Planning Application Status

PL2021063




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2021063
Lakewood Self Storage
Commercial Preliminary Development Plan
Commercial Preliminary Development Plan
Expired
02/19/2021
SALLEE REAL ESTATE INVESTMENTS LLC
Locations
Contacts
SALLEE REAL ESTATE INVESTMENTS LLC, Address:PO BOX 6437  
NEWMARK ZIMMER, Address:1485 SW MARKET ST, Phone:(816) 679-4954  
SCHLAGEL & ASSOCIATES, Address:14920 W 107TH ST, Phone:(913) 492-5158  
DALLENBACH COLE, Address:12035 COLWICK, SUITE 200, Phone:(210) 493-2234  
Reviews
Review Type Outcome Est. Completion Date Completed
Planning Review Approved with Conditions 03/30/2021 03/30/2021
Jennifer Thompson
Corrective Action Required
03/30/2021

It was noted in the landscape table the proposed evergreen heights on some species were less than 8' in height. The UDO requires a maximum height of 8' for all required plantings of an evergreen species. If the evergreens are required plantings, please revise the landscape table to reflect the correct height. A modification would be required for a reduced height.
Corrective Action Required
03/30/2021

In the landscape table for the length of medium impact area (the length of the lot), doesn't match the scaled length of the platted lot. The true length, once calculated would adjust these numbers slightly. Please revise the numbers and landscape sheet accordingly. A modification would be required if the numbers are not met.
Corrective Action Required
03/30/2021

The open space landscape requirements for the site aren't calculated correctly. The lot square footage minus the building footprint (only), is the number to use for the formula for calculating the required quantities of species. It seems the paved area was used as well. Depending on location and considered on a case by case basis: trees & shrubs for the open yard calculation may be allowed to be counted toward buffer screening; and street frontage shrubs may be counted toward parking lot screening if they serve that purpose.
Corrective Action Required
03/30/2021

Provide images of the lighting specifications within the table on the photometric sheet.
Corrective Action Required
03/30/2021

In regards to the east elevation. I understand the confusion on previously approved applications and the UDO standards. Staff will be recommending approval of 50% approved materials and a 50% metal ratio. Can we schedule a quick zoom meeting in the next couple of days to discuss this topic specifically? As most of the outstanding comments are somewhat insignificant, staff feels this project could be kept on the most up-to-date planning commission schedule. Revised plans reflecting the landscape comments could be re-submitted and additional discussion on the east elevation could happen that would give direction on the staff letter for the upcoming Planning Commission.
Traffic Review No Comments 03/30/2021 03/30/2021
Mike Weisenborn
Fire Review Approved with Conditions 03/30/2021 03/30/2021
Jim Eden
Code Statement
Corrective Action Required
03/30/2021

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Imposed Loads
Corrective Action Required
03/30/2021

IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Engineering Review Approved with Conditions 03/30/2021 03/28/2021
Gene Williams, P.E.
DE C&O #01 Eng Plans – FDP/PDP
Corrective Action Required
03/28/2021

All required engineering plans and studies, including water lines, sanitary sewers, storm drainage, streets and erosion and sediment control shall be submitted along with the final development plan. All public infrastructure must be substantially complete, prior to the issuance of any certificates of occupancy.
DE C&O #03 Eng & Insp Fees
Corrective Action Required
03/28/2021

All Engineering Plan Review and Inspection Fees shall be paid prior to approval of the associated engineering plans and prior to the issuance of any site development permits or the start of construction (excluding land disturbance permit).
DE C&O #06 Land Disturbance
Corrective Action Required
03/28/2021

A Land Disturbance Permit shall be obtained from the City if groundbreaking will take place prior to the issuance of a site development permit, building permit, or prior to the approval of the Final Development Plan / Engineering Plans.
DE C&O #11 Pavement Thickness
Corrective Action Required
03/28/2021

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE C&O #12 Cut & Fill
Corrective Action Required
03/28/2021

Any cut and / or fill operations, which cause public infrastructure to exceed the maximum / minimum depths of cover shall be mitigated by relocating the infrastructure vertically and / or horizontally to meet the specifications contained within the City’s Design and Construction Manual.
DE C&O #13 ADA Sidewalk Ramps
Corrective Action Required
03/28/2021

ADA-accessible ramp may require the dedication of additional right of way or a sidewalk easement. This will depend on the final design of the ADA-accessible ramp.
Corrective Action Required
03/28/2021

An as-built and as-graded detention basin plan shall be submitted and accepted by the City prior to issuance of any occupancy permit.
Planning Review Corrections 03/05/2021 03/05/2021
Jennifer Thompson
Corrective Action Required
03/05/2021

A preliminary development has specific criteria for review. Please provide in narrative form responses to each of the 3 PDP criteria. The criteria can be found in the UDO, Article 2.260.C.
Corrective Action Required
03/05/2021

This application does not require a special use permit due to the PMIX zoning district. However, certain conditions are in place for such facilities. A climate controlled storage facility has a set of conditions. These can be found in the UDO, Article 6.1185 (there are 4 conditions), please respond in writing how this development does or does not meet these conditions. Since this is a hybrid storage facility, the UDO has specific conditions for a self-storage type facility. These conditions can be found in the UDO, Article 6.1020 (there are four conditions), please respond in writing how this development does or does not meet these conditions. Although photographs of the surrounding area is not required, it might be helpful to have to include in the staff packet going forward to illustrate a feel for this development area.
Corrective Action Required
03/05/2021

A medium impact landscape buffer is required for the east property line/rear portion of the building. The landscaping requirements can be found in the UDO, Article 8.880.
Corrective Action Required
03/05/2021

On Sheet C1.0, remove the note indicating a Special Use Permit within the overall site data table. With the PMIX zoning a SUP isn't required.
Corrective Action Required
03/05/2021

A Form 7460 is required coordinated with the FAA.
Corrective Action Required
03/05/2021

Label and provide the breakdown of the metal panel system for the sides and rear elevations, where proposed. Staff will recommend approval of 50% of approved material (brick as shown), and the metal panels for each of these given elevations. Can a metal sample board be provided? Label the proposed colors for all exterior building materials.
Corrective Action Required
03/05/2021

Revise the accessible sign detail to include a van accessible signage/reference.
Corrective Action Required
03/05/2021

The building footprints on the landscape data table doesn't match the footprints on sheet C1.0 within the site data table.
Corrective Action Required
03/05/2021

Provide a photometric site sheet.
Engineering Review Corrections 03/05/2021 03/04/2021
Gene Williams, P.E.
Corrective Action Required
03/04/2021

Please eliminate the steel casing pipe from the fire line.
Corrective Action Required
03/04/2021

Please add an additional valve near the main connection point, on the fire line branch. The City always requires a valve on each side of the street for fire lines.
Corrective Action Required
03/04/2021

A wye should already exist for this lot. Please check Record Drawings for location of sanitary sewer wyes and stubs. Contact our Records Technician at 816-969-1800 to request a "sanitary sewer stub location drawing" for this area. They will be able to provide this in pdf format via email.
Corrective Action Required
03/04/2021

The new ADA-accessible ramp should be constructed with dedicated ramps rather than 45 degree entry ramps. As such, the right of way shown on the PDP appears too small for this type of ramp. Either a sidewalk easement or additional right of way would appear necessary, and can be dedicated by separate document. Please provide sufficient notation on the Preliminary Development Plan.
Corrective Action Required
03/04/2021

Sidewalks and general location of the private ADA-accessible route across the driveway should be shown in accordance with Michael Park comments.
Fire Review Corrections 03/05/2021 03/02/2021
Jim Eden
Code Statement
Corrective Action Required
03/02/2021

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Hydrants
Corrective Action Required
03/02/2021

IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Action required: Provide a hydrant(s) to meet this requirement.
Misc.
Corrective Action Required
03/02/2021

D104.1 Buildings exceeding three stories or 30 feet in height. Buildings or facilities exceeding 30 feet (9144 mm) or three stories in height shall have not fewer than two means of fire apparatus access for each structure. Action required: Provide the second access to the north. The access may be gated with Knox padlock.
FDC
Corrective Action Required
03/02/2021

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Action required- Show the location of the FDC.
Knox Locks
Informational
03/02/2021

IFC 506.1 - Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. 506.1.1 Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. Action required- Knox key switches and padlocks shall be provided on the gates and a Kox box provided on the building
Imposed Loads
Informational
03/02/2021

IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Traffic Review Corrections 03/05/2021 03/02/2021
Michael Park
Corrective Action Required
03/02/2021

Sidewalk required along Port Dr. and Lakewood Way adjacent to subject property development.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Commercial Preliminary Development Plan fee $1,800.00 $1,800.00 Paid 03/05/2021
9110076-Legal Notice Publishing Charge $165.00 $165.00 Paid 03/05/2021
9110076-Legal Notice Publishing Charge $165.00 $165.00 Paid 03/05/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Planning Commission Meeting 04/22/2021 05:00 PM Council Chambers 04/22/2021 05:00 PM
Public Hearing Review
Approved
04/22/2021
City Council Public Hearing 05/18/2021 06:00 PM Council Chambers 05/18/2021 06:15 PM
Public Hearing Review
Approved
05/18/2021
City Council Ordinance 2nd Reading 06/08/2021 06:00 PM Council Chambers 06/08/2021 06:00 PM
Public Hearing Review
Approved
Documents & Images
Date Uploaded File Type Document Name
02/22/2021 Plans 1. Exterior Elevations (West & South) 2021.02.17
02/22/2021 Plans 2. Exterior Elevations (East & North) 2021.02.17
02/22/2021 Plans 3. Final Rendering 2021.02.17
02/22/2021 Plans 4. View 1 from NE Lakewood Way
02/22/2021 Plans 5. View 2 from NE Lakewood Way
02/22/2021 Plans 6. Canopy Lights Cut sheet
02/22/2021 Plans 7. Wall Sconce Cut sheet
02/22/2021 Plans 8. Wall Packs Cut sheet
02/22/2021 Plans Prelim Stormwater Report
02/22/2021 Plans 2021.02.19-20-261 PDP-SUP CIVIL REV0
02/22/2021 Application Form Preliminary Development Plan Executed
03/05/2021 Receipt Receipt for transaction: 2021-001102
03/08/2021 Letter Applicant Letter - Dev. Apps (DRCP)
03/23/2021 Photograph 20-261 Neighborhood Pics
03/23/2021 Plans Building Materials Board with Callouts 2021_03_12
03/23/2021 Letter City Comments 2021_03_23
03/23/2021 Plans 2021_03_23-20-261 PDP REV1
03/23/2021 Plans Exterior Elevations 1 2021_03_19
03/23/2021 Plans MBCI20_PBD Data Sheet_0706209991115_RevA_MS_0720_WEB
03/23/2021 Plans MBCI20_7_2 Panel Data Sheet_0706209991121_RevA_MS_0720_WEB
03/23/2021 Plans Exterior Elevations 2 2021_03_19
03/23/2021 Plans Photometrics2 2021_03_15
03/30/2021 Letter Applicant Letter - Dev. Apps (DRCP)
03/30/2021 Public Notice Document PL2021063 Adjacent Property Owners
04/02/2021 Plans Building Materials Board with Callouts 2021_04_01
04/02/2021 Letter Metal Wall Panel - Letter 2021_04_02
04/02/2021 Plans Exterior Elevations 1 2021_04_02
04/02/2021 Plans Exterior Elevations 2 2021_04_02
04/05/2021 Public Notice Document Affidavit
04/07/2021 Public Notice Document LEGAL PL2021-063 PDP
04/08/2021 Plans 2021_04_08-20-261 PDP L1_0 REV3
04/08/2021 Plans Packet
04/20/2021 Lakewood Storage TIA
04/26/2021 Public Notice Document DOC042621-010
05/12/2021 Public Notice Document LEGAL PL2021-063 PDP
05/26/2021 Letter CMR LW Storage Docs
05/26/2021 Application Form Lakewood Mini Storage CMR
06/02/2021 Public Notice Document DOC060221-004
06/18/2021 Ordinance 9160
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home