Permit Application Status

PRRES20246285


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20246285
Building Permit - Residential
Issued
NEW DUPLEX
NEW DUPLEX. FINISHED/UNFINISHED BASEMENT. SUSPENDED SLAB. COVERED PATIO. STOP WORK ORDER generated on 07/21/2025 12:00 AM by username 'Dustin Agcopra'. STOP WORK ORDER removed on 08/04/2025 12:00 AM by username 'Dustin Agcopra'.
12/06/2024
12/27/2024
06/09/2025
Locations
Contacts
ROCK CREEK HOMES, Address:6126 METCALF LANE, Phone:(913) 522-1945  
Kevin Guinan, Address:6126 Metcalf Lane  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
PRIDE SERVICES INC, Address:3842 GEORGIA TERR, Phone:(785) 242-9700  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
KEVIN@ROCKCREEKHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Duplex $2,486.52 $2,486.52 Paid 12/27/2024
Water Tap Fee $7,946.00 $7,946.00 Paid 12/27/2024
Water Meter Fee $1,496.06 $1,496.06 Paid 12/27/2024
Sanitary Sewer Development Fee $4,570.00 $4,570.00 Paid 12/27/2024
Right of Way Permit Fee $85.00 $85.00 Paid 12/27/2024
Residential Excise Tax Fee $1,240.32 $1,240.32 Paid 12/27/2024
Outstanding Fees Amount Paid Owing Date Paid
Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid


$75.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Foundation Inspection - Commercial Pending
Occupancy Inspection - Codes Residential Pending
Suspended Slab Inspection Pending
Erosion Control Inspection Residential Pending
Misc
Corrective Action Required
08/04/2025
Maintain overgrown vegetation
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
08/04/2025
7-17-25 Dustin A, Silt fence is down, Storm inlet needs cleaned and curb lone needs cleaned. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 7-21-25 Dustin A, Storm inlet still needs to be cleaned. 8-4-25 Dustin A, All corrections had been made, esc must be maintained throughout project.
Sidewalk Inspection Pending 9/18/2025 9/18/2025
Driveway Inspection Pending 9/18/2025 9/18/2025
Misc
Corrective Action Required
09/11/2025
9-11-25 Dustin A, Dw is formed and compacted. Approved to pour
Footing Inspection - Residential Failed 3/13/2025 03/13/2025
Misc
Corrective Action Required
03/13/2025
Erosion control not in compliance. 3rd party footing inspection denied
Erosion Control Inspection Residential Failed - Stop Work 3/13/2025 3/13/2025 03/13/2025
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
03/13/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. -Erosion control around lot not in compliance -remove rock and dirt from street
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/13/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Footing Inspection - Residential Passed 03/17/2025
Misc
Resolved
03/17/2025
Erosion control not in compliance. 3rd party footing inspection denied
Sewer Service Inspection - R Passed 03/17/2025
Erosion Control Inspection Residential Failed - Stop Work 03/17/2025
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
03/13/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. -Erosion control around lot not in compliance -remove rock and dirt from street
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/13/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Partial 3/18/2025 3/18/2025 03/18/2025
DCM2 ESC DEFICIENT INSTALLATION
Resolved
03/18/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. -Erosion control around lot not in compliance -remove rock and dirt from street
DCM3 ESC REQUIRED 2 DAY
Resolved
03/18/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Misc
Corrective Action Required
03/18/2025
- EROSION CONTROL IN PLACE AT TIME OF INSPECION.
Underslab Electrical Inspection - Residential Passed 3/19/2025 3/19/2025 03/19/2025
Misc
Informational
03/19/2025
- Both 1331,1333
Water Service Inspection - R Passed 3/19/2025 3/19/2025 03/19/2025
Misc
Informational
03/19/2025
- Both 1331,1333
Underslab Plumbing Inspection - Residential Passed 3/27/2025 3/27/2025 03/27/2025
Erosion Control Inspection Residential Failed 5/12/2025 5/12/2025 05/12/2025
Misc
Resolved
05/12/2025
- EROSION CONTROL IN PLACE AT TIME OF INSPECION.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/12/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -maintain silt fence (downed and missing multiple places around lot) -clean trash and debris from lot
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
05/12/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Erosion Control Inspection Residential Partial 5/14/2025 5/14/2025 05/14/2025
DCM3 ESC REQUIRED 2 DAY
Resolved
05/14/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -maintain silt fence (downed and missing multiple places around lot) -clean trash and debris from lot
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
05/14/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Misc
Corrective Action Required
05/14/2025
Maintain overgrown vegetation
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/14/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Gas Service Inspection - Residential Failed 6/24/2025 6/24/2025 06/24/2025
G2417.4.1 Test Pressure
Corrective Action Required
06/24/2025
1331 Bond gas line 1333 INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Rated Assembly Inspection Failed 6/24/2025 6/24/2025 06/24/2025
Misc
Corrective Action Required
06/24/2025
Address penetrations in fire rated roof decking -joist space in basement okay
Electrical Service Inspection Passed 6/24/2025 6/24/2025 06/24/2025
All Rough Inspection - Residential Failed 6/24/2025 6/24/2025 06/24/2025
Misc
Corrective Action Required
06/24/2025
Both sides -address rafter to ceiling joist connections (N and S walls) - 1331 -fire block around beam N wall in basement -tighten anchor bolts where loose throughout basement -fireblock bed 4 S wall into furr down -bond gas line 1333 -seal penetrations in roof decking -address gas pressure not at minimum
All Rough Inspection - Residential Not Ready 6/27/2025 6/27/2025 06/27/2025
Misc
Corrective Action Required
06/24/2025
Both sides -address rafter to ceiling joist connections (N and S walls) - 1331 -fire block around beam N wall in basement -tighten anchor bolts where loose throughout basement -fireblock bed 4 S wall into furr down 1333 -seal penetrations in roof decking (see vent)
Rated Assembly Inspection Failed 6/27/2025 6/27/2025 06/27/2025
Misc
Corrective Action Required
06/24/2025
Address penetrations in fire rated roof decking (see vent, not addressed) -joist space in basement okay
Gas Service Inspection - Residential Passed 6/27/2025 6/27/2025 06/27/2025
G2417.4.1 Test Pressure
Resolved
06/27/2025
1331 Bond gas line 1333 INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
All Rough Inspection - Residential Passed 7/2/2025 7/2/2025 07/02/2025
Misc
Resolved
07/02/2025
Both sides -address rafter to ceiling joist connections (N and S walls) - 1331 -fire block around beam N wall in basement -tighten anchor bolts where loose throughout basement -fireblock bed 4 S wall into furr down 1333 -seal penetrations in roof decking (see vent)
Rated Assembly Inspection Partial 7/2/2025 7/2/2025 07/02/2025
Misc
Informational
07/02/2025
Attic space -okay -joist space in basement okay
Erosion Control Inspection Residential Failed 7/17/2025 7/17/2025 07/17/2025
Misc
Corrective Action Required
05/14/2025
Maintain overgrown vegetation
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/14/2025
7-17-25 Dustin A, Silt fence is down, Storm inlet needs cleaned and curb lone needs cleaned. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Rated Assembly Inspection Passed 7/21/2025 7/21/2025 07/21/2025
Misc
Resolved
07/21/2025
Attic space -okay -joist space in basement okay
Sidewalk Inspection Failed 7/21/2025 7/21/2025 07/21/2025
Misc
Corrective Action Required
07/21/2025
7-21-25 Dustin A, Sidewalk has broken panels and a panel that was replaced without a pre pour inspection.
Erosion Control Inspection Residential Failed - Stop Work 7/21/2025 7/21/2025 07/31/2025
Misc
Corrective Action Required
07/17/2025
Maintain overgrown vegetation
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/17/2025
7-17-25 Dustin A, Silt fence is down, Storm inlet needs cleaned and curb lone needs cleaned. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 7-21-25 Dustin A, Storm inlet still needs to be cleaned. 7-31-25 Dustin A, All properties on Winthrop are STOP WORKED due to non compliance . 1. Concrete washout area is over flowing onto street. All concrete debris needs to be removed from street, washout needs to be maintained. 2. All silt needs to be cleaned from street and proper erosion control needs to be in place to keep this from happening. 3. Storm drains need to be protected, silt socks need to be replaced if they are compacted with mud or debris . Should not have grass growing out of them . After installed they need to be maintained . 4. All properties need to have erosion control in place and in working order. Must be maintained throughout 5. Before any work can be done on site an erosion control inspection will need to be scheduled. 6. NO WORK is allowed on site until these issues have been corrected.
Erosion Control Inspection Residential Partial 8/4/2025 8/4/2025 08/04/2025
Misc
Corrective Action Required
07/21/2025
Maintain overgrown vegetation
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/21/2025
7-17-25 Dustin A, Silt fence is down, Storm inlet needs cleaned and curb lone needs cleaned. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 7-21-25 Dustin A, Storm inlet still needs to be cleaned. 8-4-25 Dustin A, All corrections had been made, esc must be maintained throughout project.
Driveway Inspection Partial 9/11/2025 9/11/2025 09/11/2025
Misc
Corrective Action Required
09/11/2025
9-11-25 Dustin A, Dw is formed and compacted. Approved to pour
Sidewalk Inspection Partial 9/11/2025 9/11/2025 09/11/2025
Misc
Corrective Action Required
07/21/2025
7-21-25 Dustin A, Sidewalk has broken panels and a panel that was replaced without a pre pour inspection. 9-11-25 Dustin A, sw panels that failed due to cracks and being poured without a inspection have been removed, formed and compacted as well as the rest of sw. Slopes are in compliance. Approved to pour
Documents & Images
Date Uploaded File Type Document Name
12/06/2024 Application - Lot 42
12/06/2024 Tax Form - Lot 42
12/11/2024 Permit Codes Residential Plan Review
12/17/2024 Approved Plans APPROVED PLANS
12/17/2024 Plot Plan APPROVED PLOT PLAN
12/17/2024 Permit Codes Residential Plan Review
12/27/2024 Permit DS Building Permit
12/27/2024 Receipt Receipt for transaction: 2024-009674
03/10/2025 Lot 42 Pier Inspection
03/10/2025 Lot 42 Footing Inspection
03/13/2025 Letter INSPECTION SUMMARY
03/13/2025 Letter Stop Work Order
03/17/2025 Letter INSPECTION SUMMARY
03/17/2025 Letter INSPECTION SUMMARY
03/17/2025 Letter Stop Work Order
03/18/2025 Letter INSPECTION SUMMARY
03/19/2025 Letter INSPECTION SUMMARY
03/19/2025 Letter INSPECTION SUMMARY
03/27/2025 Letter INSPECTION SUMMARY
04/25/2025 2025_04_11_1333-35 SW Winthrop Ter_GSlab_Sealed
05/12/2025 Letter INSPECTION SUMMARY
05/14/2025 Letter INSPECTION SUMMARY
06/24/2025 Letter INSPECTION SUMMARY
06/24/2025 Letter INSPECTION SUMMARY
06/24/2025 Letter INSPECTION SUMMARY
06/24/2025 Letter INSPECTION SUMMARY
06/27/2025 Letter INSPECTION SUMMARY
06/27/2025 Letter INSPECTION SUMMARY
06/27/2025 Letter INSPECTION SUMMARY
07/02/2025 Letter INSPECTION SUMMARY
07/02/2025 Letter INSPECTION SUMMARY
07/17/2025 Letter INSPECTION SUMMARY
07/17/2025 Letter INSPECTION SUMMARY
07/21/2025 Letter INSPECTION SUMMARY
07/21/2025 Letter INSPECTION SUMMARY
07/21/2025 Letter Stop Work Order
07/21/2025 Letter Stop Work Order
07/31/2025 Letter INSPECTION SUMMARY
07/31/2025 Letter Stop Work Order
08/04/2025 Letter INSPECTION SUMMARY
09/11/2025 Letter INSPECTION SUMMARY
09/11/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home