Summary
PRRES20244953
Building Permit - Residential
Issued
DJ23 INVESTMENTS LLC
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - UNFINISHED BASEMENT
09/18/2024
09/26/2024
03/22/2025
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
DJ23 INVESTMENTS LLC, Address:7200 W 132ND ST  
Doug Jenson, Address:11010 Nora Dodge Dr, Phone:(816) 266-0685  
DOUG@APGKC.COM  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 09/26/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 09/26/2024
8331507-Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 09/26/2024
8331401-Water Tap Fee $3,973.00 $3,973.00 Paid 09/26/2024
8350015-Water Meter Fee $748.03 $748.03 Paid 09/26/2024
9110078-Valuation Fee New Single Family $1,191.46 $1,191.46 Paid 09/26/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 10/18/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 02/10/2025
Outstanding Fees Amount Paid Owing Date Paid
9110078-Temporary Occupancy Fee $50.00 $0.00 $50.00 Not Paid


$50.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Codes Residential Pending
Misc
Corrective Action Required
02/27/2025
-sod -splash blocks and sump pump discharge to extend 36” from foundation -address pending driveway inspection -will check final grade at later date (to much snow in ground) -back porch stairs has risers greater than 7 3/4 of an inch in height -backyard security lights are covered with plastic sheeting -seal gas line at exterior siding Passed for TCO only
Erosion Control Inspection Residential Pending
Miscellaneous Correction
Informational
02/27/2025
Erosion is in place at the time of inspection
Erosion Control Inspection Residential Partial 10/4/2024 10/04/2024
Miscellaneous Correction
Informational
10/04/2024
Full erosion control measures are in place and must be maintained until CofO
Footing Inspection - Residential Failed 10/4/2024 10/4/2024 10/04/2024
Miscellaneous Correction
Corrective Action Required
10/04/2024
Two joints at the S/W corner of the basement do not have 24 inches of steel overlap One section of the basement east wall is missing its form board
Footing Inspection - Residential Not Ready 10/7/2024 10/07/2024
Miscellaneous Correction
Corrective Action Required
10/04/2024
Two joints at the S/W corner of the basement do not have 24 inches of steel overlap One section of the basement east wall is missing its form board No improvements were made Not ready for re inspection
Erosion Control Inspection Residential Partial 10/7/2024 10/07/2024
Miscellaneous Correction
Informational
10/04/2024
Full erosion control measures are in place and must be maintained until CofO
Footing Inspection - Residential Passed 10/7/2024 10/07/2024
Miscellaneous Correction
Resolved
10/07/2024
Two joints at the S/W corner of the basement do not have 24 inches of steel overlap One section of the basement east wall is missing its form board No improvements were made Not ready for re inspection
Erosion Control Inspection Residential Partial 10/22/2024 10/22/2024
Miscellaneous Correction
Informational
10/07/2024
Full erosion control measures are in place and must be maintained until CofO
Underslab Plumbing Inspection - Residential Passed 10/22/2024 10/22/2024 10/22/2024
All Rough Inspection - Residential Failed 11/6/2024 11/6/2024 11/06/2024
Miscellaneous Correction
Corrective Action Required
11/06/2024
Garage portal PFH inspection only - Exterior sheeting does not extend to the double top plate - Anchor bolts are not located in the middle 1/3 of bottom plate This is a partial inspection only
Erosion Control Inspection Residential Failed 11/6/2024 11/06/2024
Miscellaneous Correction
Resolved
11/06/2024
Full erosion control measures are in place and must be maintained until CofO
Miscellaneous Correction
Corrective Action Required
11/06/2024
Silt fence and or straw waddle is missing at the front of the lot on west side Full erosion control measures must be in place and properly maintained until CofO
All Rough Inspection - Residential Failed 11/13/2024 11/13/2024 11/13/2024
Miscellaneous Correction
Resolved
11/13/2024
Garage portal PFH inspection only - Exterior sheeting does not extend to the double top plate - Anchor bolts are not located in the middle 1/3 of bottom plate This is a partial inspection only
Miscellaneous Correction
Corrective Action Required
11/13/2024
- Garage PFH anchor bolts are not located within the center 1/3 of the bottom plate - Garage PFH anchor bolts are not tightened down to the bottom plate - Exterior garage PFH sheeting passed and is okay to cover
Erosion Control Inspection Residential Failed 11/26/2024 11/26/2024
Miscellaneous Correction
Resolved
11/26/2024
Silt fence and or straw waddle is missing at the front of the lot on west side Full erosion control measures must be in place and properly maintained until CofO
Miscellaneous Correction
Corrective Action Required
11/26/2024
Repair damaged silt fence along the front of the lot adjacent to the street Full erosion control measures must be in place and properly maintained until CofO
All Rough Inspection - Residential Failed 11/26/2024 11/26/2024 11/26/2024
Miscellaneous Correction
Resolved
11/26/2024
- Garage PFH anchor bolts are not located within the center 1/3 of the bottom plate - Garage PFH anchor bolts are not tightened down to the bottom plate - Exterior garage PFH sheeting passed and is okay to cover
Miscellaneous Correction
Resolved
12/05/2024
Install roof boot for plumbing in bathroom 2, primary bathroom and laundry room Provide information on black tie down screws used in the garage Place garage anchor bolts in the middle 1/3 of bottom plate 2 stud pack is not installed for GT in garage along east wall Steel Ibeam in basement along the west wall does not bear on 3 inches of concrete in the pocket 2x10 in the basement above electrical panel has holes drilled within 2 inches of it’s edge for electrical lines Ibeam in basement does not bear 3 inches in the concrete pocket at the NW corner together Gas lines are not installed at the time of all rough inspection
Miscellaneous Correction
Corrective Action Required
12/05/2024
Install roof boot for plumbing in bathroom 2, primary bathroom and laundry room Provide information on black tie down screws used in the garage Place garage anchor bolts in the middle 1/3 of bottom plate 2 stud pack is not installed for GT in garage along east wall Steel Ibeam in basement along the west wall does not bear on 3 inches of concrete in the pocket 2x10 in the basement above electrical panel has holes drilled within 2 inches of it’s edge for electrical lines Ibeam in basement does not bear 3 inches in the concrete pocket at the NW corner together Gas lines are not installed at the time of all rough inspection -House was locked and no access code was left to get in -Provide better access other than a plank to walk on over an open stoop to thre front door No access. Not Ready 12/05/24 KBEARD 8:30am
Gas Service Inspection - Residential Not Ready 11/26/2024 11/26/2024 11/26/2024
Miscellaneous Correction
Corrective Action Required
11/26/2024
Gas line and bonding was not installed at the time of inspection Not ready for inspection
Electrical Service Inspection Passed 11/26/2024 11/26/2024 11/26/2024
Gas Service Inspection - Residential Failed 12/5/2024 12/05/2024
Miscellaneous Correction
Corrective Action Required
11/26/2024
Gas line and bonding was not installed at the time of inspection Not ready for inspection
Miscellaneous Correction
Corrective Action Required
12/05/2024
No access
All Rough Inspection - Residential Failed 12/5/2024 12/5/2024 12/05/2024
Miscellaneous Correction
Corrective Action Required
11/26/2024
Install roof boot for plumbing in bathroom 2, primary bathroom and laundry room Provide information on black tie down screws used in the garage Place garage anchor bolts in the middle 1/3 of bottom plate 2 stud pack is not installed for GT in garage along east wall Steel Ibeam in basement along the west wall does not bear on 3 inches of concrete in the pocket 2x10 in the basement above electrical panel has holes drilled within 2 inches of it’s edge for electrical lines Ibeam in basement does not bear 3 inches in the concrete pocket at the NW corner together Gas lines are not installed at the time of all rough inspection
All Rough Inspection - Residential Failed 12/10/2024 12/10/2024 12/10/2024
Miscellaneous Correction
Corrective Action Required
12/05/2024
Provide information on black tie down screws used in the garage Steel Ibeam in basement along the west wall does not bear on 3 inches of concrete in the pocket 2x10 in the basement above electrical panel has Ibeam in basement does not bear 3 inches in the concrete pocket at the NW corner together Gas lines ( no presure )
Gas Service Inspection - Residential Failed 12/10/2024 12/10/2024
Miscellaneous Correction
Resolved
12/10/2024
Gas line and bonding was not installed at the time of inspection Not ready for inspection
Miscellaneous Correction
Resolved
12/10/2024
No access
Misc
Corrective Action Required
12/10/2024
- No pressure on gauge.
All Rough Inspection - Residential Passed 12/11/2024 12/11/2024 12/11/2024
Miscellaneous Correction
Resolved
12/11/2024
Provide information on black tie down screws used in the garage Steel Ibeam in basement along the west wall does not bear on 3 inches of concrete in the pocket 2x10 in the basement above electrical panel has Ibeam in basement does not bear 3 inches in the concrete pocket at the NW corner together Gas lines ( no presure )
Gas Service Inspection - Residential Passed 12/16/2024 12/16/2024 12/16/2024
Misc
Resolved
12/16/2024
- No pressure on gauge.
Sewer Service Inspection - R Passed 12/18/2024 12/18/2024 12/18/2024
Water Service Inspection - R Partial 12/18/2024 12/18/2024
Miscellaneous Correction
Informational
12/18/2024
Poly ran about 15 feet out from the foundation and is okay to cover This is a partial pass only
Water Service Inspection - R Passed 12/19/2024 12/19/2024
Miscellaneous Correction
Resolved
12/19/2024
Poly ran about 15 feet out from the foundation and is okay to cover This is a partial pass only
Driveway Inspection Partial 2/6/2025 2/6/2025 02/06/2025
Misc
Informational
02/06/2025
02/06/25 Jamie S, DW is compacted and meets city requirements. Approved to pour.
Occupancy Inspection - Codes Residential Failed 2/19/2025 2/19/2025 02/19/2025
Misc
Corrective Action Required
02/19/2025
-sod -missing gutters -splash blocks and sump pump discharge to extend 36” from foundation -provide properly illuminated address -provide locking hardware to at front door -address pending driveway inspection -provide issued lawn irrigation permit -will check final grade at later date (to much snow in ground) -provide self closing and latching door for garage -provide attic access cover -seal penetrations above garage doors -stairs in garage risers difference greater than 3/8” -address stairs not installed at rear slider
Occupancy Inspection - Codes Residential Ready for Temp CO 2/26/2025 2/27/2025 02/27/2025
Misc
Corrective Action Required
02/19/2025
-sod -splash blocks and sump pump discharge to extend 36” from foundation -address pending driveway inspection -will check final grade at later date (to much snow in ground) -back porch stairs has risers greater than 7 3/4 of an inch in height -backyard security lights are covered with plastic sheeting -seal gas line at exterior siding Passed for TCO only
Plot Plan Inspection Passed 2/27/2025 02/27/2025
Erosion Control Inspection Residential Partial 2/27/2025 02/27/2025
Miscellaneous Correction
Resolved
02/27/2025
Repair damaged silt fence along the front of the lot adjacent to the street Full erosion control measures must be in place and properly maintained until CofO
Miscellaneous Correction
Informational
02/27/2025
Erosion is in place at the time of inspection
Driveway Inspection Passed 2/27/2025 2/27/2025 02/27/2025
Misc
Informational
02/06/2025
02/06/25 Jamie S, DW is compacted and meets city requirements. Approved to pour. 02/27/25 Jamie S, DW slopes are within city standards.
Documents & Images
Date Uploaded File Type Document Name
09/18/2024 RS 126 License_Tax_Application 9_18_24
09/18/2024 RS 126 Permit Application Signed 9_18_24
09/18/2024 LOT 126 FINAL
09/23/2024 Permit Codes Residential Plan Review
09/26/2024 Approved Plans APPROVED PLANS
09/26/2024 Plot Plan APPROVED PLOT PLAN
09/26/2024 Approved Plans APPROVED TRUSS LAYOUT
09/26/2024 Permit Codes Residential Plan Review
09/26/2024 Permit DS Building Permit
09/26/2024 Receipt Receipt for transaction:2024-007957
10/04/2024 Letter INSPECTION SUMMARY
10/04/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/18/2024 Receipt Receipt for transaction:2024-008437
10/22/2024 Letter INSPECTION SUMMARY
10/22/2024 Letter INSPECTION SUMMARY
11/06/2024 Letter INSPECTION SUMMARY
11/06/2024 Letter INSPECTION SUMMARY
11/13/2024 Letter INSPECTION SUMMARY
11/26/2024 Letter INSPECTION SUMMARY
11/26/2024 Letter INSPECTION SUMMARY
11/26/2024 Letter INSPECTION SUMMARY
11/26/2024 Letter INSPECTION SUMMARY
12/05/2024 Letter INSPECTION SUMMARY
12/10/2024 Letter INSPECTION SUMMARY
12/10/2024 Letter INSPECTION SUMMARY
12/11/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
02/06/2025 Letter INSPECTION SUMMARY
02/10/2025 Receipt Receipt for transaction:2025-000865
02/19/2025 Letter INSPECTION SUMMARY
02/27/2025 Letter INSPECTION SUMMARY
02/27/2025 Letter INSPECTION SUMMARY
02/27/2025 Letter INSPECTION SUMMARY
02/27/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home