Permit Application Status

PRCOM20121736


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20121736
Building Permit - Commercial
Certificate of Occupancy
FORT WAYNE MATADOR INC
CHANGE OF TENANT
TENANT FINISH FOR MERCANTILE
08/01/2012
11/02/2012
10/15/2014
02/08/2013
Locations
Contacts
ALLIED RETAIL CONCEPTS LLC, Address:6205 GODDARD ST, Phone:(913) 492-8008  
TEMP-CON LLC, Address:15670 S KEELER ST, Phone:(913) 768-4888  
S & S ELECTRICAL CONTRACTING LLC, Address:574 NW 1921 RD, Phone:(816) 847-2433  
S & S MECHANICAL CONTRACTORS LLC , Address:PO BOX 4115, Phone:(913) 310-0011  
FORT WAYNE MATADOR INC, Address:185 NW SPANISH RIVER BLVD STE 100  
CM Cortland Morgan Architect, Address:711 N Fielder Rd  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/06/2012
Brian Austerman
Misc
Corrective Action Required
12/06/2012

Call 816-969-1300 to schedule flow and alarm test
Alarm Plan Review Released for Construction 11/30/2012
Brian Austerman
Misc
Corrective Action Required
11/30/2012

Per phone conversation with Bill there will be an outside horn strobe that is activated off of the flow switch only. Not to sound on general fire alarm but waterflow only. Verified at alarm testing
Misc
Corrective Action Required
11/30/2012

Duct detectors shall initiate unit shut down and transmit a supervisory signal to the alarm panel, verifiedf at alarm testing
Misc
Corrective Action Required
11/30/2012

Call 816-969-1300 to schedule alarm testing prior to the final inspection
Internal Plan Review (Res) Approved 11/30/2012 11/01/2012
Mike Weisenborn
True
License Tax Codes Approved 11/30/2012 11/01/2012
Mike Weisenborn
Building Plan Review Approved 09/14/2012 09/12/2012
Mike Weisenborn
Business License
Resolved
09/12/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Prior to permit approval, provide the name of the licensed general contractor for the project.
License contractors
Resolved
09/12/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Prior to permit approval, provide the names of the licensed mechanical, electrical and plumbing sub-contractors for the project.
Misc
Resolved
09/12/2012

Documentation from a structural engineer licensed in the State of Missouri, is required for the installation of the new mechanical equipment on the roof. Action required - Provide documentation stating that the existing roof system is capable of supporting the new equipment or provide details for the required alterations to the structure. This information is required to be signed and sealed. Mike Weisenborn 09/12/2012 9:58 AM - Additional information has been provided.
Misc
Resolved
09/12/2012

Plumbing drawings/details have not been provided for the alterations to the systems. Action required - Provide information for the alterations to the waste, vent, water and gas systems. Mike Weisenborn 09/12/2012 9:59 AM - Additional information has been provided
Bldg - Exit signage - Where required
Resolved
09/12/2012

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Two means of egress is required from the storage room due to common path of travel requirements. Provide additional exit signage at the doors from the storage room to the sales area. Mike Weisenborn 09/12/2012 9:59 AM - Corrections have been made.
Fire Plan Review Approved with Conditions 09/14/2012 09/07/2012
Brian Austerman
Knox box required
Corrective Action Required
09/07/2012

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action Required: Call 816-969-1300 to obtain an application
Construction documents - Fire protection systems
Corrective Action Required
09/07/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: This is deffered as it is a seperate submittal
Construction documents for fire alarm systems
Corrective Action Required
09/07/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: This is deferred as it is a separate submittal
Internal Plan Review (Res) Rejected 08/13/2012 08/13/2012
Mike Weisenborn
Zoning Review Approved 08/13/2012 08/13/2012
Mike Weisenborn
Building Plan Review Rejected 08/13/2012 08/13/2012
Mike Weisenborn
Business License
Corrective Action Required
08/13/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Prior to permit approval, provide the name of the licensed general contractor for the project.
License contractors
Corrective Action Required
08/13/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Prior to permit approval, provide the names of the licensed mechanical, electrical and plumbing sub-contractors for the project.
Misc
Corrective Action Required
08/13/2012

Documentation from a structural engineer licensed in the State of Missouri, is required for the installation of the new mechanical equipment on the roof. Action required - Provide documentation stating that the existing roof system is capable of supporting the new equipment or provide details for the required alterations to the structure. This information is required to be signed and sealed.
Misc
Corrective Action Required
08/13/2012

Plumbing drawings/details have not been provided for the alterations to the systems. Action required - Provide information for the alterations to the waste, vent, water and gas systems.
Bldg - Exit signage - Where required
Corrective Action Required
08/13/2012

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Two means of egress is required from the storage room due to common path of travel requirements. Provide additional exit signage at the doors from the storage room to the sales area.
Fire Plan Review Approved 08/13/2012 08/08/2012
Brian Austerman
Misc
Corrective Action Required
08/08/2012

FDC needs labeled showing what address it serves
Misc
Corrective Action Required
08/08/2012

Door to riser room needs labeled as "SPRINKLER ROOM"
Misc
Corrective Action Required
08/08/2012

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action Required: For all units 2,000 CFM or greater duct detection is required. Activation will shut down the unit and send a supervisory signal to the panel. Verified at alarm testing
Construction documents - Fire protection systems
Corrective Action Required
08/08/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide plans for approval for any sprinkler modifications
Construction documents for fire alarm systems
Corrective Action Required
08/08/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide alarm plans for approval for any alarm system modifications
Portable fire extinguishers - general
Corrective Action Required
08/08/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide a minimum size of 2A10B:C extinguishers
Address numbers required
Corrective Action Required
08/08/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Provide addressing on all exterior doors leading into the space
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,225.50 $1,225.50 Paid 11/02/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Above Ceiling Inspection Partial 11/6/2012 at 12:00 AM 11/06/2012
Misc
Partial Correction
11/06/2012
NO ISSUES FOUND ON GWB CEILING FRAMING ONLY AT "CASH" & "COUNT" SPACES; ABOVE-CEILING ELECTRICAL NO TREADY FOR INSPECTION
In-wall Inspection Not Ready 11/6/2012 at 12:00 AM 11/06/2012
Misc
Corrective Action Required
11/06/2012
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT DRAWINGS.
In-wall Inspection Partial 11/6/2012 at 12:00 AM 11/06/2012
Misc
Resolved
11/06/2012
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT DRAWINGS.
Misc
Partial Correction
11/06/2012
OK TO COVER WHEN READY WALL FRAMING AT DEMISING WALL.
In-wall Inspection Passed 11/12/2012 11/12/2012 at 12:00 AM 11/12/2012
Misc
Resolved
11/12/2012
OK TO COVER WHEN READY WALL FRAMING AT DEMISING WALL.
Rough Plumbing Inspection - Commercial Partial 11/27/2012 (8:00 to 5:00) 11/27/2012 at 12:00 AM 11/27/2012
Misc
Corrective Action Required
11/27/2012
UNDERSLAB FOR TWO BATHS AND MOP SINK APPROVED. NEED TO SEE TIE IN TO EXISTING VENTS IN WALL. OKAY TO COVER GROUND PLUMBING.
Rough Plumbing Inspection - Commercial Passed 11/30/2012 11/30/2012 at 12:00 AM 11/30/2012
Misc
Resolved
11/30/2012
UNDERSLAB FOR TWO BATHS AND MOP SINK APPROVED. NEED TO SEE TIE IN TO EXISTING VENTS IN WALL. OKAY TO COVER GROUND PLUMBING.
Above Ceiling Inspection Partial 1/3/2013 1/3/2013 at 12:00 AM 01/03/2013
Misc
Partial Correction
11/06/2012
OKAY TO DROP EVERYWHERE EXCEPT WHERE MC COMES THROUGH CEILING FOR CASH REGISTERS
Alarm Test Passed 1/11/2013 at 3:00 PM 01/14/2013
Sprinkler - Flow Test Failed 1/11/2013 at 3:00 PM 01/14/2013
Above Ceiling Inspection Passed 01/14/2013
Misc
Resolved
01/14/2013
OKAY TO DROP EVERYWHERE EXCEPT WHERE MC COMES THROUGH CEILING FOR CASH REGISTERS
Occupancy Inspection - Codes Commercial Failed 1/14/2013 1/14/2013 at 12:00 AM 01/14/2013
Misc
Corrective Action Required
01/14/2013
1. PENDING FIRE DEPARTMENT APPROVAL FOR TCO- 2. APPROVED FOR STOCKING AND TRAINING ONLY. NOT TO BE OPEN TO THE PUBLIC. CONTACT MIKE COPELAND FOR TCO WHEN FIRE DEPARTMENT ISSUES ARE COMPLETE.
Occupancy Inspection - Fire Temporary C of O 1/14/2013 at 12:00 AM 01/14/2013
Misc
Corrective Action Required
01/14/2013
- restore the fire department connection for the sprinkler system back to working order. - need access keys for the store. (to lock in the knox box) - label the access door for the sprinkler room on the sales side of the door - lower sprinkler heads below the drop ceiling as needed located at the rear of the sales area - replace exterior water flow bell with a weatherproof horn/strobe - address exterior of the double doors to receiveing ( southwest double doors) with numeric address of 901
Occupancy Inspection - Fire Passed 2/6/2013 at 12:00 AM 02/06/2013
Misc
Corrective Action Required
01/14/2013
- restore the fire department connection for the sprinkler system back to working order. - need access keys for the store. (to lock in the knox box) - label the access door for the sprinkler room on the sales side of the door - lower sprinkler heads below the drop ceiling as needed located at the rear of the sales area - replace exterior water flow bell with a weatherproof horn/strobe - address exterior of the double doors to receiveing ( southwest double doors) with numeric address of 901
Occupancy Inspection - Codes Commercial Full C of O 2/8/2013 at 12:00 AM 02/08/2013
Misc
Resolved
02/08/2013
1. PENDING FIRE DEPARTMENT APPROVAL FOR TCO- 2. APPROVED FOR STOCKING AND TRAINING ONLY. NOT TO BE OPEN TO THE PUBLIC. CONTACT MIKE COPELAND FOR TCO WHEN FIRE DEPARTMENT ISSUES ARE COMPLETE.
Documents & Images
Date Uploaded File Type Document Name
08/13/2012 Letter Plan Review Conditions
11/01/2012 Letter Plan Review Conditions
11/02/2012 Letter Building Permit
11/06/2012 Letter Inspection Summary
11/06/2012 Letter Inspection Summary
11/12/2012 Letter Inspection Summary
11/27/2012 Letter Inspection Summary
11/30/2012 Letter Inspection Summary
01/03/2013 Letter Inspection Summary
01/14/2013 Letter Inspection Summary
01/14/2013 Letter Fire Loss Reduction Form
02/06/2013 Letter Fire Loss Reduction Form
02/08/2013 Letter Field Certificate of Occupancy
02/11/2013 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
06/27/2013 Letter Fire (Sprinkler) Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home