Permit Application Status

PRCOM20121319


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20121319
Building Permit - Commercial
Certificate of Occupancy
ASSOCIATED PEDIATRIC INVESTORS LLC
NEW COMMERCIAL
NEW BUILDING
06/12/2012
07/30/2012
12/23/2012
02/25/2013
Locations
Contacts
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
CITY WIDE HEATING & COOLING INC, Address:2824 ROE LANE, Phone:(913) 384-6006  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
HOLLIS MILLER ARCHITECTS  
ASSOCIATED PEDIATRIC INVESTORS LLC, Address:1425 NW BLUE PKWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 06/26/2012 10/25/2012
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
10/25/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Plans received October 18, 2012.
Misc
Corrective Action Required
10/25/2012

Duct detector activation shall send a supervisory alarm only to the panel and Central Station, without activation of interior horn/strobe appliances. Verified at inspection.
Installation acceptance testing
Corrective Action Required
10/25/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. The alarm system will be tested during the occupancy inspection for the building.
Internal Plan Review (Res) Approved 08/03/2012 07/30/2012
Mike Weisenborn
True
Final Development Plan Review Approved 08/03/2012 07/30/2012
Mike Weisenborn
Building Plan Review Approved 07/10/2012 07/11/2012
Mike Weisenborn
License contractors
Corrective Action Required
07/03/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing subcontractors prior to permit issuance.
Final Development Plan
Corrective Action Required
07/03/2012

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required - This comment is for information purposes.
Bldg - Draftstopping - Other groups
Resolved
07/10/2012

2006 IBC 717.4.3 - Other groups. Draftstopping shall be installed in attics and concealed roof spaces, such that any horizontal area does not exceed 3,000 square feet. Action required - Show how this requirement will be met. Mike Weisenborn 07/10/2012 9:54 AM - Information has been added to the plans.
Plumb - Separate facilities
Resolved
07/10/2012

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Designate the restrooms in the waiting area as mens and womens on the plans. Mike Weisenborn 07/10/2012 9:54 AM - Corrections have been made.
Engineered truss package
Corrective Action Required
07/03/2012

Copies of the engineered truss package were not provided at the time of permit application. Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
Bldg - Occupant load calculations - Areas without fixed seats
Resolved
07/10/2012

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - I have discussed the calculated occupant load with Mark and we are comfortable with using the one person per 100 square for the required plumbing fixture calculations. For exiting requirements the occupant load of the waiting area can either be based on the actual number of chairs being provided as shown on Sheet A140, or by the above mentioned table. Make needed corrections to the occupant load calculations. Mike Weisenborn 07/10/2012 9:55 AM - Corrections have been made.
Bldg - Minimum number of exits
Resolved
07/10/2012

2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way. Action required - As the occupant load of the waiting room is greater than 50 it is required to have two means of egress from the room. Provide a second means of egress from the waiting room meeting the code requirements for door swing, door hardware and exit signage. Mike Weisenborn 07/10/2012 9:55 AM - A second exit to the exterior has been added from the waiting area.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
07/03/2012

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Resolved
07/10/2012

I am unable to locate information for the sliding entry doors showing compliance with Sections 1008.1.3.2 and 1008.1.3.3 of the 2006 IBC. Action required - Provide additional documentation from the manufactor showing compliance with these sections. Mike Weisenborn 07/10/2012 9:56 AM - Additional information has been provided.
Accessibility - Water closet - Grab bars
Resolved
07/10/2012

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - I am unable to find a reference for the required vertical grab bar. Provide additional information. Mike Weisenborn 07/10/2012 9:57 AM - Additional information has been added.
Bldg - Attic spaces - Access
Corrective Action Required
07/30/2012

2006 IBC 1209.2 - Attic spaces. An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. A 30-inch minimum clear headroom in the attic space shall be provided at or above the access opening. Action required - This will be verified on inspection.
Fire Plan Review Approved 07/11/2012 07/03/2012
Brian Austerman
Misc
Corrective Action Required
07/03/2012

Plans received on July 2nd, approved on July 3rd as per prior comments
Internal Plan Review (Res) Rejected 06/26/2012 06/26/2012
Mike Weisenborn
License Tax Codes Approved 06/26/2012 06/26/2012
Mike Weisenborn
Building Plan Review Rejected 06/26/2012 06/26/2012
Mike Weisenborn
License contractors
Corrective Action Required
06/26/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing subcontractors prior to permit issuance.
Final Development Plan
Corrective Action Required
06/26/2012

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required - This comment is for information purposes.
Bldg - Draftstopping - Other groups
Corrective Action Required
06/26/2012

2006 IBC 717.4.3 - Other groups. Draftstopping shall be installed in attics and concealed roof spaces, such that any horizontal area does not exceed 3,000 square feet. Action required - Show how this requirement will be met.
Plumb - Separate facilities
Corrective Action Required
06/26/2012

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Designate the restrooms in the waiting area as mens and womens on the plans.
Engineered truss package
Corrective Action Required
06/26/2012

Copies of the engineered truss package were not provided at the time of permit application. Action required - Provide two (2) copies of the engineered truss package. The package shall be signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to framing inspection.
Bldg - Occupant load calculations - Areas without fixed seats
Corrective Action Required
06/26/2012

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - I have discussed the calculated occupant load with Mark and we are comfortable with using the one person per 100 square for the required plumbing fixture calculations. For exiting requirements the occupant load of the waiting area can either be based on the actual number of chairs being provided as shown on Sheet A140, or by the above mentioned table. Make needed corrections to the occupant load calculations.
Bldg - Minimum number of exits
Corrective Action Required
06/26/2012

2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way. Action required - As the occupant load of the waiting room is greater than 50 it is required to have two means of egress from the room. Provide a second means of egress from the waiting room meeting the code requirements for door swing, door hardware and exit signage.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
06/26/2012

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Corrective Action Required
06/26/2012

I am unable to locate information for the sliding entry doors showing compliance with Sections 1008.1.3.2 and 1008.1.3.3 of the 2006 IBC. Action required - Provide additional documentation from the manufactor showing compliance with these sections.
Accessibility - Water closet - Grab bars
Corrective Action Required
06/26/2012

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - I am unable to find a reference for the required vertical grab bar. Provide additional information.
Fire Plan Review Approved 06/26/2012 06/21/2012
Brian Austerman
Misc
Corrective Action Required
06/21/2012

1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Action Required: Panic hardware or 1/4 turn thumb latch only are allowed. For information only
Address numbers required
Corrective Action Required
06/21/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). For information only, verified at inspection
Misc
Corrective Action Required
06/21/2012

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. Action Required: This is referenced on M3.15 but I did not see it on the plan. To be verified at inspection
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/21/2012

2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action Required: Provide a minimum of one 2A10B:C extinguisher for every 75' of travel distance. Verified at inspection
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $6,317.50 $6,317.50 Paid 07/30/2012
8350015-Water Meter Fee $458.91 $458.91 Paid 07/30/2012
8331401-Water Tap Fee $8,144.00 $8,144.00 Paid 07/30/2012
9110073-Right of Way Permit Fee $60.00 $60.00 Paid 07/30/2012
8331507-Sewer Connection Fee $1,170.00 $1,170.00 Paid 07/30/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 8/22/2012 (11:30) 8/22/2012 at 12:00 AM 08/22/2012
Misc
Partial Correction
08/22/2012
GRADE BEAMS AND PERIMETER PADS APPROVED SOUTH OF THE 5 LINE. RECOMMEND BENDING UP A PIECE OF STEEL NEAR ELECTRIC SERVICE GEAR FOR UFFER GROUND.
Footing Inspection - Commercial Partial 8/24/2012 (11:00) 8/24/2012 at 12:00 AM 08/24/2012
Misc
Partial Correction
08/24/2012
ENTIRE PERIMETER FOOTING APPROVED EXCEPT 5 FEET AT NORTH WALL. TWO COLUMN PADS APPROVED
Footing Inspection - Commercial Partial 8/28/2012 (11:30) 8/28/2012 at 12:00 AM 08/28/2012
Misc
Partial Correction
08/28/2012
PERIMETER GRADE BEAM AND TWO PADS APPROVED
Underslab Plumbing Inspection - Commercial Partial 8/28/2012 8/28/2012 at 12:00 AM 08/28/2012
Misc
Partial Correction
08/28/2012
3 4 INCH LINES HEADING SOUTH AT EAST WEST AND MIDDLE OF BUILDING APPROVED.
Water Service Inspection Partial 8/28/2012 (3:00) 8/28/2012 at 12:00 AM 08/28/2012
Misc
Partial Correction
08/28/2012
COPPER APPRVED 100 FEET FROM BUILDING ALONG SIDE OF THE 6 INCH WATER.
Water Service Inspection Partial 8/29/2012 8/29/2012 at 12:00 AM 08/29/2012
Misc
Partial Correction
08/28/2012
COPPER APPRVED 100 FEET FROM BUILDING ALONG SIDE OF THE 6 INCH WATER. ADDITIONAL 100 FEET APPROVED.
Underslab Plumbing Inspection - Commercial Partial 8/29/2012 8/29/2012 at 12:00 AM 08/29/2012
Misc
Partial Correction
08/29/2012
BATH GROUPS ON EAST AND WEST WALLS APPROVED AND MAIN LINE LEAVING THE BUILDING
Footing Inspection - Commercial Partial 8/30/2012 (9:30) 8/30/2012 at 12:00 AM 08/30/2012
Misc
Partial Correction
08/28/2012
PERIMETER GRADE BEAM AND TWO PADS APPROVED TRANSFORMER PAD GRADE BEAM APPROVED
Underslab Electrical Inspection - Commercial Passed 8/31/2012 8/31/2012 at 12:00 AM 08/31/2012
Footing Inspection - Commercial Passed 9/10/2012 (3:00) 9/10/2012 at 12:00 AM 09/10/2012
Misc
Resolved
09/10/2012
PERIMETER GRADE BEAM AND TWO PADS APPROVED TRANSFORMER PAD GRADE BEAM APPROVED
Sewer Service Inspection Partial 9/20/2012 (1:00) 9/20/2012 at 12:00 AM 09/20/2012
Misc
Partial Correction
09/20/2012
APPROVED TO 30 FEET PAST 2ND CLEAN OUT
Water Service Inspection Partial 9/25/2012 (4:00) 9/26/2012 at 12:00 AM 09/26/2012
Misc
Partial Correction
08/29/2012
COPPER APPRVED TO VAULT
Sewer Service Inspection Passed 9/27/2012 (2:15) 9/28/2012 at 12:00 AM 09/28/2012
Misc
Partial Correction
09/20/2012
APPROVED TO 30 FEET PAST 2ND CLEAN OUT
Underground Electrical Inspection - Commercial Partial 10/1/2012 at 12:00 AM 10/01/2012
Misc
Corrective Action Required
10/01/2012
FOLLOWING INSPCTED- - TEMP UNDERGOUND SERVICE TO BUILDING- - UNDERGROUND ELECT FEED FROM SOUTH WEST CORNER BUILDING TO LIGHT POLES.
Underground Electrical Inspection - Commercial Partial 10/2/2012 10/2/2012 at 12:00 AM 10/02/2012
Misc
Partial Correction
10/02/2012
FOLLOWING INSPCTED- - TEMP UNDERGOUND SERVICE TO BUILDING- - UNDERGROUND ELECT FEED FROM SOUTH WEST CORNER BUILDING TO LIGHT POLES. -TWO FOR INCH APPROVED GOING TO TRANSFORMER PAD
Underground Electrical Inspection - Commercial Partial 10/3/2012 10/3/2012 at 12:00 AM 10/03/2012
Misc
Partial Correction
10/02/2012
FOLLOWING INSPCTED- - TEMP UNDERGOUND SERVICE TO BUILDING- - UNDERGROUND ELECT FEED FROM SOUTH WEST CORNER BUILDING TO LIGHT POLES. -TWO FOR INCH APPROVED GOING TO TRANSFORMER PAD
Misc
Corrective Action Required
10/03/2012
PROVIDE PHOTOS FOR PROOF OF DEPTH FOR PARKING LOT LIGHT POLE BASES
Water Service Inspection Passed 10/2/2012 (4:00) 10/2/2012 at 12:00 AM 10/03/2012
Misc
Resolved
10/03/2012
COPPER APPRVED TO VAULT
In-wall Inspection Failed 10/26/2012 10/26/2012 at 12:00 AM 10/26/2012
P305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS
Corrective Action Required
10/26/2012
PROTECT PLUMBING PIPES WITH PROTECTIVE SHIELD PLATES WHERE LESS THAN 1.5 INCHES FROM THE FACE OF THE STUD. PROTECT WHERE PIPES COME THROUGH THE FLOOR.
Misc
Corrective Action Required
10/26/2012
SECURE MC CABLE WITHIN 12 INCHES OF THE BOX.
Above Ceiling Inspection Partial 10/26/2012
Misc
Corrective Action Required
10/26/2012
OKAY TO INSTALL HARD LID. LEAVE OUT ACCESS TO SEE ACCESS PANELS IN THE DRAFT STOPS.
Above Ceiling Inspection Partial 10/26/2012
Misc
Corrective Action Required
10/26/2012
OKAY TO INSTALL HARD LID. LEAVE OUT ACCESS TO SEE ACCESS PANELS IN THE DRAFT STOPS.
In-wall Inspection Partial 10/30/2012 10/30/2012 at 12:00 AM 10/30/2012
P305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS
Resolved
10/30/2012
PROTECT PLUMBING PIPES WITH PROTECTIVE SHIELD PLATES WHERE LESS THAN 1.5 INCHES FROM THE FACE OF THE STUD. PROTECT WHERE PIPES COME THROUGH THE FLOOR.
Misc
Resolved
10/30/2012
SECURE MC CABLE WITHIN 12 INCHES OF THE BOX.
Misc
Partial Correction
10/30/2012
PERIMETER IN WALL APPROVED.
Sidewalk Inspection Passed 10/31/2012 at 10:00 AM 10/31/2012
Above Ceiling Inspection Partial 11/1/2012 11/1/2012 at 12:00 AM 11/02/2012
Misc
Partial Correction
11/02/2012
OKAY TO INSTALL HARD LID. LEAVE OUT ACCESS TO SEE ACCESS PANELS IN THE DRAFT STOPS. TOP ROUGH PLUMBING APPROVED AT EAST PATIENT AREA.
In-wall Inspection Not Ready 11/12/2012 11/12/2012 at 12:00 AM 11/12/2012
Misc
Partial Correction
10/30/2012
PERIMETER IN WALL APPROVED.
Misc
Corrective Action Required
11/12/2012
CALL WHEN ALL TRADES ARE COMPLETE. PLUMBING ALSO NEEDS TO HAVE BOCA PLATES
In-wall Inspection Not Ready 11/14/2012 at 12:00 AM 11/12/2012
Misc
Partial Correction
11/12/2012
PERIMETER IN WALL APPROVED.
P305.8 Protection against physical damage
Corrective Action Required
11/12/2012
PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1.5 inches (38 mm) from the nearest edge of the member, the pipe shall be protected by shield plates. Protective shield plates shall be a minimum of 0.062-inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched or bored, and shall extend a minimum of 2 inches (51 mm) above sole plates and below top plates. CALL FOR RE-INSPECTION WHEN ALL TRADES COMPLETE FOR IN WALL
In-wall Inspection Passed 11/15/2012 at 12:00 AM 11/15/2012
Misc
Resolved
11/15/2012
PERIMETER IN WALL APPROVED.
P305.8 Protection against physical damage
Resolved
11/15/2012
PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1.5 inches (38 mm) from the nearest edge of the member, the pipe shall be protected by shield plates. Protective shield plates shall be a minimum of 0.062-inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched or bored, and shall extend a minimum of 2 inches (51 mm) above sole plates and below top plates. CALL FOR RE-INSPECTION WHEN ALL TRADES COMPLETE FOR IN WALL
Electrical Service Inspection Passed 11/21/2012 (8:00 to 5:00) 11/21/2012 at 12:00 AM 11/21/2012
Above Ceiling Inspection Partial 12/5/2012 12/5/2012 at 12:00 AM 12/05/2012
Misc
Partial Correction
11/02/2012
OKAY TO INSTALL HARD LID. LEAVE OUT ACCESS TO SEE ACCESS PANELS IN THE DRAFT STOPS. TOP ROUGH PLUMBING APPROVED AT EAST PATIENT AREA. EXTERIOR SOFFITS APPROVED TO COVER
Above Ceiling Inspection Partial 12/7/2012 12/7/2012 at 12:00 AM 12/07/2012
Misc
Partial Correction
12/05/2012
OKAY TO INSTALL HARD LID. LEAVE OUT ACCESS TO SEE ACCESS PANELS IN THE DRAFT STOPS. TOP ROUGH PLUMBING APPROVED AT EAST PATIENT AREA. EXTERIOR SOFFITS APPROVED TO COVER VESTEBULE NORTH CANS APPROVED
Above Ceiling Inspection Partial 12/13/2012 12/13/2012 at 12:00 AM 12/13/2012
Misc
Partial Correction
12/07/2012
OKAY TO INSTALL HARD LID. LEAVE OUT ACCESS TO SEE ACCESS PANELS IN THE DRAFT STOPS. TOP ROUGH PLUMBING APPROVED AT EAST PATIENT AREA. EXTERIOR SOFFITS APPROVED TO COVER VESTEBULE NORTH CANS APPROVED EXAM ROOMS, TWO BATHROOMS MIDDLE AND SOUTH OF BUILDING OKAY TO DROP TILE
Above Ceiling Inspection Partial 12/19/2012 12/19/2012 at 12:00 AM 12/19/2012
Misc
Partial Correction
12/13/2012
ALL AREAS APPROVED TO DROP SOUTH OF WAITING AREA.
Above Ceiling Inspection Passed 12/31/2012 at 12:00 AM 12/31/2012
Misc
Resolved
12/31/2012
ALL AREAS APPROVED TO DROP SOUTH OF WAITING AREA.
Occupancy Inspection - Water Utilities Not Ready 2/8/2013 at 12:00 AM 02/08/2013
Occupancy Inspection - Planning Passed 2/25/2013 at 12:00 AM 02/25/2013
Corrective Action Required
02/25/2013
Separate sign permits shall be submitted to the Planning and Development Department for the monument and wall signs.
Corrective Action Required
02/25/2013
The Planning and Development Department reserves the ability to re-inspect all landscaping materials in the spring to ensure they have survived the winter.
Corrective Action Required
02/25/2013
Please note, all parking lot screening shrubs shall be allowed to grow to a minimum height of 2.5 feet.
Alarm Test Passed 2/25/2013 at 12:00 AM 02/25/2013
Occupancy Inspection - Fire Passed 2/25/2013 at 12:00 AM 02/25/2013
Occupancy Inspection - Codes Commercial Full C of O 2/25/2013 2/25/2013 at 12:00 AM 02/25/2013
Underground Electrical Inspection - Commercial Passed 03/04/2013
Misc
Resolved
03/04/2013
FOLLOWING INSPCTED- - TEMP UNDERGOUND SERVICE TO BUILDING- - UNDERGROUND ELECT FEED FROM SOUTH WEST CORNER BUILDING TO LIGHT POLES. -TWO FOR INCH APPROVED GOING TO TRANSFORMER PAD
Misc
Resolved
03/04/2013
PROVIDE PHOTOS FOR PROOF OF DEPTH FOR PARKING LOT LIGHT POLE BASES
Underslab Plumbing Inspection - Commercial Passed 03/04/2013
Misc
Partial Correction
08/29/2012
BATH GROUPS ON EAST AND WEST WALLS APPROVED AND MAIN LINE LEAVING THE BUILDING
Occupancy Inspection - Engineering Passed 2/25/2013 at 12:00 AM 03/06/2013
Documents & Images
Date Uploaded File Type Document Name
06/26/2012 Letter Plan Review Conditions
07/30/2012 Letter Building Permit
07/30/2012 Letter Plan Review Conditions
08/22/2012 Letter Inspection Summary
08/24/2012 Letter Inspection Summary
08/28/2012 Letter Inspection Summary
08/29/2012 Letter Inspection Summary
08/30/2012 Letter Inspection Summary
08/31/2012 Letter Inspection Summary
09/10/2012 Letter Inspection Summary
09/20/2012 Letter Inspection Summary
09/26/2012 Letter Inspection Summary
10/01/2012 Letter Inspection Summary
10/02/2012 Letter Inspection Summary
10/26/2012 Letter Inspection Summary
10/30/2012 Letter Inspection Summary
11/02/2012 Letter Inspection Summary
11/12/2012 Letter Inspection Summary
11/15/2012 Letter Inspection Summary
11/21/2012 Letter Inspection Summary
12/05/2012 Letter Inspection Summary
12/07/2012 Letter Inspection Summary
12/13/2012 Letter Inspection Summary
12/19/2012 Letter Inspection Summary
12/31/2012 Letter Inspection Summary
02/25/2013 Letter Fire Loss Reduction Form
02/25/2013 Letter Field Certificate of Occupancy
02/25/2013 Letter Planning Inspection Summary
03/04/2013 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home