Summary
PL2020377
RIDGE AT WINTERSET SUMMIT - STREET AND STORM
Engineering Plan Review
Engineering Plan Review
Approved
12/15/2020
REORGANIZED SCHOOL DIST NO 7
Locations
Contacts
REORGANIZED SCHOOL DIST NO 7, Address:600 SE MILLER ST  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
SKELSEY KEVIN R & MOLLY E, Address:2720 SW GRAY LANE  
CUNDIFF JON D & VICKY L, Address:701 SW WINTERWALK LN  
DAVIS TOM & MARY, Address:178 SW ROOSEVELT RDG  
PACE FRANK & KRISTINE, Address:2408 SW WINTERCREEK CT  
VEACH BRETT & ALISON, Address:185 SW WINTER RD  
WINTERSET COMMUNITY ASSOCIATION INC, Address:2505 SW WINTERCREEK DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Record Drawings Review No Comments 02/04/2022 02/02/2022
Gene Williams, P.E.
As-graded MDP Review No Comments 01/10/2022 01/10/2022
Gene Williams, P.E.
Engineering Review Approved with Conditions 02/02/2021 02/02/2021
Gene Williams, P.E.
Traffic Review No Comments 02/02/2021 01/28/2021
Michael Park
Engineering Review Corrections 01/25/2021 01/25/2021
Gene Williams, P.E.
Corrective Action Required
01/25/2021

The note for Option 2 on the cover sheet is still incorrect. It is showing 6 inch MoDOT Type 5 over geogrid. This does not match the typical section view.
Corrective Action Required
01/25/2021

Sidewalk was not shown, nor the ADA-accessible ramp entering the cul-de-sac. At the present time, no "payment in lieu of" for the sidewalk has been granted by the Dept. Director.
Traffic Review Corrections 01/25/2021 01/25/2021
Michael Park
Corrective Action Required
01/25/2021

Sidewalk was not waived by City Council for this recently approved subdivision. There was no waiver or modification to UDO sidewalk requirments granted by City Council in its approval. Refer to previous comment regarding required sidewalk.
Engineering Review Corrections 12/29/2020 12/29/2020
Gene Williams, P.E.
Corrective Action Required
12/29/2020

Typical section for the street is not correct. The surface course must be either Type 5 or 6, and the base course must be Type 5.
Corrective Action Required
12/29/2020

Typical section of the street is not correct if using geogrid. If using geogrid, 10 inches of aggregate must be used rather than 6 inches.
Corrective Action Required
12/29/2020

Grading appears to be too steep over most of the project. We are measuring 2:1 slopes over a significant portion of the project.
Corrective Action Required
12/29/2020

The island shown at the end of the cul-de-sac should be removed.
Corrective Action Required
12/29/2020

The location of sidewalk and ADA-accessible ramps entering the cul-de-sac was missing.
Corrective Action Required
12/29/2020

The Master Drainage Plan was missing the basement type for each lot, the MBOE for each lot, and the existing and finish corner elevations for each lot.
Corrective Action Required
12/29/2020

Stationing was missing on the plan view of the street.
Corrective Action Required
12/29/2020

A trenching and backfill detail was missing for the pipe installation. Be aware the City has changed the requirements for aggregate on top of the pipe. It is now 12 inches over the pipe rather than the previous 6 inches.
Corrective Action Required
12/29/2020

Please specify in plain language the rip rap type, the dimensions of the rip rap, the depth of the rip rap, approximate tons of rip rap, and geotextile beneath the rip rap. The calculations shown within the plans are required, but the critical information described above should be provided without consulting a table.
Corrective Action Required
12/29/2020

The underdrain detail is missing from the standard details.
Corrective Action Required
12/29/2020

Ensure the notes concerning the pavement thickness and subgrade match the typical section view.
Corrective Action Required
12/29/2020

Normally, a separate erosion and sediment control plan is required for residential subdivisions. The size of this particular subdivision, however, does not necessarily require the submission of a separate erosion and sediment control plan, unless work shall begin prior to issuance of an infrastructure permit. If work shall commence prior to this time, please submit a separate erosion and sediment control plan to the City.
Corrective Action Required
12/29/2020

A toe wall detail was missing for the flared end section.
Corrective Action Required
12/29/2020

The rip rap area appears to be installed in an area greater than the design slope of 13 percent. Please review and revise as appropriate, including the calculations for the rip rap dimensions and sizing.
Traffic Review Corrections 12/29/2020 12/22/2020
Michael Park
Corrective Action Required
12/22/2020

Sidewalk required along one side of road. Payment in lieu of construction may be an option per UDO criteria and site conditions. South side of road should be considered based on trail location and road alignment to the east/south.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home