Review Type |
Outcome |
Est. Completion Date |
Completed |
Building Codes Review
|
No Comments
|
06/20/2023
|
06/13/2023
|
|
Joe Frogge
|
|
Miscellaneous Correction
Light pole base must be at least 36" below grade to protect from frost.
6/12/23 - not addressed.
|
|
|
Planning Review
|
No Comments
|
06/20/2023
|
06/13/2023
|
|
Mike Weisenborn
|
|
|
Fire Review
|
Approved with Conditions
|
06/20/2023
|
06/13/2023
|
|
Mike Weisenborn
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only-The tenant finish use (occupancy type) may require additional fire protection, or fire area separation per IBC chapter 7.
|
|
Imposed Loads
Corrective Action Required
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Confirm the drive aisles of the parking lot will be capable of supporting 75,000-pounds for protection of this lot and any proposed building to the south.
|
|
Fire Lanes - Marking
Corrective Action Required
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Fire lane marking on this lot shall be provided when the lot to the south is developed.
|
|
|
Engineering Review
|
Approved with Conditions
|
06/20/2023
|
06/13/2023
|
|
Mike Weisenborn
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $59,980.02.
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
|
Traffic Review
|
No Comments
|
06/20/2023
|
06/13/2023
|
|
Mike Weisenborn
|
|
|
Traffic Review
|
No Comments
|
06/12/2023
|
06/12/2023
|
|
Dawn Bell
|
|
|
Building Codes Review
|
Corrections
|
06/12/2023
|
06/12/2023
|
|
Joe Frogge
|
|
Miscellaneous Correction
Corrective Action Required
Light pole base must be at least 36" below grade to protect from frost.
6/12/23 - not addressed.
|
|
|
Planning Review
|
No Comments
|
06/12/2023
|
06/09/2023
|
|
Hector Soto Jr.
|
|
Corrective Action Required
|
|
|
Engineering Review
|
Approved with Conditions
|
06/12/2023
|
06/09/2023
|
|
Susan Nelson, P.E.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $59,980.02.
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
|
Fire Review
|
Approved with Conditions
|
06/12/2023
|
06/06/2023
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only-The tenant finish use (occupancy type) may require additional fire protection, or fire area separation per IBC chapter 7.
|
|
Imposed Loads
Corrective Action Required
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Confirm the drive aisles of the parking lot will be capable of supporting 75,000-pounds for protection of this lot and any proposed building to the south.
|
|
Fire Lanes - Marking
Corrective Action Required
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Fire lane marking on this lot shall be provided when the lot to the south is developed.
|
|
|
Traffic Review
|
No Comments
|
05/22/2023
|
05/24/2023
|
|
Susan Barry, P.E.
|
|
|
Fire Review
|
Corrections
|
05/22/2023
|
05/22/2023
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only-The tenant finish use (occupancy type) may require additional fire protection, or fire area separation per IBC chapter 7.
|
|
Imposed Loads
Corrective Action Required
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Confirm the drive aisles of the parking lot will be capable of supporting 75,000-pounds for protection of this lot and any proposed building to the south.
|
|
Fire Lanes - Marking
Corrective Action Required
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Fire lane marking on this lot shall be provided when the lot to the south is developed.
|
|
|
Engineering Review
|
Corrections
|
05/22/2022
|
05/21/2023
|
|
Susan Nelson, P.E.
|
|
Corrective Action Required
General
- Please provide Engineer’s Estimate of Probable Costs.
- Show and label all existing utilities and easements.
|
|
Corrective Action Required
Sheet C3.0
- Show existing sanitary sewer continuing west in the NW corner. Show on all sheets.
|
|
Corrective Action Required
Sheet C4.0/C5.0
- Is there another proposed storm line southeast from MH at the edge of Lot 4? This line is not shown in Sheet C6.0
- Trash enclosure concrete pad should extend 30’ out from the doors.
|
|
Corrective Action Required
Sheet C6.0
- Please show HGL on storm lines.
- Graphically show with hatching and call out the compacted backfill 18” min. over the top of the pipe.
|
|
Corrective Action Required
Sheet C12.0
- On the concrete detail, show that the aggregate base and compacted subgrade extends 12” min. behind the back of curb.
- Please provide a detail of the temporary asphalt curb.
|
|
Corrective Action Required
Sheet C13.0
- Note: Only ornamental tree varieties are allowed within public easements.
|
|
|
Planning Review
|
Corrections
|
05/22/2023
|
05/19/2023
|
|
Hector Soto Jr.
|
|
Corrective Action Required
SITE DATA TABLE.
- List the Floor Area Ratio (FAR) for the proposed building.
- List both the number of required parking spaces (based on use and building square footage) and proposed parking spaces.
- The table indicates that 41 total parking spaces are provided, but the plan appears to show construction of a total of 59 spaces. Revise.
- Label the proposed square footage of impervious coverage.
|
|
Corrective Action Required
EASEMENTS. Show and label the limits of both the 20' U/E and 38' S/E (Sanitary Easement) that run through the property.
|
|
Corrective Action Required
CURBING. C-1 curbing is shown to be used on either side of the drive aisle located south of the proposed building. The City's development ordinance requires all parking lot boundaries to be constructed of CG-1 curbing. Revise.
|
|
Corrective Action Required
STREETS/SIDEWALKS.
- Label the Lowenstein Dr ROW width.
- Show and label the existing sidewalk along Lowenstein Dr, including its width.
|
|
Corrective Action Required
TRASH ENCLOSURE PAD. Trash enclosure areas shall be improved with a Portland cement concrete pad and a Portland cement concrete approach 30 feet in length, measured from the enclosure opening. The pad and approach shall be improved with a minimum six inches of full depth unreinforced Portland cement concrete constructed on a sub-grade of four inches of granular base course.
|
|
Corrective Action Required
BUILDING SETBACKS. Show and label the platted 30' building line along the Lowenstein Dr frontage.
|
|
Corrective Action Required
BUILDING.
- The building footprint on the civil plans does not match those depicted on the architectural plans. Revise to match, including the building's projections.
- The west building elevation is a flat wall plane, save for bumpouts at the building corners. To comply with the UDO requirements for four-sided architecture, provide an additional bumpout along the west facade to provide additional relief for the long expanse of wall to match the other elevations.
|
|
Corrective Action Required
BUILDING MATERIAL. The building material labeled WD-1 on the elevations are noted as being wood/fiber cement siding. Please note that real wood is a conditional material under City ordinance, which may only be permitted with City Council approval via a public hearing. However, wood composite or fiber cement siding with a wood appearance is a material allowed by right. Remove the reference to wood or clarify the material as being an engineered wood product.
|
|
Corrective Action Required
RTU SCREENING. Dash-in the location of RTUs on the building elevations for staff to review for compliance with the requirement that they will be fully screened from view on all sides by the building parapet walls being built to a height at least equal to the height of the mechanical units. Please take into account the additional height from the curbs on which the RTUs will sit.
|
|
|
Building Codes Review
|
Corrections
|
05/22/2023
|
05/18/2023
|
|
Joe Frogge
|
|
Miscellaneous Correction
Corrective Action Required
Light pole base must be at least 36" below grade to protect from frost.
|
|
|