PL2018210
Cobey Creek 1st Plat - Water Lines
Engineering Plan Review
Engineering Plan Review
Approved
11/21/2018
JCM DEVELOPMENT LLC
Locations
Contacts
JCM DEVELOPMENT LLC, Address:1314 SW MARKET ST  
JCM DEVELOPMENT LLC, Address:1314 SW MARKET ST  
HG CONSULT, INC, Address:9007 PINE ST, Phone:(816) 759-2285  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 03/24/2021 03/23/2021
Gene Williams, P.E.
Corrective Action Required
03/23/2021

DEG ACCEPTED and MDNR Close-Out Documents were supplied.
Engineering Review Approved with Conditions 04/30/2019 04/23/2019
Gene Williams, P.E.
Engineering Review Corrections 03/19/2019 03/19/2019
Gene Williams, P.E.
Corrective Action Required
03/19/2019

Please see the comments on the Street, Stormwater, Master Drainage Plan, and Erosion and Sediment Control concerning the adjustment of sanitary sewer line depth and storm sewer depth to achieve the depth of cover requirements for the three (3) substandard locations shown on the plans. It appears the sanitary sewer and/or storm sewer depth can be changed to achieve the required depth of cover, thus negating the need for pipe insulation. Of particular concern is the northernmost water line along Corbin Dr. This is a dead end line, and will have zero flow after development. The combination of zero flow, and less than 2 feet of cover, will lead to freezing of the pipe, regardless of the insulation provided.
Engineering Review Corrections 12/14/2018 12/14/2018
Gene Williams, P.E.
Corrective Action Required
12/14/2018

The general layout of the water line should be revised as follows: 1) complete a loop from Cobey Creek Dr. to the connection on M-150, and 2) eliminate the loop to the southwest on Ayva Blvd. until a later phase. The reason for this recommended change is to eliminate the drainage issues that will be created by the construction of the loop at Ayva Blvd. and M-150, and also the issue of access to this line by Water Utilities. Although ultimately this will require the addition of another loop on M-150, it will eliminate the need to provide suitable drainage structures or drainage conveyance systems along the rough-graded roadway, and will also eliminate access issues for Water Utilities personnel.
Corrective Action Required
12/14/2018

All Sheets: Please update all construction contact notes. Development Services - Inspections Group should be contacted for all inspection activities, not Public Works. The phone number is 816-969-1200.
Corrective Action Required
12/14/2018

As applicable, off-Site easements shall be required along all unplatted portions of the development prior to approval of the plans. The easements must be in a form acceptable to the City, and standard templates can be obtained by contacting the right of way agent at 816-969-1800. The easements should be general utility easements, dedicated to the City of Lee's Summit (i.e., grantee).
Corrective Action Required
12/14/2018

Notes must be provided that the cut-in tee installation on M-150 must be performed at night, with adequate notice to affected users. The installation must be completed within 8 hours. The contractor is responsible for providing sufficient notice to all affected water users.
Corrective Action Required
12/14/2018

An additional butterfly valve appears to be warranted on the 12 inch main along M-150 (i.e., at both locations, including the new one along Cobey Creek Dr.). The location of this valve should be placed within a reasonable distance of the branch tee.
Corrective Action Required
12/14/2018

Is it possible to identify each water line (e.g., Water Line A, Water Line B, etc.) on the general overview layout sheet? This would greatly enhance the plans.
Corrective Action Required
12/14/2018

Separate permits from MoDOT are required for the water line installation beneath M-150. Although the City does not require casing pipe for water lines to be installed beneath roadways, MoDOT may require this to be installed. If so, please show all details, including sufficient notes and standard drawing call-outs on the plan view. Provide the length of the casing carrier pipe, material type and size, and specify the connection is to be bored and cased.
Corrective Action Required
12/14/2018

Sheet 5 of 14: An additional fire hydrant appears warranted along Cobey Creek Dr.
Corrective Action Required
12/14/2018

Overview Sheet and Sheet 5 of 14: Water Line C does not appear to serve any purpose other than for future phases. Please delete it, at least delete the portion from the west side of Cobey Creek Dr. near station 0+75 onwards. It would be acceptable to install the crossing, and provide a temporary fire hydrant at the end of the line, on the west side of Cobey Creek Dr.
Corrective Action Required
12/14/2018

Sheet 6 of 14: The end of the line shows a plug, with an offset fire hyrdrant. Typically, end of the line fire hydrants should be installed "in-line", unless the location of the fire hydrant for future phases will not change. Is this the proposed permanent location of the offset fire hydrant?
Corrective Action Required
12/14/2018

Is it possible to show the locations of fire hydrants on the general overview sheet? This would greatly enhance the plans.
Corrective Action Required
12/14/2018

General Comment on All Plan Sheets: The locations of all bends must be shown. The magnitude of the bend must also be shown (e.g., 45 degree, 22.5 degree, etc.). Thrust blocks should also be called-out at these locations. C-900 pipe does not allow for any flexure in the pipe. The only allowance is within the pipe joint itself, and the magnitude of this "bend" is only 1 degree per joint. This equates to approximately 1200 feet minimum radius of "curvature" (i.e., it is not really curvature, but resembles curvature when stacking several 1 degree bends in the joint). To summarize, no flexure is allowed in the pipe, but a very small deflection can be provided in the joint to achieve a very modest "radius of curvature".
Corrective Action Required
12/14/2018

The above comment concerning the location and magnitude of bends would apply to all applicable line segments, and this would appear to apply to all segments that are currently shown in a curved configuration.
Corrective Action Required
12/14/2018

There appears to be several locations where fill is being proposed, with finish grade higher than existing grade elevation. Provide sufficient notes at these locations specifying that the installation of water line follow the Design and Construction Manual (i.e., fill must be brought-in, properly compacted, and then the pipe is installed after this has been completed).
Corrective Action Required
12/14/2018

All M-150 Roadway Crossings: One valve is required at the tee, but an additional valve is also required on the opposite side of the roadway. Due to the arterial nature of this roadway, this is needed to isolate the segment beneath the roadway in the event of repair.
Corrective Action Required
12/14/2018

Two (2) unneccesary and undesired "jogs" are shown at the following locations: 1) Carter Rd. and Corbin Dr. intersection, and 2) Riley Way and Corbini Dr. intersection. It is unknown why these "jogs" are shown. They create maintenance issues, and the second "jog" creates a parallel line which is not desired or needed.
Corrective Action Required
12/14/2018

Please remove the trench check details. These are only used for sanitary sewer laterals.
Corrective Action Required
12/14/2018

Please remove the water meter well detail. These are not installed as part of this project.
Corrective Action Required
12/14/2018

Please remove the backflow vault detail. It is not used on this project.
Corrective Action Required
12/14/2018

Sheet 4 of 14: Please show on the profile view, the 8 inch line, and the 12 inch line. This can be in the form of a note on the profile view, showing dimension lines from xxx to xxx, or similar.
Corrective Action Required
12/14/2018

The locations of the air release assemblies for the 12 inch line were not shown. These must be specified at all high points on the 12 inch line.
Corrective Action Required
12/14/2018

Insuffient depth of cover is shown graphically on Sheet 5 of 14 near station 0+00.
Corrective Action Required
12/14/2018

There appear to be numerous instances where valves are shown beneath finish grade on the various profile views. Please clean-up as appropriate.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home