Summary


PRSUBD20261149
Public Infrastructure
In Plan Review
JOHN KNOX VILLAGE
DEVELOPMENT COMPLETE
Public Sanitary Sewer Relocation
03/19/2026
Locations
Contacts
BHC Engineering, Address:Attn: Eric Byrd, Phone:(913) 663-1900  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
SFCS, Inc., Address:Attn: Daron Speicht, AIA, Phone:(704) 577-6183  
BHC Engineering, Address:Attn: Eric Byrd, Phone:(913) 663-1900  
Scott Ready, Phone: 8169691225  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review - Sanitary Corrections 04/02/2026 04/02/2026
Gene Williams, P.E.
Miscellaneous Correction
Corrective Action Required
04/01/2026

It appears the existing line was installed at minimum or near minimum slope, and relocation might not be possible. You are showing little or no drop at manholes, and understand this was done due to the lack of additional fall. The City cannot approve without a 0.20 drop or more across each invert without a waiver. It would appear the building should be moved south to avoid relocation of the sanitary sewer line.
Miscellaneous Correction
Corrective Action Required
04/01/2026

Concrete boxouts in accordance with SAN-9 shall be installed if lid is within pavement. Please label on plan view and reference SAN-9. Also, show the orientation, with the diamond shape evident as viewed along the traveled way.
Miscellaneous Correction
Corrective Action Required
04/01/2026

Trenching and backfill detail is needed for the sanitary line, and shall require 12 inhes aggregate over the pipe.
Miscellaneous Correction
Corrective Action Required
04/01/2026

Sanitary line is too close along west side of proposed building. Minimum distance is 15 feet as measured from the outside of pipe or manhole, to the furthest point along the foundation of the building.
Miscellaneous Correction
Corrective Action Required
04/01/2026

If you can achieve relocation and still meet separation distance requirements, ensure a minimum 0.20 drop at all manholes with deflection angle less than 45 degrees, and 0.50 feet drop for deflection angles greater than or equal to 45 degrees.
Miscellaneous Correction
Corrective Action Required
04/01/2026

Provide details on line abandonment in accordance with the Design and Construction Manual. This is contained within the design criteria of the City of Lee's Summit sanitary sewer requirements. Please ensure specific notes are provided for the abandonment in place rather than a statement such as "abandon as per City requirements".
Miscellaneous Correction
Corrective Action Required
04/02/2026

Provide notes specifying NO DOGHOUSE MANHOLES.
Miscellaneous Correction
Corrective Action Required
04/02/2026

There appears to be a third service line that ties into the existing sewer, but not shown. Please investigate and show on the plans.
Miscellaneous Correction
Corrective Action Required
04/02/2026

Provide City manhole numbers for existing manholes. Please call me if you need me to look these up.
Miscellaneous Correction
Corrective Action Required
04/02/2026

MDNR permit is not required due to the short length of the relocation.
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
03/19/2026 Plans Sanitary Relocation Plans_Rev 0_PRSUBD20261149
03/19/2026 Engineers Estimate Sanitary Relocation Estimate of Probable Cost_Rev 0_PRSUBD20261149
04/02/2026 Letter SUBD Comment Letter
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home