Permit Application Status

PRCOM20100324


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20100324
Building Permit - Commercial
Certificate of Occupancy
LBP IV LLC
NEW TENANT FINISH
Tenant finish
12/21/2010
01/14/2011
07/04/2011
02/28/2011
Locations
Contacts
CAPITAL CONSTRUCTION SERVICES LLC, Address:2642 NE HAGAN RD, Phone:(816) 875-0018  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
BLUE SPRINGS ELECTRICAL SERVICE, Address:3402 LAKE SHORE DR, Phone:(816) 224-9911  
CLEARLINE PLUMBING LLC, Address:14922 KNORPP RD, Phone:(816) 524-4449  
LBP IV LLC, Address:3215 NE CARNEGIE DR STE 200  
LBP IV LLC, Address:3170 NE CARNEGIE DR STE 400  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 01/14/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
01/14/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received 12/31/2010. Revised plans recieved 01/11/2011
Installation acceptance testing
Corrective Action Required
01/14/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule hydrostatic and flow tests.
Misc
Corrective Action Required
01/14/2011

Determine the method of storage to be used in the warehouse and the commodity to be stored. Provide fire protection in accordance with IFC Chapter 23, 2006 Edition and NFPA 13. Provide revised plans if needed. Revised rack plans submitted January 11, 2011.
Internal Plan Review (Res) Approved 01/13/2011
Mike Weisenborn
Fire Plan Review Approved 01/12/2011 01/13/2011
Brian Austerman
Misc
Corrective Action Required
01/05/2011

Fire Department 2006 IFC- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED- DUCT DETECTORS SHALL INITIATE A SUPERVISORY ALARM, VERIFIED AT INSPECTION
Construction documents - Fire protection systems
Corrective Action Required
01/05/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED- PROVIDE CONSTRUCTION DOCUMENTS FOR MODIFICATIONS TO SPRINKLER/STANDPIPE SYSTEM TO FIRE DEPARTMENT FOR APPROVAL
Construction documents for fire alarm systems
Corrective Action Required
01/05/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED- PROVIDE CONSTRUCTION DOCUMENTS FOR ALARM SYSTEM MODIFICATIONS TO FIRE DEPARTMENT FOR APPROVAL
Alarm testing.
Corrective Action Required
01/05/2011

2006 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. ACTION REQUIRED- CALL 969-1316 TO SCHEDULE ALARM TESTING PRIOR TO FINAL
Misc
Corrective Action Required
01/05/2011

Fire Department 2006 IFC- 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits ACTION REQUIRED- PROVIDE EXTERIOR REMOTE HEADS FOR EXIT LANDING ILLUMINATION ON EMERGENCY POWER, VERIFIED AT INSPECTION
Misc
Corrective Action Required
01/05/2011

Fire Department 2006 IFC-2301.3 Construction documents. At the time of building permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International Building Code, the storage permit submittal shall include the information specified in this section. Following approval of the plans, a copy of the approved plans shall be maintained on the premises in an approved location. The plans shall include the following: 1. Floor plan of the building showing locations and dimensions of high-piled storage areas. 2. Usable storage height for each storage area. 3. Number of tiers within each rack, if applicable. 4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 5. Aisle dimensions between each storage array. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 2303. 8. Location of commodities which are banded or encapsulated. 9. Location of required fire department access doors. 10. Type of fire suppression and fire detection systems. 11. Location of valves controlling the water supply of ceiling and in-rack sprinklers. 12. Type, location and specifications of smoke removal and curtain board systems. 13. Dimension and location of transverse and longitudinal flue spaces. 14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area shall be provided at the time of permit, when required by the fire code official. ACTION REQUIRED- SHOW WHAT IS BEING STORED AND HOW, NO STORAGE ALLOWED OVER 12' UNLESS PROTECTED BY IN RACK SUPPRESSION SYSTEM. ALSO DEPENDING ON COMMODITY CLASS THERE MAY BE A REQUIREMENT FOR STANDPIPES AND SMOKE REMOVAL PER CHAPTER 23. PROVIDE DETAIL RESOLVED ON RESUBMITTAL, VERIFIED AT INSPECTION
Sprinkler Plan Review Rejected 01/06/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
01/06/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received 12/31/2010. Revised plans received 01/11/2011
Installation acceptance testing
Corrective Action Required
01/06/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule hydrostatic and flow tests.
Misc
Corrective Action Required
01/06/2011

Determine the method of storage to be used in the warehouse and the commodity to be stored. Provide fire protection in accordance with IFC Chapter 23, 2006 Edition and NFPA 13. Provide revised plans if needed. Revised rack plans submitted January 11, 2011.
Internal Plan Review (Res) Rejected 01/05/2011 01/05/2011
Mike Weisenborn
Building Plan Review Approved 01/05/2011 01/04/2011
Mike Weisenborn
Zoning Review Approved 01/05/2011 01/04/2011
Mike Weisenborn
License Tax Codes Approved 01/05/2011 01/04/2011
Mike Weisenborn
Fire Plan Review Rejected 01/05/2011 12/28/2010
Brian Austerman
Misc
Corrective Action Required
12/28/2010

Fire Department 2006 IFC- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED- DUCT DETECTORS SHALL INITIATE A SUPERVISORY ALARM, VERIFIED AT INSPECTION
Construction documents - Fire protection systems
Corrective Action Required
12/28/2010

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED- PROVIDE CONSTRUCTION DOCUMENTS FOR MODIFICATIONS TO SPRINKLER/STANDPIPE SYSTEM TO FIRE DEPARTMENT FOR APPROVAL
Construction documents for fire alarm systems
Corrective Action Required
12/28/2010

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED- PROVIDE CONSTRUCTION DOCUMENTS FOR ALARM SYSTEM MODIFICATIONS TO FIRE DEPARTMENT FOR APPROVAL
Alarm testing.
Corrective Action Required
12/28/2010

2006 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. ACTION REQUIRED- CALL 969-1316 TO SCHEDULE ALARM TESTING PRIOR TO FINAL
Misc
Corrective Action Required
12/28/2010

Fire Department 2006 IFC- 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits ACTION REQUIRED- PROVIDE EXTERIOR REMOTE HEADS FOR EXIT LANDING ILLUMINATION ON EMERGENCY POWER, VERIFIED AT INSPECTION
Misc
Corrective Action Required
12/28/2010

Fire Department 2006 IFC-2301.3 Construction documents. At the time of building permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International Building Code, the storage permit submittal shall include the information specified in this section. Following approval of the plans, a copy of the approved plans shall be maintained on the premises in an approved location. The plans shall include the following: 1. Floor plan of the building showing locations and dimensions of high-piled storage areas. 2. Usable storage height for each storage area. 3. Number of tiers within each rack, if applicable. 4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 5. Aisle dimensions between each storage array. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 2303. 8. Location of commodities which are banded or encapsulated. 9. Location of required fire department access doors. 10. Type of fire suppression and fire detection systems. 11. Location of valves controlling the water supply of ceiling and in-rack sprinklers. 12. Type, location and specifications of smoke removal and curtain board systems. 13. Dimension and location of transverse and longitudinal flue spaces. 14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area shall be provided at the time of permit, when required by the fire code official. ACTION REQUIRED- SHOW WHAT IS BEING STORED AND HOW, NO STORAGE ALLOWED OVER 12' UNLESS PROTECTED BY IN RACK SUPPRESSION SYSTEM. ALSO DEPENDING ON COMMODITY CLASS THERE MAY BE A REQUIREMENT FOR STANDPIPES AND SMOKE REMOVAL PER CHAPTER 23. PROVIDE DETAIL
Historical Preservation Review Approved 01/05/2011 12/21/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $993.50 $993.50 Paid 01/14/2011
8331507-Sewer Connection Fee $420.00 $420.00 Paid 01/14/2011
8331506-EFHB Maybrook, Full $596.54 $596.54 Paid 01/14/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 2/15/2011 at 12:00 AM 01/18/2011
Above Ceiling Inspection Passed 2/8/2011 at 12:00 AM 02/08/2011
Gas Service Inspection - Commercial Passed 2/15/2011 at 12:00 AM 02/15/2011
Gas Piping Inspection - Commercial Passed 2/15/2011 at 12:00 AM 02/15/2011
Sprinkler - Hydrostatic Test Passed 2/16/2011 at 12:00 AM 02/16/2011
Alarm Test Passed 2/17/2011 at 12:00 AM 02/17/2011
Sprinkler - Flow Test Passed 2/17/2011 at 12:00 AM 02/17/2011
Occupancy Inspection - Fire Passed 02/17/2011
Electrical Service Inspection Passed 2/8/2011 at 12:00 AM 02/17/2011
Misc
Resolved
02/17/2011
TABLE 310.16 -DERIVED PHASED CONDUCTORS-1/0 ALUM ONLY OK FOR MAX. 125 AMP BREAKER AS ALLOWD PER 240.4. THIS IS DOWNSTREAM OF SERVICE *200 AMP SERVICE OK FOR RELEASE
Occupancy Inspection - Codes Commercial Temporary C of O 2/8/2011 at 12:00 AM 02/17/2011
Misc
Corrective Action Required
02/17/2011
ELECTRICAL DEFICIENCIES: -INSTALL 15 AMP HACR BREAKER FOR A/C UNIT -INSTALL 30 AMP RATED INSTANT WATER HEATER RECEPTACLE UNDER CONFERENCE RM SINK
Misc
Corrective Action Required
02/17/2011
-PROVIDE ADA SINK CABINET PER DETAIL 5/A2 IN RM 104
Misc
Corrective Action Required
02/17/2011
COMPLETE PARTITION IN MEN RESTROOM
Misc
Corrective Action Required
02/17/2011
SUPPORT WATER LINES ABOVE STORAGE AREA AT INTERVAL NO MORE THAN 6 FT
Occupancy Inspection - Codes Commercial Full C of O 2/28/2011 2/28/2011 at 12:00 AM 02/28/2011
Misc
Resolved
02/28/2011
ELECTRICAL DEFICIENCIES: -INSTALL 15 AMP HACR BREAKER FOR A/C UNIT -INSTALL 30 AMP RATED INSTANT WATER HEATER RECEPTACLE UNDER CONFERENCE RM SINK
Misc
Resolved
02/28/2011
-PROVIDE ADA SINK CABINET PER DETAIL 5/A2 IN RM 104
Misc
Resolved
02/28/2011
COMPLETE PARTITION IN MEN RESTROOM
Misc
Resolved
02/28/2011
SUPPORT WATER LINES ABOVE STORAGE AREA AT INTERVAL NO MORE THAN 6 FT
Documents & Images
Date Uploaded File Type Document Name
01/05/2011 Letter Plan Review Conditions
01/06/2011 Letter Fire (Sprinkler) Plan Review
01/14/2011 Letter Plan Review Conditions
01/14/2011 Letter Building Permit
01/18/2011 Letter Inspection Summary
02/01/2011 Letter Inspection Summary
02/08/2011 Letter Inspection Summary
02/15/2011 Letter Inspection Summary
02/17/2011 Letter Fire Loss Reduction Form
02/17/2011 Letter Temporary Certificate of Occupancy
02/28/2011 Letter Field Certificate of Occupancy
03/01/2011 Letter Final Certificate of Occupancy
06/27/2013 Letter Plan Review Conditions
06/27/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home