Engineering Review
|
No Comments
|
06/24/2015
|
06/24/2015
|
|
Gene Williams, P.E.
|
|
|
Engineering Review
|
Corrections
|
06/15/2015
|
06/15/2015
|
|
Gene Williams, P.E.
|
|
Corrective Action Required
In our previous comment letter, it was noted that slope of the sanitary lines were suspect. One of the sanitary sewer lines (i.e., 8 inch) is still shown with a slope of 0.50%. The minimum is 0.60%, although a greater slope is recommended to allow for construction tolerance.
|
|
Corrective Action Required
Please see comment #7 in our previous comment letter. This manhole and sewer line is still too deep. It appears that manhole C2 is now re-named as C3, and perhaps that is why the comment was overlooked.
|
|
Corrective Action Required
Please see comment #11 in our previous comment letter. The water line is shown too close to the sanitary sewer line, and neither the City nor the MDNR will allow it.
|
|
Corrective Action Required
Please show and label all existing and proposed easements. This was requested in comment #3 of our previous comment letter.
|
|
|
Engineering Review
|
Corrections
|
05/26/2015
|
05/26/2015
|
|
Gene Williams, P.E.
|
|
Corrective Action Required
Please provide a separate plan set for the sanitary sewer.
|
|
Corrective Action Required
Please provide an overview sheet showing the location of the sanitary sewer on one sheet.
|
|
Corrective Action Required
Please show the location of all existing and all future easements.
|
|
Corrective Action Required
Please label the existing City sanitary sewer manholes with the City manhole number.
|
|
Corrective Action Required
Please label all road names.
|
|
Corrective Action Required
Sheet C404: Sanitary sewer line C is shown with 0.6% slope. This is the minimum slope, and should be specified with perhaps 0.7% to account for installation tolerance. The City cannot accept any sanitary sewer less than the minimum.
|
|
Corrective Action Required
Sheet C404: Manhole C2 is shown with approximately 16 feet of cover. This is greater than allowed by the Design and Construction Manual (i.e., 15 feet maximum).
|
|
Corrective Action Required
There are several instances where the 12" sanitary sewer line is shown with the minimum 0.40% slope. Please use a higher number to allow for tolerance in installation since the City will not accept any sanitary sewer less than the minimum slope (e.g. 0.39% will not be acceptable).
|
|
Corrective Action Required
Is there a reason that the water line is not shown "grayed out" in the background? Please consider adding the water line layer in the background.
|
|
Corrective Action Required
Please move manhole A3 outside the limits of the future sidewalk.
|
|
Corrective Action Required
It appears a portion of the public water line along Innovation Parkway is on the same side of the road as the sanitary sewer. If this is the case, then a minimum separation of ten (10) feet must be maintained as measured from the outside of the pipe, and five (5) feet from any storm sewer.
|
|
Corrective Action Required
|
|
Corrective Action Required
Is there a reason that north is pointing downward on many of the plan sheets?
|
|
Corrective Action Required
Standard details will need to be included within the plan set for the sanitary sewer. This is due to MDNR requirements for a stamped set of details.
|
|
|