Lee's Summit Airport - Hangar V
Commercial Final Development Plan
Commercial Final Development Plan
Approved
04/21/2020
CITY OF LEE'S SUMMIT MISSOURI
New private hangar.
Locations
Contacts
CITY OF LEE'S SUMMIT MISSOURI, Address:220 SE GREEN ST  
THOMPSON BUILDERS LLC, Address:4559 GROVE ST, Phone:(913) 915-2836  
RL SALLEE REAL ESTATE INVESTMENTS LLC, Address:2610 NE R D MIZE RD  
LOVELACE & ASSOCIATES LLC, Address:929 SE 3RD ST, Phone:(816) 347-9997  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 07/21/2020 07/15/2020
Loic Nguinguiri, E.I.
DE Engineers Estimate
Corrective Action Required
07/15/2020

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $5,506.54
DE C&O #11 Pavement Thickness
Corrective Action Required
07/15/2020

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE Contact Field Eng. Inspector
Corrective Action Required
07/15/2020

Please contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
Planning Review No Comments 07/21/2020 07/14/2020
Mike Weisenborn
Traffic Review No Comments 07/21/2020 07/14/2020
Mike Weisenborn
Building Codes Review No Comments 07/21/2020 07/14/2020
Mike Weisenborn
Fire Review Approved with Conditions 07/21/2020 07/14/2020
Mike Weisenborn
Code Statement
Corrective Action Required
07/14/2020

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Misc.
Corrective Action Required
07/14/2020

As the fire area of the building is greater than 12,000 square feet, the building shall be provided with an automatic fire sprinkler system or divided into fire areas in accordance with Chapter 7 of the 2018 IBC.
Fire Review Approved with Conditions 07/14/2020 07/13/2020
Jim Eden
Code Statement
Corrective Action Required
07/14/2020

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Misc.
Corrective Action Required
07/14/2020

As the fire area of the building is greater than 12,000 square feet, the building shall be provided with an automatic fire sprinkler system or divided into fire areas in accordance with Chapter 7 of the 2018 IBC.
Planning Review No Comments 07/14/2020 07/13/2020
Hector Soto Jr.
Engineering Review Corrections 07/14/2020 07/10/2020
Loic Nguinguiri, E.I.
Corrective Action Required
07/10/2020

The estimate includes both 6” concrete and 8” aggregate base combined together as a single item. In reviewing the previously submitted site plan, these areas of concrete and of aggregate are not clearly delineated. Please revise the site plan to clarify where each type of surface will be constructed. Revise the estimate to separate those two surface types. Please ensure that the quantity of each that is shown on the revised estimate can be verified from the revised site plan.
Corrective Action Required
07/10/2020

Please remove the striping cost item from the engineering cost estimate since the work will be performed on a private property.
Corrective Action Required
07/10/2020

The City does not request water meter related costs to be included into the EOOPCC sheet. Therefore, please dissociate to only show water service line and water main tap related expenses as applicable.
Building Codes Review No Comments 07/14/2020 07/07/2020
Mike Weisenborn
Traffic Review No Comments 07/14/2020 07/07/2020
Mike Weisenborn
Fire Review Corrections 05/22/2020 05/22/2020
Jim Eden
Code Statement
Corrective Action Required
05/22/2020

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Misc.
Corrective Action Required
05/15/2020

As the fire area of the building is greater than 12,000 square feet, the building shall be provided with an automatic fire sprinkler system or divided into fire areas in accordance with Chapter 7 of the 2018 IBC.
Planning Review Corrections 05/22/2020 05/22/2020
Hector Soto Jr.
Corrective Action Required
05/22/2020

LIGHT FIXTURES. Cut sheets for all exterior wall pack light fixtures shall be provided for review. The light fixtures shall have full 90-degree cutoffs to direct the light downward and so the light source is not visible from off the property.
Corrective Action Required
05/22/2020

APPLICATION. The application provided did not include the signature of the property owner. An application signed by the property owner is required to be submitted.
Engineering Review Corrections 05/22/2020 05/22/2020
Loic Nguinguiri, E.I.
Corrective Action Required
05/22/2020

An itemized and sealed Engineer's Opinion Of Probable Construction Costs has not been provided. The Final Development Plan’s engineering review fee and the inspection fee are based on this estimate, and calculated at 3% of the total. Items to include in the estimate include: 1) grading to establish proper drainage, 2) grading for parking, 3) removal and replacement of poor quality subgrade (estimated quantity), 4) water and sanitary utility items, 5) pavement, 6) erosion and sediment control, 7) final restoration, including sodding, seeding, fertilizer, mulch, and topsoil.
Building Codes Review No Comments 05/22/2020 05/20/2020
Joe Frogge
Miscellaneous Correction
Resolved
05/20/2020

Provide the following: - Sewer pipe material. - Water pipe material. - Screening for ground mounted hvac equipment. 5/20/20 - pipe materials covered in MEP designs - screening not required at airport
Traffic Review No Comments 05/22/2020 05/18/2020
Mike Weisenborn
Traffic Review No Comments 05/05/2020 05/05/2020
Mike Weisenborn
Planning Review Corrections 05/05/2020 05/05/2020
Hector Soto Jr.
Corrective Action Required
05/05/2020

BUILDING ELEVATIONS. The elevations submitted are not clear and the notes are difficult to read. Provide revised elevations that identify all exterior building materials, colors and light fixtures.
Corrective Action Required
05/05/2020

LIGHT FIXTURES. Cut sheets for all exterior wall pack light fixtures shall be provided for review. The light fixtures shall have full 90-degree cutoffs to direct the light downward and so the light source is not visible from off the property.
Corrective Action Required
05/05/2020

APPLICATION. The application provided did not include the signature of the property owner. An application signed by the property owner is required to be submitted.
Corrective Action Required
05/05/2020

ACCESSIBLE PARKING SPACE. Revise the note regarding the mounting height of the sign to a minimum of 5' above grade, measured to the bottom of the sign.
Corrective Action Required
05/05/2020

VICINITY MAP. Add a vicinity map to provide more context to the hangar site within the airport and surrounding area at large.
Corrective Action Required
05/05/2020

SODDING. All disturbed areas surrounding the hangar shall be sodded.
Corrective Action Required
05/05/2020

PARKING SPACES. Dimension the parking spaces. The spaces shall be a minimum 9' x 19'.
Fire Review Corrections 05/05/2020 04/28/2020
Jim Eden
Code Statement
Informational
04/28/2020

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Misc.
Corrective Action Required
04/28/2020

The dimensions on the drawings on are difficult to read. What is the total square footage, including the second floor.? S1 occupancies greater than 12,000 are required to be sprinklered or provided with rated barriers per IBC to reduce the fire area to less than 12,000sq. ft.
Engineering Review Corrections 05/05/2020 04/28/2020
Loic Nguinguiri, E.I.
Corrective Action Required
05/20/2020

An itemized and sealed Engineer's Opinion Of Probable Construction Costs has not been provided. The Final Development Plan’s engineering review fee and the inspection fee are based on this estimate, and calculated at 3% of the total. Items to include in the estimate include: 1) grading to establish proper drainage, 2) grading for parking, 3) removal and replacement of poor quality subgrade (estimated quantity), 4) water and sanitary utility items, 5) pavement, 6) erosion and sediment control, 7) final restoration, including sodding, seeding, fertilizer, mulch, and topsoil.
Building Codes Review Corrections 05/05/2020 04/27/2020
Joe Frogge
Miscellaneous Correction
Corrective Action Required
04/27/2020

Provide the following: - Sewer pipe material. - Water pipe material. - Screening for ground mounted hvac equipment.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $600.00 $600.00 Paid 04/22/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
04/21/2020 Activity Document Application
04/21/2020 Plans Site Plan Doc - Apr 21 2020 - 1-09 PM
04/22/2020 Receipt Receipt for transaction: 2020-001676
05/05/2020 Plans Doc - Apr 21 2020 - 1-07 PM
05/05/2020 Letter Applicant Letter - FDP (DFDP)
05/12/2020 Final Development Plan Hangar V Corrections
05/12/2020 Plans Hangar V Plumbing & Mechanical Plans
05/15/2020 Plans Signature Builders New Hanger Project_merged
05/22/2020 Letter Applicant Letter - FDP (DFDP)
05/29/2020 Letter Applicant Letter - FDP (DFDP)
06/22/2020 Plans LS hanger V Permit 6_18
06/29/2020 Letter PLAN REVIEW CONDITION RESPONSE LETTER 2_
07/07/2020 Engineers Estimate Hangar V Cost Estimate
07/14/2020 Letter Applicant Letter - FDP (DFDP)
07/14/2020 Letter Applicant Letter - FDP (DFDP)3 - Responses
07/14/2020 Engineers Estimate Hangar V Cost Estimate-2
07/20/2020 Activity Document CV Fee Worksheet PL2020-120
07/20/2020 Letter Applicant Letter - FDP (DFDP)
08/17/2020 Approved Plans Approved Hangar V Civil
10/28/2020 Letter NRA_Notification
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home