Permit Application Status

PRRES20250365


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20250365
Building Permit - Residential
Issued
CLAYTON PROPERTIES GROUP INC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED AND UNFINISHED BASEMENT - COVERED AND UNCOVERED DECK -
02/02/2025
02/17/2025
Locations
Contacts
TRUMARK HOMES, LLC, Address:424 SE MAXWELL DR, Phone:(816) 564-5613  
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
MARK A YANCIK, Address:508 nw manor dr  
TRUMARKHOMES.MARK@GMAIL.COM  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
IMPACT ELECTRICAL SOLUTIONS LLC, Address:14 ANCHOR DRIVE, Phone:(816) 674-9345  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 02/17/2025
Right of Way Permit Fee $85.00 $85.00 Paid 02/17/2025
Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 02/17/2025
Water Tap Fee $3,973.00 $3,973.00 Paid 02/17/2025
Water Meter Fee $748.03 $748.03 Paid 02/17/2025
Valuation Fee New Single Family $1,758.57 $1,758.57 Paid 02/17/2025
Not Ready Inspection Fee $75.00 $75.00 Paid 09/05/2025
Not Ready Inspection Fee $75.00 $75.00 Paid 09/05/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Occupancy Inspection - Codes Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Failed 3/27/2025 3/27/2025 03/27/2025
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/27/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. ***3/27/25 -Provide erosion control methods at spoils piles on adjacent lot, clean debris from streets, post address.
Footing Inspection - Residential Passed 3/27/2025 3/27/2025 03/27/2025
Misc
Informational
03/27/2025
Approved by David Ainsworth on 3/26/25
Erosion Control Inspection Residential Partial 4/2/2025 4/2/2025 04/02/2025
DCM3 ESC REQUIRED 2 DAY
Resolved
04/02/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. ***3/27/25 -Provide erosion control methods at spoils piles on adjacent lot, clean debris from streets, post address.
Erosion Control Inspection Residential Partial 04/16/2025
Underslab Plumbing Inspection - Residential Passed 4/16/2025 4/16/2025 04/16/2025
Erosion Control Inspection Residential Partial 04/23/2025
Sewer Service Inspection - R Passed 4/23/2025 4/23/2025 04/23/2025
Erosion Control Inspection Residential Failed 4/30/2025 04/30/2025
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
04/30/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. **CLEAN STREET AND RESTORE EROSION CONTROL TO COMPLIANCE
Water Service Inspection - R Passed 4/30/2025 4/30/2025 04/30/2025
All Rough Inspection - Residential Not Ready 6/25/2025 6/25/2025 06/25/2025
Misc
Corrective Action Required
06/25/2025
6/25/25 Inspection for "Need inspection on garage door portal framing, front porch ceiling and back deck ceiling only" -PFH nailed through moisture barrier- seal penetrations -Front porch ceiling- already covered -Back deck ceiling- Not framed at all -CSPF at back- missing nailing pattern and full length king studs in corner ***Not ready
Erosion Control Inspection Residential Partial 6/25/2025 6/25/2025 06/25/2025
DCM2 ESC DEFICIENT INSTALLATION
Resolved
06/25/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. **CLEAN STREET AND RESTORE EROSION CONTROL TO COMPLIANCE
All Rough Inspection - Residential Partial 6/30/2025 6/30/2025 06/30/2025
Misc
Resolved
06/30/2025
6/25/25 Inspection for "Need inspection on garage door portal framing, front porch ceiling and back deck ceiling only" -PFH nailed through moisture barrier- seal penetrations -Front porch ceiling- already covered -Back deck ceiling- Not framed at all -CSPF at back- missing nailing pattern and full length king studs in corner ***Not ready
Misc
Informational
06/30/2025
PFH at garage is ok Front and back porches are ok to cover Cs-pf at rear is nailed properly and no is ok
Gas Service Inspection - Residential Failed 8/14/2025 8/14/2025 08/14/2025
G2417.4.1 Test Pressure
Corrective Action Required
08/14/2025
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Electrical Service Inspection Passed 8/14/2025 8/14/2025 08/14/2025
All Rough Inspection - Residential Failed 8/14/2025 8/14/2025 08/14/2025
Misc
Informational
06/30/2025
PFH at garage is ok Front and back porches are ok to cover Cs-pf at rear is nailed properly and no is ok
Misc
Corrective Action Required
08/14/2025
**8/14/25 House not ready for inspection. List is incomplete. Correct all items before rescheduling inspection** -Seal top plate penetration at exterior garage wall -Provide structural straps at top plates lapped less than 24” by beam -Seal top plates at hvac chase -Provide rafter/collar ties at rafters not connected to ceiling joists at garage wall -Tighten anchor bolts throughout -Missing joist hanger at entry bathroom -Cripple walls less than 14" are required to be sheathed continuously on one side and fastened to top and bottom plates per R602.9 -Rafters over notched and not connected to ceiling joists at master closet exterior wall -Address ceiling and roof loads landing on non load bearing walls at powder, master bath, laundry, foyer -Provide code compliant structural straps at over bored top plates on load bearing walls -Nail all intersecting wall studs 12” oc -Fur out around and protect dryer duct in bathroom -Strap top plates lapped less than 24” at dinning exterior by windows/master bed -Roof struts to 4’ oc max -Missing stiff backs at roof struts multiple locations -plywood cripple wall at exterior great room -Replace broken cripple stud above windows at great room -Strap top plates lapped less than 24” at great room exterior -Seal top plates at great room exterior corner -Seal gaps at dead space at great room/stairwell double wall -Missing joist hanger at joist to beam near stairwell -Secure pex lines at shower bed 2 -Solid block behind hinge locations at front door -Seal penetrations in studs at return air bed 2 -Nail rafter to ceiling joists at bed 2 -Provide structural strap at over bored top plates bed -Nail exterior sheathing to studs at bed 2 corner -Provide lateral restraint at LVL beam at stairwell/great room -Fireblock double wall at stairs-also use approved materials -Complete all Fireblocking at ceiling lines, double walls etc at basement -Tighten nuts at columns in basement -Fireblock stair landing -Anchor sill plates in basement **Basement not inspected **Exterior not inspected
Gas Service Inspection - Residential Not Ready 8/21/2025 8/21/2025 08/21/2025
G2417.4.1 Test Pressure
Corrective Action Required
08/14/2025
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
All Rough Inspection - Residential Failed 8/21/2025 8/21/2025 08/21/2025
Misc
Informational
08/14/2025
PFH at garage is ok Front and back porches are ok to cover Cs-pf at rear is nailed properly and no is ok
Misc
Corrective Action Required
08/14/2025
-not further inspections until overgrown vegetation is in compliance maintain overgrown vegetation around lot -Cripple walls less than 14" are required to be sheathed continuously on one side and fastened to top and bottom plates per R602.9 -Rafters over notched and not connected to ceiling joists at master closet exterior wall -plywood cripple wall at exterior great room -Seal gaps at dead space at great room/stairwell double wall -Secure pex lines at shower bed 2 -Fireblock double wall at stairs-also use approved materials -Complete all Fireblocking at ceiling lines, double walls etc at basement -Fireblock stair landing -fireblock furr out wall to ceiling space in bed 5 -fire block dead space at bed 5 bath -nail all intersecting wall corners together to code -fire block dead space at bed3/4 bath -fire block bed 3/bath wall near window into furr down -provide additional support for furr down in family room to floor joist above where furr down span greater than 4’ un supported -CS-PF at rear slider not nailed to cspf specifications -have engineer address notched cspf header above slider
All Rough Inspection - Residential Passed 8/26/2025 8/26/2025 08/26/2025
Misc
Informational
08/21/2025
PFH at garage is ok Front and back porches are ok to cover Cs-pf at rear is nailed properly and no is ok
Misc
Resolved
08/26/2025
-not further inspections until overgrown vegetation is in compliance maintain overgrown vegetation around lot -Cripple walls less than 14" are required to be sheathed continuously on one side and fastened to top and bottom plates per R602.9 -Rafters over notched and not connected to ceiling joists at master closet exterior wall -plywood cripple wall at exterior great room -Seal gaps at dead space at great room/stairwell double wall -Secure pex lines at shower bed 2 -Fireblock double wall at stairs-also use approved materials -Complete all Fireblocking at ceiling lines, double walls etc at basement -Fireblock stair landing -fireblock furr out wall to ceiling space in bed 5 -fire block dead space at bed 5 bath -nail all intersecting wall corners together to code -fire block dead space at bed3/4 bath -fire block bed 3/bath wall near window into furr down -provide additional support for furr down in family room to floor joist above where furr down span greater than 4’ un supported -CS-PF at rear slider not nailed to cspf specifications -have engineer address notched cspf header above slider
Gas Service Inspection - Residential Passed 8/26/2025 8/26/2025 08/26/2025
G2417.4.1 Test Pressure
Resolved
08/26/2025
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Sidewalk Inspection Partial 9/22/2025 9/22/2025 09/22/2025
Misc
Informational
09/22/2025
9-22-25 PS Sidewalk pre pour, forms in place and aggregate compacted. Approved to pour
Driveway Inspection Partial 9/22/2025 9/22/2025 09/22/2025
Misc
Informational
09/22/2025
9-22-25 PS Driveway approach pre pour, forms in place and aggregate compacted, approved to pour
Sidewalk Inspection Passed 10/1/2025 10/1/2025 10/01/2025
Misc
Informational
09/22/2025
9-22-25 PS Sidewalk pre pour, forms in place and aggregate compacted. Approved to pour 10-1-25 PS Sidewalk meets ADA and LS specs
Driveway Inspection Passed 10/1/2025 10/1/2025 10/01/2025
Misc
Informational
09/22/2025
9-22-25 PS Driveway approach pre pour, forms in place and aggregate compacted, approved to pour 10-1-25 PS Driveway approach meets ADA and LS specs
Documents & Images
Date Uploaded File Type Document Name
02/02/2025 LOT 128 WOODSIDE PERMIT APPLICATION
02/02/2025 128 Woodside Staked
02/02/2025 4365LA PLAN LOT 128 WOODSIDE
02/03/2025 Approved Plans APPROVED PLANS
02/03/2025 Plot Plan APPROVED PLOT PLAN
02/04/2025 Permit Codes Residential Plan Review
02/17/2025 Permit DS Building Permit
02/17/2025 Receipt Receipt for transaction:2025-000948
03/26/2025 3RD Party Insp Report M L Crose 2123 NW Killarney Ln LSMO 3rd Party Footing Inspection Report Pg 1 3-26-25
03/26/2025 3RD Party Insp Report M L Crose 2123 NW Killarney Ln LSMO 3rd Party Footing Inspection Report Pg 2 3-26-25
03/27/2025 Letter INSPECTION SUMMARY
03/27/2025 Letter INSPECTION SUMMARY
04/02/2025 Letter INSPECTION SUMMARY
04/16/2025 Letter INSPECTION SUMMARY
04/16/2025 Letter INSPECTION SUMMARY
04/23/2025 Letter INSPECTION SUMMARY
04/23/2025 Letter INSPECTION SUMMARY
04/30/2025 Letter INSPECTION SUMMARY
04/30/2025 Letter INSPECTION SUMMARY
06/25/2025 Letter INSPECTION SUMMARY
06/25/2025 Letter INSPECTION SUMMARY
06/30/2025 Letter INSPECTION SUMMARY
08/14/2025 Letter INSPECTION SUMMARY
08/14/2025 Letter INSPECTION SUMMARY
08/14/2025 Letter INSPECTION SUMMARY
08/21/2025 Letter INSPECTION SUMMARY
08/21/2025 Letter INSPECTION SUMMARY
08/26/2025 Letter INSPECTION SUMMARY
08/26/2025 Letter INSPECTION SUMMARY
09/05/2025 2025_09_03 2123 NW Killarney Letter
09/05/2025 Receipt Receipt for transaction:2025-006909
09/22/2025 Letter INSPECTION SUMMARY
09/22/2025 Letter INSPECTION SUMMARY
10/01/2025 Letter INSPECTION SUMMARY
10/01/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home