PL2020100
The Townhomes of Chapel Ridge 2nd Plat - Public Water
Engineering Plan Review
Engineering Plan Review
Complete
04/08/2020
CHAPEL RIDGE RESIDENTIAL LLC
Locations
Contacts
CHAPEL RIDGE RESIDENTIAL LLC, Address:3170 NE CARNEGIE DR #400  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
Reviews
Review Type Outcome Est. Completion Date Completed
Record Drawings Review No Comments 08/16/2022 08/16/2022
Sue Pyles, P.E.
Record Drawings Review Corrections 08/27/2021 09/07/2021
Sue Pyles, P.E.
Corrective Action Required
09/07/2021

The plans called for removal of existing water cross, installation of a new tee, and removal of existing water line along the east side of Lot 9. Please revise the record drawings to match what work was actually done at that location.
Corrective Action Required
09/07/2021

Please revise the Engineer’s Certification to include all required as previously provided. Be sure to cross out the appropriate option at the end of the certification’s first sentence to identify how the information was obtained.
Engineering Review No Comments 06/03/2020 06/03/2020
Sue Pyles, P.E.
Engineering Review Corrections 05/06/2020 04/30/2020
Sue Pyles, P.E.
Corrective Action Required
04/30/2020

Revise the project name to match the Townhomes plat name in the project title on the cover sheet and in the title block on each sheet.
Corrective Action Required
04/30/2020

Revise the sediment basin label to sediment trap, as per the street & storm plan review comments.
Corrective Action Required
04/30/2020

Show and label the proposed easement outside of the plat boundary. Submit a draft of the off-site easement for review. The easement will need to be recorded prior to issuance of Substantial Completion of the project.
Engineering Review Corrections 04/24/2020 04/21/2020
Sue Pyles, P.E.
Corrective Action Required
04/21/2020

Sheet C.500: • Water Note 2 references standards that pertain to ductile iron pipe, which are already in the Design and Construction Manual and don’t need referenced separately. In any case, since the plan set calls for C900 PVC pipe, this note is not necessary. • The gate valve listed in Water Note 4 is not on the City’s Approved Product’s List for Water Utilities. The approved model for Mueller is the 2360 Series. • Water Note 5 is not needed. It references Clay and Bailey P-108, which is not on the City’s Approved Product’s List for Water Utilities. • KCP&L is now Evergy. Please update the plan set.
Corrective Action Required
04/21/2020

Sheet C.501: • The line type used for existing sanitary and water aren’t the typical dashed lines. Is there a reason for the change? • The existing water line that extends south from the removal location across NE Lone Hill Drive is shown south to the existing sanitary. For clarity, as a cut off point for this water line in the drawing, please extend it slightly beyond the sanitary line. • Label the street names on this sheet and throughout the plan set.
Corrective Action Required
04/21/2020

Sheets C.502 – C.503: • Include the following note: “Compacted Fill shall be placed to a minimum 18” above the top of the pipe prior to installation. • Show and label the limits of the compacted fill placement in the Profile views. Use hatching for clarity. • The FH graphic is difficult to read. Please revise for clarity. • Is there a FH at the Line 1 connection location with the existing water main? If so, is it permanent to be kept or temporary to be removed? • Deflection in the water line is only allowed in the joints, and only within tolerances approved by the manufacturer. Please provide the manufacturer’s tolerances and include the radius of curvature of all pipe to ensure it meets those tolerances. In all locations necessary, show and label all horizontal and vertical bends required.
Corrective Action Required
04/21/2020

Submit an Engineer's Estimate of Probable Construction Costs.
Hearings
Title Location Date Time
Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home