PL2020375
The Ridge at Winterset Summit - Water Line
Engineering Plan Review
Engineering Plan Review
Approved
12/15/2020
REORGANIZED SCHOOL DIST NO 7
Locations
Contacts
REORGANIZED SCHOOL DIST NO 7, Address:600 SE MILLER ST  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
SKELSEY KEVIN R & MOLLY E, Address:2720 SW GRAY LANE  
CUNDIFF JON D & VICKY L, Address:701 SW WINTERWALK LN  
DAVIS TOM & MARY, Address:178 SW ROOSEVELT RDG  
PACE FRANK & KRISTINE, Address:2408 SW WINTERCREEK CT  
VEACH BRETT & ALISON, Address:185 SW WINTER RD  
WINTERSET COMMUNITY ASSOCIATION INC, Address:2505 SW WINTERCREEK DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Record Drawings Review No Comments 02/04/2022 02/02/2022
Gene Williams, P.E.
Engineering Review No Comments 01/25/2021 01/25/2021
Gene Williams, P.E.
Traffic Review No Comments 01/25/2021 01/19/2021
Michael Park
Engineering Review Corrections 12/29/2020 12/29/2020
Gene Williams, P.E.
Corrective Action Required
12/29/2020

The City does not desire the water main to be extended all the way around the cul-de-sac as shown. Lot 1604 has access to the public water main across the street, and not across the cul-de-sac. Please revise.
Corrective Action Required
12/29/2020

As drawn, it appears bends will be required to manage the excessive bends in the vertical axis. Only 1 degree of deflection is allowed within the fitting itself, with zero deflection within the pipe. This equates to an approximate 1200 foot radius of bend minimum, based on a 20 foot stick of pipe. Please review and revise the plans as appropriate. It would appear that with variable depth of bury, the water main might be able to be installed without vertical bends.
Corrective Action Required
12/29/2020

Where pipe is to be installed in fill, please show on the profile view in graphical format how fill will be installed prior to trenching and installation. This is a new requirement for all pipes, whether water main, sanitary sewer, or storm lines.
Corrective Action Required
12/29/2020

A trenching and backfill detail is missing. Please be aware that the aggregate requirements on the top of the pipe have changed to 12 inches rather than 6 inches.
Traffic Review No Comments 12/29/2020 12/18/2020
Michael Park
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home