PL2022372
Lee's Summit High School - Robotics Facility
Commercial Final Development Plan
Commercial Final Development Plan
Approved
10/21/2022
LEES SUMMIT SCHOOL DIST R 7
Locations
Contacts
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
MULTISTUDIO, Address:4200 PENNSYLVANIA AVE  
KAW VALLEY ENGINEERING INC, Address:14700 W 114TH TERR, Phone:(913) 894-5150  
Reviews
Review Type Outcome Est. Completion Date Completed
Planning Review No Comments 11/18/2022 11/17/2022
Hector Soto Jr.
Engineering Review Approved with Conditions 11/18/2022 11/17/2022
Gene Williams, P.E.
DE Engineers Estimate
Corrective Action Required
11/17/2022

The Engineer’s Estimate of Probable Construction Costs shall be resubmitted to include erosion and sediment control devices and measures, final restoration, and sodding, seeding, fertilizer, topsoil and mulch. Fees to be determined based on the estimate.
Corrective Action Required
11/17/2022

The waiver to the stormwater detention requirements is currently under review by the City Engineer. Final approval is contingent upon this waiver being approved by the City Engineer.
DE Contact Field Eng. Inspector
Corrective Action Required
11/17/2022

Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / discussion with the assigned Field Engineering Inspector.
DE Future Repair Work
Corrective Action Required
11/17/2022

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Fire Review Approved with Conditions 11/18/2022 11/16/2022
Jim Eden
Code Statement
Resolved
11/16/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code. The International Existing Building Code is NOT adopted by the City of Lee's Summit
Miscellaneous Correction
Resolved
11/16/2022

903.2.3 Group E. An automatic sprinkler system shall be provided for Group E occupancies as follows: 1. Throughout all Group E fire areas greater than 12,000 square feet (1115 m2) in area. 2. The Group E fire area is located on a floor other than a level of exit discharge serving such occupancies. Exception: In buildings where every classroom has not fewer than one exterior exit door at ground level, an automatic sprinkler system is not required in any area below the lowest level of exit discharge serving that area. 3. The Group E fire area has an occupant load of 300 or more. The addition takes the building over the 12,000 square foot threshold for a sprinkler system, unless other approved building provisions are implemented.
Fire Lanes
Informational
11/16/2022

IFC 503.2.1 - Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). The existing (non-conforming) fire lane between the buildings shall be maintained.
Building Codes Review No Comments 11/18/2022 11/14/2022
Joe Frogge
Miscellaneous Correction
Corrective Action Required
11/11/2022

Sanitary connection at manhole not allowed. 11/14/22 - Deferred to Engineering approval
Traffic Review No Comments 11/18/2022 11/11/2022
Scott Ready
Engineering Review Corrections 11/04/2022 11/04/2022
Gene Williams, P.E.
Corrective Action Required
11/04/2022

An erosion and sediment control plan appeared to be missing. Please submit an erosion and sediment control plan for this project. Since the disturbed area is less than 1 acre, a SWPPP shall not be required.
Corrective Action Required
11/04/2022

The waiver for stormwater is being reviewed. It is our recommendation the waiver should be approved. However, please include the project number PL2022372 on the form, and please limit the exhibits to one (1) (i.e., grading plan?). Recommend highlighting the new building additions in yellow on the single exhibit. We would also suggest a quick analysis of the increase in stormwater peak discharge for the newly-created impervious area by use of a table showing the pre versus post-development peak flows due to the building addtions. A quick calculation shows about 0.3 cfs increase in stormwater peak flows for the 100 year event, and it would be beneficial to show this in the form of a table. Please review and revise as appropriate.
Corrective Action Required
11/04/2022

It appears the public sanitary sewer is being relocated. Separate public sanitary sewer plans shall be required. Doghouse manholes are not allowed in the City of Lee's Summit. Please submit a separate sanitary sewer relocation plan, and eliminate all doghouse manholes. Ensure a minimum of 15 feet clearance from the building and the outside of the sanitary sewer line is maintained by the realignment.
Fire Review Corrections 11/04/2022 11/01/2022
Jim Eden
Code Statement
Corrective Action Required
11/01/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code. The International Existing Building Code is NOT adopted by the City of Lee's Summit
Miscellaneous Correction
Corrective Action Required
11/01/2022

903.2.3 Group E. An automatic sprinkler system shall be provided for Group E occupancies as follows: 1. Throughout all Group E fire areas greater than 12,000 square feet (1115 m2) in area. 2. The Group E fire area is located on a floor other than a level of exit discharge serving such occupancies. Exception: In buildings where every classroom has not fewer than one exterior exit door at ground level, an automatic sprinkler system is not required in any area below the lowest level of exit discharge serving that area. 3. The Group E fire area has an occupant load of 300 or more. The addition takes the building over the 12,000 square foot threshold for a sprinkler system, unless other approved building provisions are implemented.
Fire Lanes
Corrective Action Required
11/01/2022

IFC 503.2.1 - Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). The existing (non-conforming) fire lane between the buildings shall be maintained.
Traffic Review No Comments 11/04/2022 11/01/2022
Brad Cooley, P.E., RSPI
Planning Review Corrections 11/04/2022 11/01/2022
Hector Soto Jr.
Corrective Action Required
11/01/2022

GROUND-MOUNTED UNITS. Is any new HVAC equipment proposed for the addition, or will the existing equipment serve the addition? Show the location of any new ground-mounted equipment.
Corrective Action Required
11/01/2022

EXTERIOR MATERIALS. Label the proposed exterior building materials and colors.
Building Codes Review Corrections 11/04/2022 10/26/2022
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/26/2022

Sanitary connection at manhole not allowed.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $725.00 $725.00 Paid 11/07/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
10/21/2022 Application Form Final Development Plan_LSHS_Signed
10/21/2022 Plans 220909_LSHS Bid Set_REDUX
10/21/2022 Engineer Report/Study 20220909 LSHS Robotics Stormwater Compliance Letter (R0)
10/28/2022 Engineers Estimate LSHS Robotics -EPEOPCC 20221027
11/04/2022 Letter Applicant Letter - FDP (DFDP)
11/07/2022 Receipt Receipt for transaction: 2022-008758
11/11/2022 Engineer Report/Study 22-5546 Lee's Summit High School Robotics Additions-Geotech
11/11/2022 Plans 220909_LSHS Permit Set
11/11/2022 Letter 20221108 LSHS Robotics Stormwater Compliance Letter (R1)
11/11/2022 Letter Lee's Summit HS FDP Responses
11/11/2022 Letter LSR7 Robotics - ASI 001-ISS 003 - LSHS Narrative
11/17/2022 Email EMAIL TO CITYENGINEERNOV2022
11/18/2022 Letter Applicant Letter - FDP (DFDP)
11/21/2022 Waiver/Modification Document WAIVER_STORMWATER_MAIN_HIGHSCHOOLNOV2022(s)
11/21/2022 Engineers Estimate LSHS Robotics -EPEOPCC 20221118
11/23/2022 Letter 22_1123_Lee Summit HS FDP Comments
11/23/2022 Approved Plans APPROVED LSHS ROBOTICS ADDITION
12/02/2022 Activity Document Copy of FeeWSBluePkwyLSHSRobotics
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home