Planning Application Status

PL2015069




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2015069
Summit Innovation Center Public Water Line Extension
Engineering Plan Review
Engineering Plan Review
Approved
05/04/2015
TOWNSEND SUMMIT LLC
Locations
Contacts
Not shown for privacy reasons.
TOWNSEND SUMMIT LLC, Address:1311 MCCORMICK RD STE 470, Phone:(303) 947-2044  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 06/24/2015 06/24/2015
Gene Williams, P.E.
Engineering Review Corrections 06/15/2015 06/15/2015
Gene Williams, P.E.
Corrective Action Required
06/15/2015

Please see comment #19 of our previous comment letter. Existing and proposed easements were not shown for the on-site water lines on the re-submittal. This will be necessary to determine whether the water line is contained within the easement with enough space to maintain the line in the future.
Corrective Action Required
06/15/2015

Please see comment #11 of our previous comment letter. Easements were shown for the off-site 12" water line, but they are too close (i.e., 3 feet) of the edge of the easement to allow for future maintenance of the line. Please move the proposed water line so it is more centered within the easement with at least five (5) feet from the outside of the pipe to the edge of the easement.
Engineering Review Corrections 05/26/2015 05/26/2015
Gene Williams, P.E.
Corrective Action Required
05/26/2015

Please provide a separate plan set for the water line. This should include the entire public water line, including the "off-site" water line.
Corrective Action Required
05/26/2015

Please provide an overview sheet showing the location of the water line in bold in relation to other features (grayed-out).
Corrective Action Required
05/26/2015

Please add a note stating that "...all construction shall follow the City of Lee's Summit Design and Construction Manual as adopted by Ordinance 5813. Where discrepancies exist between these plans and the Design and Construction Manual, the Design and Construction Manual shall prevail."
Corrective Action Required
05/26/2015

All Sheets: Please specify a minimum of 42" of cover, and a maximum depth of 7 feet.
Corrective Action Required
05/26/2015

All Sheets: Please specify a butterfly valve on the 12 inch water line. Butterfly valves are required for all water lines 12 inches and greater.
Corrective Action Required
05/26/2015

Sheet C301: Fire hydrants are required for every 500 feet of street length. It appears this requirement has not been met.
Corrective Action Required
05/26/2015

Sheet C301: It appears that a blow-off assembly will be necessary at the high point of the 12 inch water line.
Corrective Action Required
05/26/2015

Sheet C302: It appears a blow-off assembly will be necessary at the high point of the 12 inch water line.
Corrective Action Required
05/26/2015

Sheet C302: It appears the fire hydrant spacing is not sufficient, and additional fire hydrants will be necessary to meet the 500 hundred feet requirement.
Corrective Action Required
05/26/2015

Sheet C302: A butterfly valve should be specified rather than a gate valve on the 12 inch water line. Please see previous comment.
Corrective Action Required
05/26/2015

Are there existing easements for the new 12 inch water line? If so, please show them.
Corrective Action Required
05/26/2015

Sheet C303: Please specify on the plan view that all water lines to be bored and cased beneath Ward Road.
Corrective Action Required
05/26/2015

Sheet C303: Please specify a butterfly valve on the 12 inch water line.
Corrective Action Required
05/26/2015

Sheet C303: It does not appear that the fire hydrant spacing meets the 500 foot requirement.
Corrective Action Required
05/26/2015

Sheet C303: A 12 inch by 6 inch tee is shown at station 25+00, but it does not appear to serve any purpose. Is this a typographical error? Was this intended to be a butterfly valve?
Corrective Action Required
05/26/2015

Sheet C304: It does not appear that the fire hydrant spacing meets the 500 foot requirement.
Corrective Action Required
05/26/2015

Sheet C305: Please specify the water line beneath Ward Road will be bored and cased.
Corrective Action Required
05/26/2015

It is unclear where the water line along Innovation Parkway is in relation to the sanitary sewer. Please ensure there is a minimum of ten (10) feet horizontal distance between the sanitary sewer and water line, as measured from the outside of the respective pipes.
Corrective Action Required
05/26/2015

Please show the location of all existing and proposed easements.
Corrective Action Required
05/26/2015

Standard details should be provided within the water line extension plan set. This is an MDNR requirement since they require sealed standard details. Please ensure that the casing carrier pipe detail, blow off assembly detail, valve box and cover details, thrust block (horizontal and vertical) detail, fire hydrant assembly detail, and any other details are included in the plan set.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
05/26/2015 Letter PW-Comment Letter (Engineering Plans)
06/15/2015 Letter PW-Comment Letter (Engineering Plans)
08/07/2015 Letter PW-Engineering Approval Letter
11/02/2017 Activity Document Fee WorksheetWaterLine
11/02/2017 Activity Document MDNR Concurrence Letter Water Line
11/02/2017 Activity Document MDNR Concurrence Letter Water Line
11/02/2017 Activity Document Water Model Printout
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home