Permit Application Status

PRCOM20110115


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110115
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
NEW TENANT FINISH
RETAIL CLOTHING STORE - SPACE PREVIOUSLY UNOCCUPIED
02/04/2011
03/31/2011
08/23/2011
05/05/2011
Locations
Contacts
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
KCG Architects, Address:21 Grand Ave Suite #201  
PYATT MECHANICAL INC, Address:32205 E BURGESS RD, Phone:(816) 650-5270  
HORIZON RETAIL CONSTRUCTION INC, Address:9999 E EXPLORATION CT, Phone:(262) 638-6000  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 04/12/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
04/12/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received April 8, 2011.
Installation acceptance testing
Corrective Action Required
04/12/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule testing.
Alarm Plan Review Released for Construction 04/11/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
04/11/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received April 4, 2011.
Misc
Corrective Action Required
04/11/2011

Duct detection shall be supervisory notification only and shall not activate interior horn/strobes or be transmitted to the central station as a fire alarm. To be verified at inspection. Verified at inspection.
Installation acceptance testing
Corrective Action Required
04/11/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test.
License Tax Codes Approved 02/16/2011 03/31/2011
Codes Admin
Internal Plan Review (Res) Approved 03/01/2011
Joe Frogge
Fire Plan Review Approved 03/03/2011 03/01/2011
Jim Eden
Misc
Resolved
03/01/2011

The shell building was approved with a horizontal exit corridor. Submit revised plans for exiting from the shell building.
Construction documents for fire alarm systems
Corrective Action Required
02/24/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Misc
Resolved
03/01/2011

2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action required: Provide exterior emergency egress lighting if not already provided as the shell.
Installation acceptance testing
Corrective Action Required
02/24/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Fire protection systems shall be tested and operable prior to scheduling an occupancy testing. Testing shall take place before or after regular business hours for the neighboring tenants. cal (816) 969-1300 to schedule a test.
Fire-resistant-rated construction - Maintenance
Resolved
03/01/2011

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Action required.Provide information on the rated walls and door assembly for this space.
Address numbers required
Resolved
03/01/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required:The address shall be posted obn all exterior doors and doors to interior public corridors.
Building Plan Review Approved 03/03/2011 02/25/2011
Joe Frogge
Misc
Resolved
02/25/2011

2006 IBC 1022.2 Separation. The separation between buildings or refuge areas connected by a horizontal exit shall be provided by a fire wall complying with Section 705 or a fire barrier complying with Section 706 and having a fire-resistance rating of not less than 2 hours. Opening protectives in horizontal exit walls shall also comply with Section 715. The horizontal exit separation shall extend vertically through all levels of the building unless floor assemblies have a fire-resistance rating of not less than 2 hours with no unprotected openings. Exception: A fire-resistance rating is not required at horizontal exits between a building area and an above-grade pedestrian walkway constructed in accordance with Section 3104, provided that the distance between connected buildings is more than 20 feet (6096 mm). Horizontal exit walls constructed as fire barriers shall be continuous from exterior wall to exterior wall so as to divide completely the floor served by the horizontal exit. Door exiting storage room into adjacent tenant space appears to be a horizontal exit as defined in Chapter 10. Provide additional information as to how this exit qualifies as an emergency egress. Note: if this is determined to be a horizontal exit more review comments will become applicable; i.e. u.l. for wall, rated door, penetrations, etc.
Misc
Resolved
02/25/2011

2006 IBC Section 1004 Occupant Load Calculated occupant load on cover sheet has incorrect conclusions. "Rounding down" is not appropriate in this instance. Update and resubmit.
Misc
Corrective Action Required
02/24/2011

Submittal Requirements: General contractor/permit holder and MEP subs must be listed on permit prior to issuance.
Bldg - Accessibility - Where required
Resolved
02/25/2011

2006 IBC 1103.1 - Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Resubmittal shall show how accessibility will be maintained. Specifically, service facilities per Section 1109.12.
Misc
Resolved
02/25/2011

2006 IMC 403.2 Outdoor air required. The minimum ventilation rate of outdoor air shall be determined in acordance with Section 403.3. Resubmittal shall detail means of supplying minimum outside air per Table 403.3 as providing means for relief air.
Misc
Resolved
02/25/2011

2006 IMC 603.10 Supports. Ducts shall be supported with approved hangers at intervals not exceeding 10 feet or by other approved duct support systems designed in accordance with the IBC. Flexible ducts shall be supported in accordance with the manufacturer's installation instructions. Flex duct support detail shows 1" wide hangers. Most manufacturer's require 1-1/2" wide support. Resubmittal not required. This may be verified during inspection process.
Misc
Resolved
02/25/2011

2006 IPC. Cover sheet states UPC as our plumbing code. Please correct.
Internal Plan Review (Res) Rejected 02/16/2011 02/24/2011
Joe Frogge
Building Plan Review Rejected 02/16/2011 02/16/2011
Joe Frogge
Misc
Corrective Action Required
02/08/2011

2006 IBC 1022.2 Separation. The separation between buildings or refuge areas connected by a horizontal exit shall be provided by a fire wall complying with Section 705 or a fire barrier complying with Section 706 and having a fire-resistance rating of not less than 2 hours. Opening protectives in horizontal exit walls shall also comply with Section 715. The horizontal exit separation shall extend vertically through all levels of the building unless floor assemblies have a fire-resistance rating of not less than 2 hours with no unprotected openings. Exception: A fire-resistance rating is not required at horizontal exits between a building area and an above-grade pedestrian walkway constructed in accordance with Section 3104, provided that the distance between connected buildings is more than 20 feet (6096 mm). Horizontal exit walls constructed as fire barriers shall be continuous from exterior wall to exterior wall so as to divide completely the floor served by the horizontal exit. Door exiting storage room into adjacent tenant space appears to be a horizontal exit as defined in Chapter 10. Provide additional information as to how this exit qualifies as an emergency egress. Note: if this is determined to be a horizontal exit more review comments will become applicable; i.e. u.l. for wall, rated door, penetrations, etc.
Misc
Corrective Action Required
02/08/2011

2006 IBC Section 1004 Occupant Load Calculated occupant load on cover sheet has incorrect conclusions. "Rounding down" is not appropriate in this instance. Update and resubmit.
Misc
Corrective Action Required
02/08/2011

Submittal Requirements: General contractor/permit holder and MEP subs must be listed on permit prior to issuance.
Bldg - Accessibility - Where required
Corrective Action Required
02/08/2011

2006 IBC 1103.1 - Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Resubmittal shall show how accessibility will be maintained. Specifically, service facilities per Section 1109.12.
Misc
Corrective Action Required
02/08/2011

2006 IMC 403.2 Outdoor air required. The minimum ventilation rate of outdoor air shall be determined in acordance with Section 403.3. Resubmittal shall detail means of supplying minimum outside air per Table 403.3 as providing means for relief air.
Misc
Corrective Action Required
02/08/2011

2006 IMC 603.10 Supports. Ducts shall be supported with approved hangers at intervals not exceeding 10 feet or by other approved duct support systems designed in accordance with the IBC. Flexible ducts shall be supported in accordance with the manufacturer's installation instructions. Flex duct support detail shows 1" wide hangers. Most manufacturer's require 1-1/2" wide support. Resubmittal not required. This may be verified during inspection process.
Misc
Corrective Action Required
02/08/2011

2006 IPC. Cover sheet states UPC as our plumbing code. Please correct.
Fire Plan Review Rejected 02/16/2011 02/11/2011
Jim Eden
Misc
Corrective Action Required
02/11/2011

The shell building was approved with a horizontal exit corridor. Submit revised plans for exiting from the shell building.
Construction documents for fire alarm systems
Corrective Action Required
02/11/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Construction documents for fire alarm systems
Corrective Action Required
02/11/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Misc
Corrective Action Required
02/11/2011

2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action required: Provide exterior emergency egress lighting if not already provided as the shell.
Installation acceptance testing
Corrective Action Required
02/11/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Fire protection systems shall be tested and operable prior to scheduling an occupancy testing. Testing shall take place before or after regular business hours for the neighboring tenants. cal (816) 969-1300 to schedule a test.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
02/11/2011

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Action required.Provide information on the rated walls and door assembly for this space.
Address numbers required
Corrective Action Required
02/11/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required:The address shall be posted obn all exterior doors and doors to interior public corridors.
Zoning Review Approved 02/16/2011 02/04/2011
Hector Soto Jr.
Historical Preservation Review Approved 02/16/2011 02/04/2011
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,147.36 $1,147.36 Paid 03/31/2011
8331507-Sewer Connection Fee $180.00 $180.00 Paid 03/31/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 4/5/2011 4/5/2011 at 12:00 AM 04/05/2011
All Rough Inspection - Commercial Partial 4/11/2011 at 12:00 AM 04/11/2011
Misc
Corrective Action Required
04/11/2011
- SHEET E2.0, LINE D - MISSING OUTLET IN SOFFIT.
Misc
Partial Correction
04/11/2011
- OKAY TO SHEETROCK EXCEPT AT LINE D SOFFIT
All Rough Inspection - Commercial Passed 4/13/2011 at 12:00 AM 04/13/2011
Misc
Resolved
04/13/2011
Misc
Resolved
04/13/2011
- OKAY TO SHEETROCK EXCEPT AT LINE D SOFFIT
Electrical Service Inspection Passed 4/27/2011 at 12:00 AM 04/27/2011
Gas Piping Inspection - Commercial Partial 4/29/2011 at 12:00 AM 04/29/2011
Misc
Partial Correction
04/29/2011
SUPPORTS OF ROOFTOP PIPING IN PROGRESS
Gas Service Inspection - Commercial Failed 4/29/2011 at 12:00 AM 04/29/2011
Misc
Corrective Action Required
04/29/2011
GAS PIPING PRESSURE TEST DECREASED DURING MONITORING PERIOD
Gas Piping Inspection - Commercial Partial 5/2/2011 4/29/2011 at 12:00 AM 04/29/2011
Misc
Partial Correction
04/29/2011
SUPPORTS OF ROOFTOP PIPING IN PROGRESS
Misc
Corrective Action Required
04/29/2011
EXPOSED PIPING TO BE PAINTED BEFORE FINAL INSPECTION
Gas Service Inspection - Commercial Passed 4/29/2011 at 12:00 AM 04/29/2011
Misc
Resolved
04/29/2011
GAS PIPING PRESSURE TEST DECREASED DURING MONITORING PERIOD
Above Ceiling Inspection Passed 5/2/2011 5/2/2011 at 12:00 AM 05/02/2011
Alarm Test Passed 5/3/2011 at 12:00 AM 05/03/2011
Misc
Corrective Action Required
05/03/2011
Front of store (girls clothing) light soffit area needs additional sprinkler heads installed.
Sprinkler - Flow Test Passed 5/3/2011 at 12:00 AM 05/03/2011
Occupancy Inspection - Fire Temporary C of O 5/3/2011 at 12:00 AM 05/03/2011
Gas Piping Inspection - Commercial Passed 5/3/2011 at 12:00 AM 05/03/2011
Misc
Resolved
05/03/2011
SUPPORTS OF ROOFTOP PIPING IN PROGRESS
Misc
Resolved
05/03/2011
EXPOSED PIPING TO BE PAINTED BEFORE FINAL INSPECTION
Occupancy Inspection - Codes Commercial Partial 5/3/2011 at 12:00 AM 05/03/2011
Misc
Corrective Action Required
05/03/2011
GAS SERVICE ENTRY ADDRESS MARKING TO BE COMPLETED PER DISCUSSION
Misc
Corrective Action Required
05/03/2011
CIRCUIT BREAKER POSITION NUMBERS AT HV ELECTRICAL PANEL NOT NUMBERED
Misc
Corrective Action Required
05/03/2011
"NO SMOKING" SIGN TO AFFIXED TO PUBLIC ENTRY DOOR
Misc
Corrective Action Required
05/03/2011
ROOFTOP FINAL CLEANUP TO BE VERIFIED
Occupancy Inspection - Fire Passed 5/4/2011 at 12:00 AM 05/04/2011
Occupancy Inspection - Codes Commercial Failed 5/5/2011 at 12:00 AM 05/05/2011
Misc
Resolved
05/05/2011
GAS SERVICE ENTRY ADDRESS MARKING TO BE COMPLETED PER DISCUSSION
Misc
Resolved
05/05/2011
CIRCUIT BREAKER POSITION NUMBERS AT HV ELECTRICAL PANEL NOT NUMBERED
Misc
Resolved
05/05/2011
"NO SMOKING" SIGN TO AFFIXED TO PUBLIC ENTRY DOOR
Misc
Corrective Action Required
05/03/2011
ROOFTOP FINAL CLEANUP TO BE VERIFIED
Occupancy Inspection - Codes Commercial Full C of O 5/5/2011 at 12:00 AM 05/05/2011
Misc
Resolved
05/05/2011
ROOFTOP FINAL CLEANUP TO BE VERIFIED
Documents & Images
Date Uploaded File Type Document Name
02/16/2011 Photograph Plan Review Conditions
03/08/2011 Letter Fire Building Plan Review
03/31/2011 Letter Plan Review Conditions
03/31/2011 Letter Plan Review Conditions
03/31/2011 Letter Building Permit
04/05/2011 Letter Inspection Summary
04/11/2011 Letter Fire (Alarm) Plan Review Notice
04/11/2011 Letter Inspection Summary
04/12/2011 Letter Fire (Sprinkler) Plan Review.pdf
04/13/2011 Letter Inspection Summary
04/13/2011 Letter Inspection Summary
04/27/2011 Letter Inspection Summary
04/29/2011 Letter Inspection Summary
04/29/2011 Letter Inspection Summary
05/02/2011 Letter Inspection Summary
05/03/2011 Letter Fire Loss Reduction Form
05/03/2011 Letter Inspection Summary
05/04/2011 Letter Fire Loss Reduction Form
05/05/2011 Letter Inspection Summary
05/05/2011 Letter Final Certificate of Occupancy
05/06/2011 Letter Final Certificate of Occupancy
07/02/2013 Letter Plan Review Conditions
07/02/2013 Letter Plan Review Conditions
07/02/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home