a deferred submittal. Mike Weisenborn 04/03/2013 9:28 AM - Shop drawing for the main stairs have been provided. See additional comments on maximum rise. Details for guards, handrails and the exterior and south stair have not been submitted yet. PRovide additional information.
Bldg - Shaft enclosures - Elevators general
Partial Correction
04/03/2013

2006 IBC 707.14 - Elevator, dumbwaiter and other hoistways. Elevator, dumbwaiter and other hoistway enclosures shall be constructed in accordance with Section 707 and Chapter 30. Action required - Show how this requirement will be met. Mike Weisenborn 03/05/2013 3:03 PM - Corrections have been made. Make sure that the walls run tight to the floor/ceiling above.
Misc
Partial Correction
04/03/2013

Details for the installation of the mechanical system and equipment is not provided on the plans. Action required - Provide details. Mike Weisenborn 03/05/2013 4:49 PM - Requested as deferred submittal.
Bldg - Stairways - Treads and risers
Corrective Action Required
04/03/2013

2006 IBC 1009.3 - Stair treads and risers. Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the treads leading edge. Winder treads shall have a minimum tread depth of 11 inches measured at a right angle to the treads leading edge at a point 12 inches from the side where the treads are narrower and a minimum tread depth of 10 inches. Mike Weisenborn 04/03/2013 9:28 AM - Action required - The maximum rise of 7 inches is not met on all the stair sections. Make needed corrections. Make needed corrections
Building Plan Review Approved with Conditions 03/18/2013 04/03/2013
Mike Weisenborn
Misc
Corrective Action Required
03/11/2013

Details for construction of the stairs, handrails and guards have not been provided. Action required - Provide additional information. Mike Weisenborn 03/05/2013 2:38 PM - Per the re-submittal letter this information will be provided as a deferred submittal.
Bldg - Exterior exit ramps and stairways - Protection
Resolved
03/12/2013

2006 IBC 1023.6 - Exterior ramps and stairway protection. Exterior exit ramps and stairways shall be separated from the interior of the building as required in Section 1020.1. Openings shall be limited to those necessary for egress from normally occupied spaces. Action required - Make needed corrections. Mike Weisenborn 03/05/2013 2:43 PM - Per Table 715.4 door 120 is required to be rated for 1-hour. Make needed corrections. Mike Weisenborn 03/12/2013 10:30 AM - The door has been removed.
Bldg - Toilet rooms - Walls
Resolved
03/12/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - The finish schedule indicates that the toilet room walls are to be painted. If so, an epoxy paint must be used. Provide additional information on the plans. Mike Weisenborn 03/05/2013 2:48 PM - Corrections have been made.
Bldg - Glazing - Human impact loads
Resolved
03/12/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Item 7 of this section requires windows over nine square feet in area, within 18 inches of the floor and within 3 feet of a walking surface to meet these requirements. Indicate if any of the windows meet this requirement. Mike Weisenborn 03/05/2013 2:50 PM - Note 3 in the Window notes on Sheet A1.2 only references glazing in windows adjacent to doors. The lower pains in window types D, E, F and G is also required to be protected as it is within 18 inches of the floor and greater than 9 square feet in area. Make needed corrections. Mike Weisenborn 03/12/2013 10:31 AM - Corrections have been made.
Bldg - Elevators - Machine room construction
Resolved
03/12/2013

2006 IBC 3006.4 - Machine rooms and machinery spaces. Elevator machine rooms and machinery spaces shall be enclosed with fire barriers with a fire-resistance rating not less than the required rating of the hoistway enclosure served by the machinery. Openings shall be protected with assemblies having a fire-protection rating not less than that required for the hoistway enclosure doors. Mike Weisenborn 03/12/2013 10:32 AM - Corrections have been made. Action required - I am unable to locate the machine room. Show how this requirement will be met. Mike Weisenborn 03/05/2013 3:01 PM - Two of the walls shown for the equipment room are type W5 which is not shown to be rated. Make needed corrections. Mike Weisenborn 03/12/2013 10:32 AM
Bldg - Shaft enclosures - Elevators general
Partial Correction
03/11/2013

2006 IBC 707.14 - Elevator, dumbwaiter and other hoistways. Elevator, dumbwaiter and other hoistway enclosures shall be constructed in accordance with Section 707 and Chapter 30. Action required - Show how this requirement will be met. Mike Weisenborn 03/05/2013 3:03 PM - Corrections have been made. Make sure that the walls run tight to the floor/ceiling above.
Bldg - Doors - Panic and fire exit hardware
Resolved
03/12/2013

2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equipped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side. Action required - Doors 206, 200, 300 and the egress gate on the roof are required to meet this requirement. Make needed corrections and provide details on the gate hardware. Mike Weisenborn 03/05/2013 3:18 PM - Please contact me to discuss door 300. Mike Weisenborn 03/12/2013 10:33 AM - Corrections have been made.
Misc
Partial Correction
03/12/2013

Details for the installation of the mechanical system and equipment is not provided on the plans. Action required - Provide details. Mike Weisenborn 03/05/2013 4:49 PM - Requested as deferred submittal.
Bldg - Doors - Size of doors
Resolved
03/12/2013

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The only exception for commercial buildings is closets less than 10 square feet in area. Make needed corrections. Mike Weisenborn 03/05/2013 4:48 PM - Item has not been addressed. Mike Weisenborn 03/12/2013 10:34 AM - Corrections have been made.
Screening - Rooftop equipment
Resolved
03/12/2013

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - Two of the condinsing units are not screened. Make needed corrections. Mike Weisenborn 03/05/2013 4:48 PM - Please contact me to discuss. Mike Weisenborn 03/12/2013 10:35 AM - Corrections have been made.
Fire Plan Review Approved 03/18/2013 03/26/2013
Brian Austerman
Misc
Corrective Action Required
03/26/2013

Plan review for stairways and landings approved without fire department comment
Sprinkler Plan Review Released for Construction 03/26/2013
Brian Austerman
Installation acceptance testing
Corrective Action Required
03/26/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call 969-1300 to schedule hydrostatic test
Misc
Corrective Action Required
03/26/2013

Call 969-1300 to schedule flow test in conjunction with the alarm test prior to final
Fire Plan Review Approved with Conditions 03/18/2013 03/12/2013
Brian Austerman
Knox box required
Corrective Action Required
03/11/2013

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Plan set shows 2 knox boxes, only 1 is required, locate above FDC and near the outside waterflow H/S. Call 816.969.1300 to obtain a knox box application
Misc
Corrective Action Required
03/11/2013

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Provide duct detection on rtu's over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the alarm panel
Misc
Corrective Action Required
03/11/2013

The door to the sprinkler room need to be labeled as "SPRINKLER ROOM" Verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
03/11/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
03/11/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Misc
Corrective Action Required
03/11/2013

Revised plans and comments received and approved as listed. No further fire department comments
Building Plan Review Rejected 03/04/2013 03/05/2013
Mike Weisenborn
Misc
Resolved
02/25/2013

2006 IBC 602.2 - Types I and II. Type I and II construction are htose types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required - The Code Analysis provided indicates a construction type of II-B (Wood Frame, Unprotected). Make needed corrections. Mike Weisenborn 02/25/2013 11:10 AM - Corrections have been made.
Misc
Resolved
03/05/2013

The Code Anlysis does not indicate requirements for fire-rated assemblies. Action rquired - Make needed corrections. Mike Weisenborn 03/05/2013 2:25 PM - Additional information provided.
Misc
Resolved
03/05/2013

The Code Anlysis indicates that there is a required occupancy separateion between between the A2 and B occupancies per Table 508.3.3. Section 508.3.2 of the 2006 IBC allows for nonseparated occupancies if the area and number of stories of the building is within the most restrictive occupancy. As the entire building could be built as an A2 occupancy, which is the most restrictive, separation between occupancy types is not required. Action required - This comment is for information purposes and changes are not required. However, the separations can be removed. Mike Weisenborn 03/05/2013 2:26 PM - The separation has been removed.
Misc
Resolved
03/05/2013

The roof plan on Sheet A1.1 shows roof and overflow drains but information on the systems are not provided on the plumbing plans. Action required - Provide additional information. Mike Weisenborn 03/05/2013 2:27 PM - Additional information has been added.
Misc
Resolved
03/05/2013

The Code Anlysis provides the square footage of the entire building but not a breakdown by floor. Action required - Provide additional information. Mike Weisenborn 02/25/2013 11:10 AM - Additional information has been provided. Mike Weisenborn 03/05/2013 2:28 PM - Information has been added.
Bldg - Types of construction - General
Resolved
03/05/2013

2006 IBC 602.1 - General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602. Action required - Table 602 requires the north and south walls to one-hour fire -resistant as they are less than 5 feet from the property lines. Make needed corrections. The rating shall continue to the top of the parapet. Mike Weisenborn 03/05/2013 2:29 PM - Corrections have been made.
Misc
Resolved
03/05/2013

Per earlier conversations with Tracy Deister, the exterior walls of the 3rd floor are to be one-hour fire-resistant to meet the requirements for separation of exits. Action required - Make needed corrections. Mike Weisenborn 03/05/2013 2:37 PM - Corrections have been made.
Misc
Corrective Action Required
02/19/2013

Details for construction of the stairs, handrails and guards have not been provided. Action required - Provide additional information. Mike Weisenborn 03/05/2013 2:38 PM - Per the re-submittal letter this information will be provided as a deferred submittal.
Bldg - Exterior exit ramps and stairways - Protection
Corrective Action Required
02/19/2013

2006 IBC 1023.6 - Exterior ramps and stairway protection. Exterior exit ramps and stairways shall be separated from the interior of the building as required in Section 1020.1. Openings shall be limited to those necessary for egress from normally occupied spaces. Action required - Make needed corrections. Mike Weisenborn 03/05/2013 2:43 PM - Per Table 715.4 door 120 is required to be rated for 1-hour. Make needed corrections.
Bldg - Vertical exit enclosures - When required
Resolved
03/05/2013

2006 IBC 1020.1 - Enclosures required. Interior exit stairways and interior exit ramps shall be enclosed with fire barriers constructed in accordance with Section 706 or horizontal assemblies constructed in accordance with Section 711, or both. Exit enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories. The number of stories connected by the exit enclosure shall include any basements but not any mezzanines. An exit enclosure shall not be used for any purpose other than means of egress. (See code book for possible exceptions.) Action required - Make needed corrections. Mike Weisenborn 03/05/2013 2:46 PM - Corrections have been made.
Bldg - Toilet rooms - Walls
Corrective Action Required
02/19/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - The finish schedule indicates that the toilet room walls are to be painted. If so, an epoxy paint must be used. Provide additional information on the plans. Mike Weisenborn 03/05/2013 2:48 PM - Corrections have been made.
Bldg - Glazing - Human impact loads
Corrective Action Required
02/19/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Item 7 of this section requires windows over nine square feet in area, within 18 inches of the floor and within 3 feet of a walking surface to meet these requirements. Indicate if any of the windows meet this requirement. Mike Weisenborn 03/05/2013 2:50 PM - Note 3 in the Window notes on Sheet A1.2 only references glazing in windows adjacent to doors. The lower pains in window types D, E, F and G is also required to be protected as it is within 18 inches of the floor and greater than 9 square feet in area. Make needed corrections.
Bldg - Elevators - Machine room construction
Resolved
03/05/2013

2006 IBC - 3002.7 - Common enclosure with stairway. Elevators shall not be in a common shaft enclosure with a stairway. Action required - Make needed corrections. Mike Weisenborn 03/05/2013 2:53 PM - There is no rated stairway enclosure so there is no violation.
Bldg - Elevators - Machine room construction
Corrective Action Required
02/19/2013

2006 IBC 3006.4 - Machine rooms and machinery spaces. Elevator machine rooms and machinery spaces shall be enclosed with fire barriers with a fire-resistance rating not less than the required rating of the hoistway enclosure served by the machinery. Openings shall be protected with assemblies having a fire-protection rating not less than that required for the hoistway enclosure doors. Action required - I am unable to locate the machine room. Show how this requirement will be met. Mike Weisenborn 03/05/2013 3:01 PM - Two of the walls shown for the equipment room are type W5 which is not shown to be rated. Make needed corrections.
Bldg - Shaft enclosures - Elevators general
Partial Correction
03/05/2013

2006 IBC 707.14 - Elevator, dumbwaiter and other hoistways. Elevator, dumbwaiter and other hoistway enclosures shall be constructed in accordance with Section 707 and Chapter 30. Action required - Show how this requirement will be met. Mike Weisenborn 03/05/2013 3:03 PM - Corrections have been made. Make sure that the walls run tight to the floor/ceiling above.
Misc
Resolved
03/05/2013

The plans do not provide information for the removal of water in the elevator pit. Action required - Provide additional information. Mike Weisenborn 03/05/2013 3:06 PM - Information has been provided.
Plumb - Minimum number of fixtures
Resolved
03/05/2013

2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required - Provide calculations for the required number of fixtures.
Bldg - Doors - Panic and fire exit hardware
Corrective Action Required
02/19/2013

2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equipped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side. Action required - Doors 206, 200, 300 and the egress gate on the roof are required to meet this requirement. Make needed corrections and provide details on the gate hardware. Mike Weisenborn 03/05/2013 3:18 PM - Please contact me to discuss door 300.
Misc
Resolved
03/05/2013

The plans do not indicate how access to the bottom of the elevator shaft is provided. Action required - Provide additional information. Mike Weisenborn 03/05/2013 3:18 PM - Information has been provided.
Misc
Resolved
03/05/2013

Details for the grease interceptor indicated on the plans have not been provided. Action required - Provide additional information. Mike Weisenborn 03/05/2013 3:19 PM - Information has been provided.
Plumb - Backflow general 608.3
Resolved
03/05/2013

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Show how this requirement will be met for the ice machine. Mike Weisenborn 03/05/2013 3:19 PM - Information has been added.
Plumb - Indirect Waste General
Resolved
03/05/2013

2006 IPC Section 801.2 - Protection. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that discharge to the drainage system, shall be provided with protection against backflow, flooding fouling, contamination and stoppage of the drain. Action required - Provide information on the ice machine and any food preparation sinks. Mike Weisenborn 03/05/2013 3:20 PM - Information has been added.
Misc
Resolved
03/05/2013

Water piping is not shown on the plans. Action required - Provide the water piping layout.
WU - Double check on fire service line
Resolved
03/05/2013

Water Utilities - A double check detector check valve assembly is required on the fire service line. Action required - Provide details for the installation of the backflow.
WU - RPZ on domestic service
Resolved
03/05/2013

Water Utilities - A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use. Action required - Provide details for the installation of the backflow.
Mech - Outdoor air required
Resolved
03/05/2013

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - Provide calculations. Mike Weisenborn 03/05/2013 3:21 PM - Information has been added.
Misc
Corrective Action Required
02/19/2013

Details for the installation of the mechanical system and equipment is not provided on the plans. Action required - Provide details. Mike Weisenborn 03/05/2013 4:49 PM - Requested as deferred submittal.
Misc
Resolved
03/05/2013

Specifications for the mechanical system have not been provided. Action required - Provide specifications. Mike Weisenborn 03/05/2013 3:22 PM - Information has been added.
Misc
Resolved
03/05/2013

Specifications for the electrical system have not been provided. Action required - Provide specifications.
Accessibility - Water closet - Clearance around
Resolved
03/05/2013

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - Toilet room 302 does not meet this requirement. Make needed corrections. Mike Weisenborn 03/05/2013 3:23 PM - Corrections have been made.
Project cost
Resolved
03/05/2013

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the cost for the building minus the foundation and underslab.
Misc
Resolved
03/05/2013

2006 IPC - 904.1 - Roof extension. All open vent pipes that extend through a roof shall be terminated at least 6 inches above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least 7 feet above the roof. Action required - This needs to be noted on the plan. Mike Weisenborn 03/05/2013 3:24 PM - Corrections have been made.
Bldg - Means of egress illumination - Emergency power
Resolved
03/05/2013

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - Provide emergency lighting at all required locations. Mike Weisenborn 03/05/2013 4:01 PM - Corrections have been made.
Misc
Resolved
03/05/2013

Circuiting is not shown for the emergency lights and exit signs. Action required - Make needed corrections.
Misc
Resolved
03/05/2013

An electrical fixture schedule is not provided. Action required - Provide addtional information.
Bldg - Doors - Size of doors
Corrective Action Required
02/19/2013

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The only exception for commercial buildings is closets less than 10 square feet in area. Make needed corrections. Mike Weisenborn 03/05/2013 4:48 PM - Item has not been addressed.
Screening - Rooftop equipment
Corrective Action Required
02/19/2013

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - Two of the condinsing units are not screened. Make needed corrections. Mike Weisenborn 03/05/2013 4:48 PM - Please contact me to discuss.
Bldg - Guards - Mechanical equipment IBC
Resolved
03/05/2013

2006 IBC 1013.5 - Mechanical equipment. Guards shall be provided where appliances, equipment, fans, roof hatch openings or other components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall be constructed so as to prevent the passage of a 21-inch-diameter sphere. The guard shall extend not less than 30 inches beyond each end of such appliance, equipment fan or component. Action required - Provide a guard for the condensing units or relocate them.
License Tax Codes Approved 02/26/2013 02/25/2013
Mike Weisenborn
Fire Plan Review Approved with Conditions 02/26/2013 02/20/2013
Brian Austerman
Misc
Corrective Action Required
02/19/2013

Provide civil plans including fire main valve at the street and property lines.
Knox box required
Corrective Action Required
02/19/2013

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Plan set shows 2 knox boxes, only 1 is required, locate above FDC and near the outside waterflow H/S.
Type I hood - Where required
Corrective Action Required
02/19/2013

2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Required if grease vapors will be produced, if this is to be a warming kitchen provide a statement that no cooking will be done.
Misc
Corrective Action Required
02/19/2013

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Provide duct detection on rtu's over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the alarm panel
Misc
Corrective Action Required
02/19/2013

The door to the sprinkler room may be required to be a rated door depending on distance to the property line, provide civil plans
Misc
Corrective Action Required
02/19/2013

Provide rating on walls required to be rated as a fire wall
Misc
Corrective Action Required
02/19/2013

FDC on plan shows it located in the middle of the fire main coming into the building. This is to be a separate line to the riser.
Misc
Corrective Action Required
02/19/2013

The fire protection main coming into the building is a 4" line but the plan shows it feeding a 6" riser. The riser must be 4" or less and water availability needs to be calculated at 4" not 6".
Construction documents - Fire protection systems
Corrective Action Required
02/19/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
02/19/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Misc
Corrective Action Required
02/20/2013

Revised plans and comments received and approved as listed. No further fire department comments
Internal Plan Review (Com) Rejected 01/04/2013 01/04/2013
Mike Weisenborn
Final Development Plan Review Approved 12/27/2012 01/04/2013
Mike Weisenborn
Building Plan Review Rejected 01/04/2013 01/04/2013
Mike Weisenborn
Misc
Corrective Action Required
01/04/2013

2006 IBC 602.2 - Types I and II. Type I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required - The Code Analysis provided indicates a construction type of II-B (Wood Frame, Unprotected). Make needed corrections.
Misc
Corrective Action Required
01/04/2013

The Code Anlysis does not indicate requirements for fire-rated assemblies. Action rquired - Make needed corrections.
Misc
Corrective Action Required
01/04/2013

The Code Anlysis indicates that there is a required occupancy separateion between between the A2 and B occupancies per Table 508.3.3. Section 508.3.2 of the 2006 IBC allows for nonseparated occupancies if the area and number of stories of the building is within the most restrictive occupancy. As the entire building could be built as an A2 occupancy, which is the most restrictive, separation between occupancy types is not required. Action required - This comment is for information purposes and changes are not required. However, the separations can be removed.
Misc
Corrective Action Required
01/04/2013

The roof plan on Sheet A1.1 shows roof and overflow drains but information on the systems are not provided on the plumbing plans. Action required - Provide additional information.
Misc
Corrective Action Required
01/04/2013

The Code Anlysis provides the square footage of the entire building but not a breakdown by floor. Action required - Provide additional information.
Bldg - Types of construction - General
Corrective Action Required
01/04/2013

2006 IBC 602.1 - General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602. Action required - Table 602 requires the north and south walls to one-hour fire -resistant as they are less than 5 feet from the property lines. Make needed corrections. The rating shall continue to the top of the parapet.
Misc
Corrective Action Required
01/04/2013

Per earlier conversations with Tracy Deister, the exterior walls of the 3rd floor are to be one-hour fire-resistant to meet the requirements for separation of exits. Action required - Make needed corrections.
Misc
Corrective Action Required
01/04/2013

Details for construction of the stairs, handrails and guards have not been provided. Action required - Provide additional information.
Bldg - Exterior exit ramps and stairways - Protection
Corrective Action Required
01/04/2013

2006 IBC 1023.6 - Exterior ramps and stairway protection. Exterior exit ramps and stairways shall be separated from the interior of the building as required in Section 1020.1. Openings shall be limited to those necessary for egress from normally occupied spaces. Action required - Make needed corrections.
Bldg - Vertical exit enclosures - When required
Corrective Action Required
01/04/2013

2006 IBC 1020.1 - Enclosures required. Interior exit stairways and interior exit ramps shall be enclosed with fire barriers constructed in accordance with Section 706 or horizontal assemblies constructed in accordance with Section 711, or both. Exit enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories. The number of stories connected by the exit enclosure shall include any basements but not any mezzanines. An exit enclosure shall not be used for any purpose other than means of egress. (See code book for possible exceptions.) Action required - Make needed corrections.
Bldg - Toilet rooms - Walls
Corrective Action Required
01/04/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - The finish schedule indicates that the toilet room walls are to be painted. If so, an epoxy paint must be used. Provide additional information on the plans.
Bldg - Glazing - Human impact loads
Corrective Action Required
01/04/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Item 7 of this section requires windows over nine square feet in area, within 18 inches of the floor and within 3 feet of a walking surface to meet these requirements. Indicate if any of the windows meet this requirement.
Bldg - Elevators - Machine room construction
Corrective Action Required
01/04/2013

2006 IBC - 3002.7 - Common enclusure with stairway. Elevators shall not be in a common shaft enclosure with a stairway. Action required - Make needed corrections.
Bldg - Elevators - Machine room construction
Corrective Action Required
01/04/2013

2006 IBC 3006.4 - Machine rooms and machinery spaces. Elevator machine rooms and machinery spaces shall be enclosed with fire barriers with a fire-resistance rating not less than the required rating of the hoistway enclosure served by the machinery. Openings shall be protected with assemblies having a fire-protection rating not less than that required for the hoistway enclosure doors. Action required - I am unable to locate the machine room. Show how this requirement will be met.
Bldg - Shaft enclosures - Elevators general
Corrective Action Required
01/04/2013

2006 IBC 707.14 - Elevator, dumbwaiter and other hoistways. Elevator, dumbwaiter and other hoistway enclosures shall be constructed in accordance with Section 707 and Chapter 30. Action required - Show how this requirement will be met.
Misc
Corrective Action Required
01/04/2013

The plans do not provide information for the removal of water in the elevator pit. Action required - Provide additional information.
Plumb - Minimum number of fixtures
Corrective Action Required
01/04/2013

2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required - Provide calculations for the required number of fixtures.
Bldg - Doors - Panic and fire exit hardware
Corrective Action Required
01/04/2013

2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equipped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side. Action required - Doors 206, 200, 300 and the egress tate on the roof are required to meet this requirement. Make needed corrections and provide details on the gate hardware.
Misc
Corrective Action Required
01/04/2013

The plans do not indicate how access to the bottom of the elevator shaft is provided. Action required - Provide additional information.
Misc
Corrective Action Required
01/04/2013

Details for the grease interceptor indicated on the plans have not been provided. Action required - Provide additional information.
Plumb - Backflow general 608.3
Corrective Action Required
01/04/2013

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Show how this requirement will be met for the ice machine.
Plumb - Indirect Waste General
Corrective Action Required
01/04/2013

2006 IPC Section 801.2 - Protection. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that discharge to the drainage system, shall be provided with protection against backflow, flooding fouling, contamination and stoppage of the drain. Action required - Provide information on the ice machine and any food preparation sinks.
Misc
Corrective Action Required
01/04/2013

Water piping is not shown on the plans. Action required - Provide the water piping layout.
WU - Double check on fire service line
Corrective Action Required
01/04/2013

Water Utilities - A double check detector check valve assembly is required on the fire service line. Action required - Provide details for the installation of the backflow.
WU - RPZ on domestic service
Corrective Action Required
01/04/2013

Water Utilities - A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use. Action required - Provide details for the installation of the backflow.
Mech - Outdoor air required
Corrective Action Required
01/04/2013

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - Provide calculations.
Misc
Corrective Action Required
01/04/2013

Details for the installation of the mechanical system and equipment is not provided on the plans. Action required - Provide details.
Misc
Corrective Action Required
01/04/2013

Specifications for the mechanical system have not been provided. Action required - Provide specifications.
Misc
Corrective Action Required
01/04/2013

Specifications for the electrical system have not been provided. Action required - Provide specifications.
Accessibility - Water closet - Clearance around
Corrective Action Required
01/04/2013

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - Toilet room 302 does not meet this requirement. Make needed corrections.
Project cost
Corrective Action Required
01/04/2013

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the cost for the building minus the foundation and underslab.
Misc
Corrective Action Required
01/04/2013

2006 IPC - 904.1 - Roof extension. All open vent pipes that extend through a roof shall be terminated at least 6 inches above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least 7 feet above the roof. Action required - This needs to be noted on the plan.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
01/04/2013

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - Provide emergency lighting at all required locations.
Misc
Corrective Action Required
01/04/2013

Circuiting is not shown for the emergency lights and exit signs. Action required - Make needed corrections.
Misc
Corrective Action Required
01/04/2013

An electrical fixture schedule is not provided. Action required - Provide addtional information.
Bldg - Doors - Size of doors
Corrective Action Required
01/04/2013

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The only exception for commercial buildings is closets less than 10 square feet in area. Make needed corrections.
Screening - Rooftop equipment
Corrective Action Required
01/04/2013

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - Two of the condinsing units are not screened. Make needed corrections.
Bldg - Guards - Mechanical equipment IBC
Corrective Action Required
01/04/2013

2006 IBC 1013.5 - Mechanical equipment. Guards shall be provided where appliances, equipment, fans, roof hatch openings or other components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall be constructed so as to prevent the passage of a 21-inch-diameter sphere. The guard shall extend not less than 30 inches beyond each end of such appliance, equipment fan or component. Action required - Provide a guard for the condensing units or relocate them.
Fire Plan Review Rejected 12/27/2012 12/17/2012
Brian Austerman
Misc
Corrective Action Required
12/17/2012

Provide civil plans including fire main valve at the street and property lines.
Knox box required
Corrective Action Required
12/17/2012

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Plan set shows 2 knox boxes, only 1 is required, locate above FDC and near the outside waterflow H/S.
Type I hood - Where required
Corrective Action Required
12/17/2012

2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Required if grease vapors will be produced, if this is to be a warming kitchen provide a statement that no cooking will be done.
Misc
Corrective Action Required
12/17/2012

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Provide duct detection on rtu's over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the alarm panel
Misc
Corrective Action Required
12/17/2012

The door to the sprinkler room may be required to be a rated door depending on distance to the property line, provide civil plans
Misc
Corrective Action Required
12/17/2012

Provide rating on walls required to be rated as a fire wall
Misc
Corrective Action Required
12/17/2012

FDC on plan shows it located in the middle of the fire main coming into the building. This is to be a separate line to the riser.
Misc
Corrective Action Required
12/17/2012

The fire protection main coming into the building is a 4" line but the plan shows it feeding a 6" riser. The riser must be 4" or less and water availability needs to be calculated at 4" not 6".
Construction documents - Fire protection systems
Corrective Action Required
12/17/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
12/17/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $3,841.04 $3,841.04 Paid 03/13/2013
8331507-Sewer Connection Fee $780.00 $780.00 Paid 03/13/2013
$780.00
8350015-Water Meter Fee $1,500.05 $1,500.05 Paid 04/04/2013
$1,500.05
8331401-Water Tap Fee $10,283.00 $10,283.00 Paid 04/04/2013
$10,283.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 4/23/2013 4/23/2013 at 12:00 AM 04/23/2013
In-wall Inspection Not Ready 4/24/2013 at 12:00 AM 04/24/2013
Corrective Action Required
04/24/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES:
In-wall Inspection Partial 4/25/2013 4/25/2013 at 12:00 AM 04/25/2013
Misc
Partial Correction
04/25/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 106 THRU 113; 201; 203; 204; 206 EXCEPT N WALL; 207;
Above Ceiling Inspection Partial 4/26/2013 4/25/2013 at 12:00 AM 04/25/2013
Misc
Partial Correction
04/25/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS IN 202 OK TO CONCEAL WITH INSULATION
Rough Electrical Inspection - Commercial Partial 04/29/2013
Misc
Partial Correction
04/29/2013
OK TO COVER WHEN READY LIQUID-TIGHT NM CONDUIT AND BOXES FOR RECEPTS AT EAST AND SOUTH PARAPET WALLS.
In-wall Inspection Partial 4/29/2013 (8:00 to 5:00) 5/2/2013 at 12:00 AM 05/02/2013
Misc
Partial Correction
04/25/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 106 THRU 113; 200; 201; 202; 203; 204; 206 INCLUDING N WALL; 207; 208
In-wall Inspection Partial 5/6/2013 at 12:00 AM 05/06/2013
Misc
Partial Correction
05/02/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 106 THRU 113; 200; 201; 202; 203; 204; 206 INCLUDING N WALL; 207; 208; 201 W WALL @ STAIRWELL;
Rated Assembly Inspection Partial 5/6/2013 at 12:00 AM 05/06/2013
Misc
Partial Correction
05/06/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT STAIRWELL: 201 W WALL @ STAIRWELL EAST FACE;
Misc
Corrective Action Required
05/06/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT ELEVATOR SHAFT:
Above Ceiling Inspection Partial 5/6/2013 at 12:00 AM 05/06/2013
Misc
Partial Correction
04/25/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS IN 202 OK TO CONCEAL WITH INSULATION
Misc
Partial Correction
05/06/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Above Ceiling Inspection Not Ready 5/9/2013 5/9/2013 at 12:00 AM 05/09/2013
Misc
Partial Correction
05/06/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS IN 202 OK TO CONCEAL WITH INSULATION
Misc
Partial Correction
05/06/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Above Ceiling Inspection Partial 5/10/2013 5/10/2013 at 12:00 AM 05/10/2013
Misc
Partial Correction
05/09/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204 & 207 AFTER ALL MC ELECT CABLE RUNS ARE SECURED WITHIN 12" OF ENTRY TO BOXES;
Misc
Partial Correction
05/09/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
05/10/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PERIMETER OF 202;
In-wall Inspection Partial 5/10/2013 at 12:00 AM 05/10/2013
Misc
Partial Correction
05/06/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 106 THRU 113; 200; 201; 202; 203; 204; 206 INCLUDING N WALL; 207; 208; 201 W WALL @ STAIRWELL; STAIRWELLS; 3RD FLOOR SPACES COMPLETE EXCEPT ELEVATOR FRON WALL;
Above Ceiling Inspection Partial 5/17/2013 5/17/2013 at 12:00 AM 05/17/2013
Misc
Partial Correction
05/10/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204 & 207 AFTER ALL MC ELECT CABLE RUNS ARE SECURED WITHIN 12" OF ENTRY TO BOXES;
Misc
Partial Correction
05/10/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
05/10/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PERIMETER OF 201;202; 203;206;207;208
Rated Assembly Inspection Partial 5/21/2013 at 12:00 AM 05/21/2013
Misc
Partial Correction
05/06/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT STAIRWELL: 201 W WALL @ STAIRWELL EAST FACE; WEST WALL OF STAIRWELL FULL HEIGHT;
Misc
Corrective Action Required
05/06/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT ELEVATOR SHAFT:
In-wall Inspection Partial 5/21/2013 at 12:00 AM 05/21/2013
Misc
Partial Correction
05/10/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 106 THRU 113; 200; 201; 202; 203; 204; 206 INCLUDING N WALL; 207; 208; 201 W WALL @ STAIRWELL; STAIRWELLS; 3RD FLOOR SPACES COMPLETE EXCEPT ELEVATOR FRONT WALL; 3RD FLOOR PERIMETER WALLS;
Above Ceiling Inspection Partial 5/21/2013 5/21/2013 at 12:00 AM 05/21/2013
Misc
Partial Correction
05/17/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204 & 207 AFTER ALL MC ELECT CABLE RUNS ARE SECURED WITHIN 12" OF ENTRY TO BOXES;
Misc
Partial Correction
05/17/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
05/17/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PERIMETER OF 201; 202; 203; 206; 207; 208; 301;
Sidewalk Inspection Passed/Re-Inspect 5/15/2013 at 8:45 AM 05/22/2013
Underground Electrical Inspection - Commercial Failed 5/23/2013 at 12:00 AM 05/23/2013
Misc
Corrective Action Required
05/23/2013
SECONDARY ELECTRICAL SERVICE CONDUIT NOT APPROVED TO COVER. APPROVED DRAWING SHOWS THREE 4" PVC. 3" HAVE BEEN LAID IN TRENCH.
Above Ceiling Inspection Partial 5/24/2013 5/24/2013 at 12:00 AM 05/24/2013
Misc
Partial Correction
05/21/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204 & 207 AFTER ALL MC ELECT CABLE RUNS ARE SECURED WITHIN 12" OF ENTRY TO BOXES;
Misc
Partial Correction
05/21/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
05/21/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 106; 107; 108; PERIMETER OF 201; 202; 203; 206; 207; 208; 301;
Underground Electrical Inspection - Commercial Partial 5/24/2013 at 12:00 AM 05/24/2013
Misc
Partial Correction
05/24/2013
OK TO COVER WHEN READY THREE 4" PVC SECONDARY ELECTRICAL SERVICE CONDUITS TRENCHED FROM XFMR LOCATION TO BUILDING AT METER BANK
Rated Assembly Inspection Partial 5/29/2013 at 12:00 AM 05/29/2013
Misc
Partial Correction
05/21/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT STAIRWELL 2: 201 W WALL @ STAIRWELL EAST FACE; WEST WALL OF STAIRWELL FULL HEIGHT; ONE LAYER OF 5/8" TYPE X GWB FASTENER PATTERN OK
Misc
Corrective Action Required
05/21/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT ELEVATOR SHAFT:
Above Ceiling Inspection Partial 5/29/2013 at 12:00 AM 05/29/2013
Misc
Partial Correction
05/24/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204 & 207 AFTER ALL MC ELECT CABLE RUNS ARE SECURED WITHIN 12" OF ENTRY TO BOXES;
Misc
Partial Correction
05/24/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
05/24/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: LID @ TOP OF STAIRWELL #1; 105; 106; 107; 108; 111; 112; CLO 114; CLO 117; PERIMETER OF 201; 202; 203; 206; 207; 208; 301;
Gas Piping Inspection - Commercial Not Ready 5/29/2013 at 12:00 AM 05/29/2013
Misc
Corrective Action Required
05/29/2013
EXPOSED GAS PIPING TO BE PAINTED
Misc
Corrective Action Required
05/29/2013
ROOFTOP PIPING SUPPORTS TO BE CLAMPED TO PIPE
Gas Service Inspection - Commercial Passed 5/29/2013 5/29/2013 at 12:00 AM 05/29/2013
Above Ceiling Inspection Partial 6/5/2013 6/5/2013 at 12:00 AM 06/05/2013
Misc
Partial Correction
05/29/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204 & 207 AFTER ALL MC ELECT CABLE RUNS ARE SECURED WITHIN 12" OF ENTRY TO BOXES;
Misc
Partial Correction
05/29/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
05/29/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 106; 107; 108; 111; 112; CLO 114; CLO 117; PERIMETER OF 201; 202; 203; 206; 207; 208; 301; LIDS @ STAIRWELL #2; TOIL 302;
Rated Assembly Inspection Partial 6/5/2013 at 12:00 AM 06/05/2013
Misc
Partial Correction
05/29/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT STAIRWELL 2: 201 W WALL @ STAIRWELL EAST FACE; WEST WALL OF STAIRWELL FULL HEIGHT; ONE LAYER OF 5/8" TYPE X GWB FASTENER PATTERN OK
Misc
Corrective Action Required
05/29/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT ELEVATOR SHAFT:
Misc
Partial Correction
06/05/2013
OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION AT 1 HR FIRE-RATED WALLS @ FOLLOWING LOCATIONS: 3RD FLOOR PERIMETER WALLS EXCEPT AT ELEVATOR SHAFT;
Above Ceiling Inspection Partial 6/7/2013 6/7/2013 at 12:00 AM 06/07/2013
Misc
Partial Correction
06/05/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204 & 207 AFTER ALL MC ELECT CABLE RUNS ARE SECURED WITHIN 12" OF ENTRY TO BOXES;
Misc
Partial Correction
06/05/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
06/05/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 106; 107; 108; 111; 112; CLO 114; CLO 117; PERIMETER OF 201; 202; 203; 206; 207; 208; 301; LIDS @ STAIRWELL #2; TOIL 302; LID AT TOP OF ELEVATOR SHAFT; 204 NOT APPROVED: NEC 300-11 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]
Rated Assembly Inspection Partial 6/7/2013 6/7/2013 at 12:00 AM 06/07/2013
Misc
Partial Correction
06/05/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT STAIRWELL 2: 201 W WALL @ STAIRWELL EAST FACE; WEST WALL OF STAIRWELL FULL HEIGHT; ONE LAYER OF 5/8" TYPE X GWB FASTENER PATTERN OK
Misc
Partial Correction
06/07/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT ELEVATOR SHAFT: ALL EXCEPT TOP 6' -- SEE SCREW SPACING
Misc
Partial Correction
06/05/2013
OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION AT 1 HR FIRE-RATED WALLS @ FOLLOWING LOCATIONS: 3RD FLOOR PERIMETER WALLS EXCEPT AT ELEVATOR SHAFT;
Above Ceiling Inspection Partial 6/11/2013 6/11/2013 at 12:00 AM 06/11/2013
Misc
Partial Correction
06/07/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204; 207; 119; 118; BOTTOM OF STAIRWELL 102;
Misc
Partial Correction
06/07/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
06/07/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 106; 107; 108; 111; 112; CLO 114; CLO 117; PERIMETER OF 201; 202; 203; 206; 207; 208; 301; LIDS @ STAIRWELL #2; TOIL 302; LID AT TOP OF ELEVATOR SHAFT; 204 NOT APPROVED: NEC 300-11 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]
Rated Assembly Inspection Partial 6/11/2013 at 12:00 AM 06/11/2013
Misc
Partial Correction
06/07/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT STAIRWELL 2: 201 W WALL @ STAIRWELL EAST FACE; WEST WALL OF STAIRWELL FULL HEIGHT; ONE LAYER OF 5/8" TYPE X GWB FASTENER PATTERN OK
Misc
Partial Correction
06/07/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT ELEVATOR SHAFT: GWB FULL HEIGHT OK TO TAPE, MUD & FIRE-SEAL;
Misc
Partial Correction
06/07/2013
OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION AT 1 HR FIRE-RATED WALLS @ FOLLOWING LOCATIONS: 3RD FLOOR PERIMETER WALLS EXCEPT AT ELEVATOR SHAFT;
Sprinkler - Hydrostatic Test Passed 6/18/2013 at 10:00 AM 06/18/2013
Above Ceiling Inspection Partial 6/21/2013 at 12:00 AM 06/21/2013
Misc
Resolved
06/21/2013
SYSTEMS ABOVE BOTTOM CHORD OF ROOF/CEILING JOISTS OK TO CONCEAL WITH INSULATION IN FOLLOWING AREAS: 202; 204; 207; 119; 118; BOTTOM OF STAIRWELL 102;
Misc
Resolved
06/21/2013
SOFFIT FRAMING AND ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY AT 1ST FLOOR EAST ENTRANCE AND 2ND FLOOR EAST VERANDA
Misc
Partial Correction
06/11/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 106; 107; 108; 111; 112; CLO 114; CLO 117; PERIMETER OF 201; 202; 203; 206; 207; 208; 301; LIDS @ STAIRWELL #2; TOIL 302; LID AT TOP OF ELEVATOR SHAFT; 204
Electrical Service Inspection Passed 7/1/2013 7/1/2013 at 12:00 AM 07/01/2013
Above Ceiling Inspection Passed 7/1/2013 at 12:00 AM 07/01/2013
Misc
Resolved
07/01/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 106; 107; 108; 111; 112; CLO 114; CLO 117; PERIMETER OF 201; 202; 203; 206; 207; 208; 301; LIDS @ STAIRWELL #2; TOIL 302; LID AT TOP OF ELEVATOR SHAFT; 204
In-wall Inspection Passed 6/5/2013 7/1/2013 at 12:00 AM 07/01/2013
Misc
Resolved
07/01/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 106 THRU 113; 200; 201; 202; 203; 204; 206 INCLUDING N WALL; 207; 208; 201 W WALL @ STAIRWELL; STAIRWELLS; 3RD FLOOR SPACES COMPLETE EXCEPT ELEVATOR FRONT WALL; 3RD FLOOR PERIMETER WALLS;
Rated Assembly Inspection Passed 7/1/2013 at 12:00 AM 07/01/2013
Misc
Resolved
07/01/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT STAIRWELL 2: 201 W WALL @ STAIRWELL EAST FACE; WEST WALL OF STAIRWELL FULL HEIGHT; ONE LAYER OF 5/8" TYPE X GWB FASTENER PATTERN OK
Misc
Resolved
07/01/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALLS AT ELEVATOR SHAFT: GWB FULL HEIGHT OK TO TAPE, MUD & FIRE-SEAL;
Misc
Resolved
07/01/2013
OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION AT 1 HR FIRE-RATED WALLS @ FOLLOWING LOCATIONS: 3RD FLOOR PERIMETER WALLS EXCEPT AT ELEVATOR SHAFT;
Underground Electrical Inspection - Commercial Passed 7/1/2013 at 12:00 AM 07/01/2013
Misc
Resolved
07/01/2013
OK TO COVER WHEN READY THREE 4" PVC SECONDARY ELECTRICAL SERVICE CONDUITS TRENCHED FROM XFMR LOCATION TO BUILDING AT METER BANK
Rough Electrical Inspection - Commercial Passed 5/29/2013 7/1/2013 at 12:00 AM 07/01/2013
Misc
Resolved
07/01/2013
OK TO COVER WHEN READY LIQUID-TIGHT NM CONDUIT AND BOXES FOR RECEPTS AT EAST AND SOUTH PARAPET WALLS.
Miscellaneous Inspection Partial 7/2/2013 at 12:00 AM 07/02/2013
Alarm Test Passed 7/3/2013 at 2:00 PM 07/03/2013
Sprinkler - Flow Test Passed 7/3/2013 at 2:00 PM 07/03/2013
Miscellaneous Inspection Passed 7/3/2013 at 12:00 AM 07/03/2013
Occupancy Inspection - Codes Commercial Not Ready 7/5/2013 at 12:00 AM 07/05/2013
Occupancy Inspection - Codes Commercial Partial 7/8/2013 at 12:00 AM 07/08/2013
Occupancy Inspection - Codes Commercial Partial 7/9/2013 at 12:00 AM 07/09/2013
Occupancy Inspection - Codes Commercial Partial 7/10/2013 7/10/2013 at 12:00 AM 07/10/2013
Misc
Corrective Action Required
07/10/2013
EXCISE TAX DUE AND OWING
Misc
Corrective Action Required
07/10/2013
FINAL INSPECTION TO BE CONTINUED 7/11 WHEN SITEWORK HAS FURTHER PROGRESSED.
Occupancy Inspection - Fire Temporary C of O 7/10/2013 at 12:00 AM 07/10/2013
Misc
Corrective Action Required
07/10/2013
(1)address the exterior of the front and rear entry doors with the numerics of 308 readable from the roadway, in a contrasting color with the background (2)label the sprinkler room access door "sprinkler room" (3)1st,2nd,3rd floor elevator smoke detectors in hallway need to be uncovered (4) smoke detector in the elevator control room needs to be uncovered (5)obtain elevator certification through state inspection (6)open j-box in elevator control room (7)secure the compressed gas bottles in the cooler room (8)3rd floor / patio exit/emerg lights missing. (9) keys for the knox box - front enrty door, 3rd floor rear entry door, security gate to rear stairs, sprinkler room door, elevator override
Sewer Service Inspection Passed 7/8/2013 at 12:00 AM 07/10/2013
Occupancy Inspection - Codes Commercial Temporary C of O 7/11/2013 at 12:00 AM 07/11/2013
Misc
Resolved
07/11/2013
EXCISE TAX DUE AND OWING
Misc
Corrective Action Required
07/10/2013
FINAL INSPECTION TO BE RESUMED 7/12 WHEN WORK HAS FURTHER PROGRESSED.
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY WATER DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT
Misc
Corrective Action Required
07/11/2013
CHECK ALL STAIR HANDRAILS FOR CODE HEIGHT 34" - 38" FROM TOE OF TREAD
Misc
Corrective Action Required
07/11/2013
RESTROOM MIRRORS SUBJECT TO APPROVAL.
Misc
Corrective Action Required
07/11/2013
BLOCK RETAINING WALL SUBJECT TO APPROVAL WHEN MANUFACTURER'S LITERATURE IS PROVIDED.
Occupancy Inspection - Codes Commercial Partial 7/12/2013 at 12:00 AM 07/14/2013
Misc
Corrective Action Required
07/11/2013
FINAL INSPECTION TO BE RESUMED 7/12 WHEN SITEWORK HAS FURTHER PROGRESSED.
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY WATER DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
07/11/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT
Misc
Corrective Action Required
07/11/2013
CHECK ALL STAIR HANDRAILS FOR CODE HEIGHT 34" - 38" FROM TOE OF TREAD
Misc
Corrective Action Required
07/11/2013
RESTROOM MIRRORS SUBJECT TO APPROVAL.
Misc
Corrective Action Required
07/11/2013
BLOCK RETAINING WALL SUBJECT TO APPROVAL WHEN MANUFACTURER'S LITERATURE IS PROVIDED.
Occupancy Inspection - Planning Temporary C of O 07/15/2013
Corrective Action Required
07/15/2013
LIGHT FIXTURES. The wall-mounted light fixtures on the north facade (in the recessed area) do not meet UDO requirements for light fixtures with full 90-degree cutoffs. Fixtures have to have full cut-offs so that the light is directed down, such as the fixture used on the west facade.
Corrective Action Required
07/15/2013
PARKING SPACES. The two parallel parking spaces on the west side of the building shall be striped according to the approved plan.
Occupancy Inspection - Codes Commercial Partial 7/17/2013 at 12:00 AM 07/17/2013
Misc
Resolved
07/17/2013
FINAL INSPECTION TO BE RESUMED 7/12 WHEN SITEWORK HAS FURTHER PROGRESSED.
Misc
Corrective Action Required
07/14/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
07/14/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Resolved
07/17/2013
RESOLVE ANY WATER DEPARTMENT ISSUES
Misc
Corrective Action Required
07/14/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
07/14/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT: SEE WATER-FED COFFEE MAKERS.
Misc
Resolved
07/17/2013
CHECK ALL STAIR HANDRAILS FOR CODE HEIGHT 34" - 38" FROM TOE OF TREAD
Misc
Corrective Action Required
07/14/2013
RESTROOM MIRRORS SUBJECT TO APPROVAL.
Misc
Corrective Action Required
07/14/2013
CONSTRUCTION OF BLOCK RETAINING WALL DOES NOT CONFORM TO MANUFACTURER'S LITERATURE. 52" HEIGHT FROM AB3 BASE TO TOP OF CAP EXCEEDS 36" MAXIMUM. RECOMMENDED 1/2" SETBACK PER COURSE HAS NOT BEEN PROVIDED.
Misc
Corrective Action Required
07/17/2013
SEAL TOP & SIDES OF ALL ELECTRICAL FIXTURES AND EQUIPMENT TO MASONRY WALLS.
Misc
Corrective Action Required
07/17/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Occupancy Inspection - Water Utilities Passed 7/17/2013 at 12:00 AM 07/17/2013
Rated Assembly Inspection Passed 7/1/2013 at 12:00 AM 07/18/2013
Misc
Partial Correction
07/10/2013
OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION AT 1 HR FIRE-RATED WALLS @ FOLLOWING LOCATIONS: SOUTH EXTERIOR WALL (S WALL OF [100]; NORTH EXTERIOR WALL AT [116] N; STORAGE [118]
Misc
Corrective Action Required
07/10/2013
(1)address the exterior of the front and rear entry doors with the numerics of 308 readable from the roadway, in a contrasting color with the background (2)label the sprinkler room access door "sprinkler room" (3)1st,2nd,3rd floor elevator smoke detectors in hallway need to be uncovered (4) smoke detector in the elevator control room needs to be uncovered (5)obtain elevator certification through state inspection (6)open j-box in elevator control room (7)secure the compressed gas bottles in the cooler room (8)3rd floor / patio exit/emerg lights missing. (9) keys for the knox box - front enrty door, 3rd floor rear entry door, security gate to rear stairs, sprinkler room door, elevator override
Occupancy Inspection - Codes Commercial Temporary C of O 7/18/2013 at 12:00 AM 07/18/2013
Misc
Corrective Action Required
07/17/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
07/17/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
07/17/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
07/17/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT: SEE WATER-FED COFFEE MAKERS.
Misc
Corrective Action Required
07/17/2013
RESTROOM MIRRORS SUBJECT TO APPROVAL.
Misc
Corrective Action Required
07/17/2013
CONSTRUCTION OF BLOCK RETAINING WALL DOES NOT CONFORM TO MANUFACTURER'S LITERATURE. 52" HEIGHT FROM AB3 BASE TO TOP OF CAP EXCEEDS 36" MAXIMUM. RECOMMENDED 1/2" SETBACK PER COURSE HAS NOT BEEN PROVIDED.
Misc
Corrective Action Required
07/17/2013
SEAL TOP & SIDES OF ALL ELECTRICAL FIXTURES AND EQUIPMENT TO MASONRY WALLS.
Misc
Corrective Action Required
07/17/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Occupancy Inspection - Fire Passed 7/22/2013 at 12:00 AM 07/22/2013
Misc
Partial Correction
07/10/2013
OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION AT 1 HR FIRE-RATED WALLS @ FOLLOWING LOCATIONS: SOUTH EXTERIOR WALL (S WALL OF [100]; NORTH EXTERIOR WALL AT [116] N; STORAGE [118]
Misc
Corrective Action Required
07/10/2013
(1)address the exterior of the front and rear entry doors with the numerics of 308 readable from the roadway, in a contrasting color with the background (2)label the sprinkler room access door "sprinkler room" (3)1st,2nd,3rd floor elevator smoke detectors in hallway need to be uncovered (4) smoke detector in the elevator control room needs to be uncovered (5)obtain elevator certification through state inspection (6)open j-box in elevator control room (7)secure the compressed gas bottles in the cooler room (8)3rd floor / patio exit/emerg lights missing. (9) keys for the knox box - front enrty door, 3rd floor rear entry door, security gate to rear stairs, sprinkler room door, elevator override
Occupancy Inspection - Codes Commercial Partial 7/26/2013 at 12:00 AM 07/26/2013
Misc
Corrective Action Required
07/18/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
07/18/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
07/18/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
07/18/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT: SEE WATER-FED COFFEE MAKERS.
Misc
Resolved
07/26/2013
RESTROOM MIRRORS SUBJECT TO APPROVAL.
Misc
Corrective Action Required
07/18/2013
CONSTRUCTION OF BLOCK RETAINING WALL DOES NOT CONFORM TO MANUFACTURER'S LITERATURE. 52" HEIGHT FROM AB3 BASE TO TOP OF CAP EXCEEDS 36" MAXIMUM. RECOMMENDED 1/2" SETBACK PER COURSE HAS NOT BEEN PROVIDED.
Misc
Resolved
07/26/2013
SEAL TOP & SIDES OF ALL ELECTRICAL FIXTURES AND EQUIPMENT TO MASONRY WALLS.
Misc
Corrective Action Required
07/18/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Occupancy Inspection - Codes Commercial Partial 8/1/2013 at 12:00 AM 08/01/2013
Misc
Corrective Action Required
07/26/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
07/26/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
07/26/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
07/26/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT: SEE WATER-FED COFFEE MAKERS.
Misc
Corrective Action Required
07/26/2013
CONSTRUCTION OF BLOCK RETAINING WALL DOES NOT CONFORM TO MANUFACTURER'S LITERATURE. 52" HEIGHT FROM AB3 BASE TO TOP OF CAP EXCEEDS 36" MAXIMUM. RECOMMENDED 1/2" SETBACK PER COURSE HAS NOT BEEN PROVIDED.
Misc
Corrective Action Required
07/26/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Occupancy Inspection - Codes Commercial Partial 8/2/2013 at 12:00 AM 08/02/2013
Misc
Resolved
08/02/2013
RESOLVE ANY FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
08/01/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
08/01/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
08/01/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT: SEE WATER-FED COFFEE MAKERS.
Misc
Corrective Action Required
08/01/2013
CONSTRUCTION OF BLOCK RETAINING WALL DOES NOT CONFORM TO MANUFACTURER'S LITERATURE. 52" HEIGHT FROM AB3 BASE TO TOP OF CAP EXCEEDS 36" MAXIMUM. RECOMMENDED 1/2" SETBACK PER COURSE HAS NOT BEEN PROVIDED.
Misc
Corrective Action Required
08/01/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
08/02/2013
LABEL EXTERIOR OF ELECT PANELS BY UNIT #. ALSO, BLANK-OFF ANY UNUSED BREAKER POSITION OPENINGS.
Occupancy Inspection - Codes Commercial Temporary C of O 8/2/2013 at 12:00 AM 08/02/2013
Misc
Corrective Action Required
08/02/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
08/02/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Corrective Action Required
08/02/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT: SEE WATER-FED COFFEE MAKERS.
Misc
Corrective Action Required
08/02/2013
CONSTRUCTION OF BLOCK RETAINING WALL DOES NOT CONFORM TO MANUFACTURER'S LITERATURE. 52" HEIGHT FROM AB3 BASE TO TOP OF CAP EXCEEDS 36" MAXIMUM. RECOMMENDED 1/2" SETBACK PER COURSE HAS NOT BEEN PROVIDED.
Misc
Corrective Action Required
08/02/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
08/02/2013
LABEL EXTERIOR OF ELECT PANELS BY UNIT #. ALSO, BLANK-OFF ANY UNUSED BREAKER POSITION OPENINGS.
Occupancy Inspection - Codes Commercial Failed 9/17/2013 at 12:00 AM 09/17/2013
Misc
Resolved
09/17/2013
RESOLVE ANY PUBLIC WORKS DEPARTMENT ISSUES
Misc
Corrective Action Required
08/02/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Resolved
09/17/2013
APPROVED BACKFLOW PREVENTION REQUIRED FOR ALL POTABLE WATER-FED EQUIPMENT: SEE WATER-FED COFFEE MAKERS.
Misc
Resolved
09/17/2013
CONSTRUCTION OF BLOCK RETAINING WALL DOES NOT CONFORM TO MANUFACTURER'S LITERATURE. 52" HEIGHT FROM AB3 BASE TO TOP OF CAP EXCEEDS 36" MAXIMUM. RECOMMENDED 1/2" SETBACK PER COURSE HAS NOT BEEN PROVIDED. NOTE: PER "MJF" AT BOB D CAMPBELL ENGINEERING 9/17/13 RETAINING WALL AS BUILT WITHOUT BATTER IS OK.
Misc
Corrective Action Required
09/17/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
09/17/2013
LABEL EXTERIOR OF ELECT PANELS BY UNIT #. ALSO, BLANK-OFF ANY UNUSED BREAKER POSITION OPENINGS.
Occupancy Inspection - Codes Commercial Failed 9/19/2013 at 12:00 AM 09/19/2013
Misc
Corrective Action Required
09/17/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Misc
Resolved
09/19/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Resolved
09/19/2013
LABEL EXTERIOR OF ELECT PANELS BY UNIT #. ALSO, BLANK-OFF ANY UNUSED BREAKER POSITION OPENINGS.
Occupancy Inspection - Codes Commercial Full C of O 9/19/2013 at 12:00 AM 09/19/2013
Misc
Resolved
09/19/2013
RESOLVE ANY PLANNING & DEVELOPMENT DEPARTMENT ISSUES
Gas Piping Inspection - Commercial Passed 9/19/2013 at 12:00 AM 09/20/2013
Misc
Resolved
09/20/2013
EXPOSED GAS PIPING TO BE PAINTED
Misc
Resolved
09/20/2013
ROOFTOP PIPING SUPPORTS TO BE CLAMPED TO PIPE
Occupancy Inspection - Engineering Passed 10/09/2013
Sidewalk Inspection Passed 10/09/2013
Documents & Images
Date Uploaded File Type Document Name
01/04/2013 Letter Plan Review Conditions
03/04/2013 Plans EXTERIOR WALL ASSEMBLY
03/06/2013 Letter Plan Review Conditions
03/12/2013 Letter Plan Review Conditions
03/13/2013 Letter Building Permit
04/03/2013 Letter Plan Review Conditions
04/25/2013 Letter Inspection Summary
04/25/2013 Letter Inspection Summary
04/29/2013 Letter Inspection Summary
05/02/2013 Letter Inspection Summary
05/06/2013 Letter Inspection Summary
05/06/2013 Letter Inspection Summary
05/17/2013 Letter Inspection Summary
05/29/2013 Letter Inspection Summary
06/07/2013 Letter Inspection Summary
06/11/2013 Letter Inspection Summary
06/21/2013 Letter Fire (Alarm) Plan Review Notice
06/21/2013 Letter Inspection Summary
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
06/26/2013 Letter Fire (Sprinkler) Plan Review
07/01/2013 Letter Inspection Summary
07/10/2013 Letter Fire Loss Reduction Form
07/10/2013 Letter Inspection Summary
07/11/2013 Letter Codes Temporary Certificate of Occupancy
07/17/2013 Letter Inspection Summary
07/26/2013 Letter Inspection Summary
08/02/2013 Letter Codes Temporary Certificate of Occupancy
08/30/2013 Letter Codes 10 Day Letter
09/04/2013 Letter Codes 10 Day Letter
09/06/2013 Receipt Mail Receipt
09/17/2013 Letter Inspection Summary
09/18/2013 Letter DOC091813-008.pdf
09/19/2013 Letter Inspection Summary
09/19/2013 Letter Field Certificate of Occupancy
09/20/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home