Permit Application Status

PRRES20245223


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20245223
Building Permit - Residential
Issued
NEW OTHER (RESIDENTIAL)
NEW INGROUND POOL Project has two addressed 2120 and 2124 combined two lots into one parcel # needs to be updated. Development Center Shared ID 12/18/2024 1:54 PM
10/03/2024
10/03/2024
Locations
Contacts
SWIM THINGS INC, Address:3010 W 40 HWY, Phone:(816) 224-2600  
DALLAS@SWIMTHINGS.COM  
HOWERTON PLUMBING LLC, Address:195 NW AA HWY, Phone:(816) 694-0303  
A & A ELECTRICAL INC, Address:705 SQUIRE CT, Phone:(816) 847-1902  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 10/03/2024 10/03/2024
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Other $360.00 $360.00 Paid 10/03/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Residential Pending
Plot Plan Inspection Pending
Pool Final - Residential Pending
Pool Steel/Bonding - Residential Pending
Misc
Informational
05/30/2025
-(4) points at shell and skimmer basket bond to perimeter approved -perimeter and hand rail bonded
Pool Steel/Bonding - Residential Failed 12/17/2024 12/17/2024 12/17/2024
Misc
Corrective Action Required
12/17/2024
No address. No inspection performed
Pool Steel/Bonding - Residential Partial 12/19/2024 12/19/2024 12/19/2024
Misc
Corrective Action Required
12/17/2024
No address. No further inspections will be performed until site address is clearly posted -(4) points at shell and skimmer basket bond to perimeter appproved
Pool Steel/Bonding - Residential Failed 5/29/2025 5/29/2025 05/29/2025
Misc
Informational
05/29/2025
-(4) points at shell and skimmer basket bond to perimeter approved
Misc
Corrective Action Required
05/29/2025
5/29/25 -Perimeter surface bonding must comply with 680.26(B)(2)(a) or (2)(b). Single rebar bent around pool does not comply with either method and is not attached to the pool shell bonding at the min (4) points. Provide 36" of steel rebar at the deck, attached to the pool shell conductors and running to the equipment pad, or install a min 8 awg bare copper conductor secured 18" to 24", from the inside of the walls of the pool, 4" to 6" below subgrade, attached to shell bonding and continuing to equipment pad.
Pool Steel/Bonding - Residential Partial 5/30/2025 5/30/2025 05/30/2025
Misc
Informational
05/29/2025
-(4) points at shell and skimmer basket bond to perimeter approved -perimeter and hand rail bonded
Misc
Resolved
05/30/2025
5/29/25 -Perimeter surface bonding must comply with 680.26(B)(2)(a) or (2)(b). Single rebar bent around pool does not comply with either method and is not attached to the pool shell bonding at the min (4) points. Provide 36" of steel rebar at the deck, attached to the pool shell conductors and running to the equipment pad, or install a min 8 awg bare copper conductor secured 18" to 24", from the inside of the walls of the pool, 4" to 6" below subgrade, attached to shell bonding and continuing to equipment pad.
Documents & Images
Date Uploaded File Type Document Name
10/03/2024 Application Form APPLICATION
10/03/2024 Plot Plan APPROVED PLOT PLAN
10/03/2024 Application Form FENCING AGREEMENT
10/03/2024 Permit DS Building Permit
10/03/2024 Receipt Receipt for transaction:2024-008080
12/17/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
05/29/2025 Letter INSPECTION SUMMARY
05/30/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home