Review Type |
Outcome |
Est. Completion Date |
Completed |
Engineering Review
|
Approved with Conditions
|
05/07/2025
|
05/07/2025
|
|
Gene Williams, P.E.
|
|
|
Engineering Review - Water
|
Corrections
|
03/14/2025
|
03/13/2025
|
|
Gene Williams, P.E.
|
|
Miscellaneous Correction
An MDNR construction permit shall not be required due to the short length. Informational comment.
|
|
Miscellaneous Correction
Prior to formal approval, a cost estimate for all work covered by these plans shall be required. The Engineering Plan Review and Inspection Fee is based on the accepted cost estimate. Informational comment.
|
|
Miscellaneous Correction
Corrective Action Required
Acquisition of off-site easements shall be required prior to approval. Applicant shall be required to acquire this public easement, not the City. It shall be an exclusive water line easement dedicated to the City. It shall follow the template provided by the City. A review copy of this easement shall be provided prior to execution and recording. Corrections required.
|
|
|
Engineering Review - Water
|
Approved with Conditions
|
12/24/2024
|
12/20/2024
|
|
Gene Williams, P.E.
|
|
Miscellaneous Correction
Fire hydrant at 1+80 needs to be reset and relocated. There is no sense in going around the fire hydrant. Show the water main as a straight-through installation, and install the fire hydrant in an offset fashion towards the shopping center to the west, outside of the flume and in the grassed area. Provide callouts for WAT-7 to be used for this fire hydrant installation. Corrections required.
|
|
Miscellaneous Correction
Notes say to "cut-in water main for domestic water supply". This should be changed to read "tap water main for domestic water supply", or equivalent language. Corrections required.
|
|
Miscellaneous Correction
You are showing the end of the line with an offset fire hydrant. Indicate on the plans this shall be installed as per WAT-8 in the plans. Corrections required.
|
|
Miscellaneous Correction
A trenching and backfill detail was missing. Corrections required.
|
|
Miscellaneous Correction
Title should be "Public Water Main Extension for Take 5 Oil Change" or equivalent language. Corrections required.
|
|
Miscellaneous Correction
What is the reasoning behind the bore underneath the driveway? It is my understanding this driveway is to be completely removed and replaced? Corrections required.
|
|
Miscellaneous Correction
Minimum depth of cover (i.e., depth over the top of pipe) is 3.5 feet unless waived by Water Utilities. There are numerous exceedances of this rule. Corrections required.
|
|
Miscellaneous Correction
Erosion and sediment control plan for this portion of the overall project is missing. Corrections required.
|
|
Miscellaneous Correction
Where are the callouts on the profile view of: 1) length of pipe, and 2) elevations of pipe at key locations? Corrections required.
|
|
Miscellaneous Correction
Sheet C4.1: We are showing the 8 inch line continues towards the fire hydrant. You will need to ensure this development is supplied with an 8 inch line for the full length of the installation, which may require the removal of additional 6 inch line as needed. Change the notation on this sheet from "Existing 6" water main (contractor to locate and verify depth prior to construction" to "Existing 8 inch water main (contractor locate and verify depth prior to construction)". Corrections required.
|
|
Miscellaneous Correction
An MDNR construction permit shall not be required due to the short length. Informational comment.
|
|
Miscellaneous Correction
Prior to formal approval, a cost estimate for all work covered by these plans shall be required. The Engineering Plan Review and Inspection Fee is based on the accepted cost estimate. Informational comment.
|
|
Miscellaneous Correction
Drawing is missing the following items: 1) existing easements, 2) right of way lines, 3) property lines. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Acquisition of off-site easements shall be required prior to approval. Corrections required.
|
|
|
Engineering Review - Water
|
Corrections
|
11/08/2024
|
11/06/2024
|
|
Gene Williams, P.E.
|
|
Miscellaneous Correction
Corrective Action Required
Fire hydrant at 1+80 needs to be reset and relocated. There is no sense in going around the fire hydrant. Show the water main as a straight-through installation, and install the fire hydrant in an offset fashion towards the shopping center to the west, outside of the flume and in the grassed area. Provide callouts for WAT-7 to be used for this fire hydrant installation. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Notes say to "cut-in water main for domestic water supply". This should be changed to read "tap water main for domestic water supply", or equivalent language. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
You are showing the end of the line with an offset fire hydrant. Indicate on the plans this shall be installed as per WAT-8 in the plans. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
A trenching and backfill detail was missing. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Title should be "Public Water Main Extension for Take 5 Oil Change" or equivalent language. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
What is the reasoning behind the bore underneath the driveway? It is my understanding this driveway is to be completely removed and replaced? Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Minimum depth of cover (i.e., depth over the top of pipe) is 3.5 feet unless waived by Water Utilities. There are numerous exceedances of this rule. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Erosion and sediment control plan for this portion of the overall project is missing. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Where are the callouts on the profile view of: 1) length of pipe, and 2) elevations of pipe at key locations? Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Sheet C4.1: We are showing the 8 inch line continues towards the fire hydrant. You will need to ensure this development is supplied with an 8 inch line for the full length of the installation, which may require the removal of additional 6 inch line as needed. Change the notation on this sheet from "Existing 6" water main (contractor to locate and verify depth prior to construction" to "Existing 8 inch water main (contractor locate and verify depth prior to construction)". Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
An MDNR construction permit shall not be required due to the short length. Informational comment.
|
|
Miscellaneous Correction
Corrective Action Required
Prior to formal approval, a cost estimate for all work covered by these plans shall be required. The Engineering Plan Review and Inspection Fee is based on the accepted cost estimate. Informational comment.
|
|
Miscellaneous Correction
Corrective Action Required
Drawing is missing the following items: 1) existing easements, 2) right of way lines, 3) property lines. Corrections required.
|
|
Miscellaneous Correction
Corrective Action Required
Are there existing off-site easements to install the water main? If not, acquisition of off-site easements shall be required. Corrections required.
|
|
|