Permit Application Status

PRRES20241323


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20241323
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED AND UNFINISHED BASEMENT - UNCOVERED DECK - ROOF TRUSSES ( DEF )
03/21/2024
03/27/2024
07/30/2024
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
CMH PARKS INC, Address:5000 CLAYTON RD  
Doug Jenson, Address:11010 Nora Dodge Dr, Phone:(816) 266-0685  
DOUG@APGKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 03/27/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 03/27/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 03/27/2024
8331401-Water Tap Fee $3,760.00 $3,760.00 Paid 03/27/2024
8350015-Water Meter Fee $680.46 $680.46 Paid 03/27/2024
9110078-Valuation Fee New Single Family $1,521.36 $1,521.36 Paid 03/27/2024
9110080-3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 07/18/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Partial 4/5/2024 04/05/2024
Miscellaneous Correction
Informational
04/05/2024
Full erosion control is in place and must be maintained until CofO
Footing Inspection - Residential Passed 4/5/2024 04/05/2024
Miscellaneous Correction
Informational
04/05/2024
Footing passed by a third party. No mention of piers were in the footing report
Sewer Service Inspection - R Passed 4/11/2024 4/11/2024 04/11/2024
Water Service Inspection - R Partial 4/11/2024 04/11/2024
Miscellaneous Correction
Informational
04/11/2024
-PEX has been run out from the foundation towards the street about 25 feet. Okay to beck fill -Remaining water will be scheduled at a later date -This is a partial pass only
Underslab Plumbing Inspection - Residential Passed 4/12/2024 4/12/2024 04/12/2024
Water Service Inspection - R Passed 4/12/2024 04/12/2024
Miscellaneous Correction
Informational
04/11/2024
-PEX has been run out from the foundation towards the street about 25 feet. Okay to beck fill -Remaining water will be scheduled at a later date -This is a partial pass only
Erosion Control Inspection Residential Partial 5/3/2024 05/03/2024
Miscellaneous Correction
Resolved
05/03/2024
Full erosion control is in place and must be maintained until CofO
Miscellaneous Correction
Informational
05/03/2024
Full erosion control is in place and must be maintained until CofO
All Rough Inspection - Residential Failed 5/10/2024 5/10/2024 05/10/2024
Miscellaneous Correction
Corrective Action Required
05/10/2024
Garage portal framing is not to code. See code R602.10.6.2, R602.10.5 and table R602.6.4 This inspection was for garage portal framing only
Erosion Control Inspection Residential Failed 5/15/2024 05/15/2024
Miscellaneous Correction
Resolved
05/15/2024
Full erosion control is in place and must be maintained until CofO
Miscellaneous Correction
Corrective Action Required
05/15/2024
Repair or replace silt fence at the street where it is damaged. Full erosion control must be maintained until CofO
All Rough Inspection - Residential Failed 5/20/2024 5/20/2024 05/20/2024
Miscellaneous Correction
Resolved
05/20/2024
Garage portal framing is not to code. See code R602.10.6.2, R602.10.5 and table R602.6.4 This inspection was for garage portal framing only
Miscellaneous Correction
Corrective Action Required
05/20/2024
- Garage CS-PF needs to be nailed across the top into the top plate - Front porch truss tie down screws can not be verified due to being covered - Some of the front porch truss hangers are covered and can not be verified This was a partial all rough inspection for the front porch and garage portal only
All Rough Inspection - Residential Failed 5/24/2024 5/24/2024 05/24/2024
Miscellaneous Correction
Resolved
05/24/2024
- Garage CS-PF needs to be nailed across the top into the top plate - Front porch truss tie down screws can not be verified due to being covered - Some of the front porch truss hangers are covered and can not be verified This was a partial all rough inspection for the front porch and garage
Misc
Informational
05/24/2024
-Garage portal frame okay to cover
Misc
Corrective Action Required
05/24/2024
Install truss screws correctly above front porch
Electrical Service Inspection Passed 6/3/2024 6/3/2024 06/03/2024
Gas Service Inspection - Residential Passed 6/3/2024 6/3/2024 06/03/2024
All Rough Inspection - Residential Failed 6/3/2024 6/3/2024 06/03/2024
Misc
Informational
05/24/2024
-Garage portal frame okay to cover
Misc
Resolved
06/03/2024
Misc
Corrective Action Required
06/03/2024
-Truss to box wall at ceiling in master north side needs re-nailed or add 2x4 bracing -J3 truss at northwest corner crooked-needs straightened -Secure 2x4 in closet of bedroom 2 -Add 2x4 at upstairs guest bathroom -Address bathroom vent fan in basement bathroom-not mounted -Address loose fire blocking every ten feet in basement
All Rough Inspection - Residential Failed 6/6/2024 6/6/2024 06/06/2024
Misc
Informational
06/03/2024
-Garage portal frame okay to cover
Misc
Resolved
06/06/2024
-Truss to box wall at ceiling in master north side needs re-nailed or add 2x4 bracing -J3 truss at northwest corner crooked-needs straightened -Secure 2x4 in closet of bedroom 2 -Add 2x4 at upstairs guest bathroom -Address bathroom vent fan in basement bathroom-not mounted -Address loose fire blocking every ten feet in basement
Miscellaneous Correction
Corrective Action Required
06/06/2024
-Have engineer address over bored floor/ceiling joist in living room for 3 inch plumbing waste line -Living room triple window header is not to approved plan -Small garage attic access is not in code compliance of 30 inches of head room space
All Rough Inspection - Residential Failed 6/7/2024 6/7/2024 06/07/2024
Misc
Resolved
06/07/2024
-Garage portal frame okay to cover
Miscellaneous Correction
Corrective Action Required
06/06/2024
-Have engineer address over bored floor/ceiling joist in living room for 3 inch plumbing waste line. -Engineers letter was never uploaded for review before site inspection
Erosion Control Inspection Residential Partial 6/10/2024 06/10/2024
Miscellaneous Correction
Corrective Action Required
05/15/2024
Repair or replace silt fence at the street where it is damaged. Full erosion control must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/10/2024
6-10-24 Dustin A, EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Street needs to be cleaned
Erosion Control Inspection Residential Passed 6/13/2024 6/13/2024 06/10/2024
Miscellaneous Correction
Corrective Action Required
06/10/2024
Repair or replace silt fence at the street where it is damaged. Full erosion control must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/10/2024
6-10-24 Dustin A, EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Street needs to be cleaned 6-10-24 Dustin A, Street and curbs have been cleaned. Silt fence reestablished.
All Rough Inspection - Residential Passed 6/11/2024 6/11/2024 06/11/2024
Miscellaneous Correction
Resolved
06/11/2024
-Have engineer address over bored floor/ceiling joist in living room for 3 inch plumbing waste line. -Engineers letter was never uploaded for review before site inspection
Piers/Caissons Inspection - Residential Passed 7/8/2024 7/8/2024 07/08/2024
Driveway Inspection Partial 7/10/2024 7/10/2024 07/10/2024
Misc
Informational
07/10/2024
7-10-24 PS Driveway approach pre pour, forms in place, aggregate compacted, approved to pour
Sidewalk Inspection Partial 7/10/2024 7/10/2024 07/10/2024
Misc
Informational
07/10/2024
7-10-24 PS Sidewalk pre pour, forms in place, aggregate compacted, approved to pour
Erosion Control Inspection Residential Partial 7/23/2024 07/23/2024
Miscellaneous Correction
Informational
07/23/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 7/25/2024 7/25/2024 07/25/2024
Misc
Corrective Action Required
07/25/2024
1929 SW Merryman. Occupancy •Front porch needs a guard rail installed facing th East •Stairwell going down to the basement does not have the required 36 inches of travel distance at the platform Sod, sump pump extension and splash pads are not installed
Driveway Inspection Passed 7/26/2024 07/26/2024
Misc
Informational
07/10/2024
7-10-24 PS Driveway approach pre pour, forms in place, aggregate compacted, approved to pour 7-26-24 Dustin A, DW is poured to city specs and slopes are in compliance. Passed
Sidewalk Inspection Failed 7/26/2024 07/26/2024
Misc
Informational
07/10/2024
7-10-24 PS Sidewalk pre pour, forms in place, aggregate compacted, approved to pour 7-26-24 Dustin A, SW is poured, There are 2 panels on right side of drive that do not pass ADA compliance. (Marked with pink paint). I talked with Colby ( contractor ) and he said they would be out Monday to replace. I talked with codes inspector as well and it will be ok to receive TCO.
Plot Plan Inspection Passed 7/29/2024 07/29/2024
Occupancy Inspection - Codes Residential Full C of O 7/30/2024 7/30/2024 07/30/2024
Misc
Resolved
07/30/2024
Documents & Images
Date Uploaded File Type Document Name
03/21/2024 MN 134 License_Tax_Application signed
03/21/2024 MN 134 LS Residental Permit Application_1 Signed
03/26/2024 Approved Plans APPROVED PLANS
03/26/2024 Plot Plan APPROVED PLOT PLAN
03/26/2024 Permit Codes Residential Plan Review
03/27/2024 Permit DS Building Permit
03/27/2024 Receipt Receipt for transaction:2024-001930
04/01/2024 3RD Party Insp Report 134 Manor at Stoney Creek - Subgrade- signed
04/04/2024 134 Manor at Stoney Creek - FTG-Signed
04/05/2024 Letter INSPECTION SUMMARY
04/05/2024 Letter INSPECTION SUMMARY
04/11/2024 Letter INSPECTION SUMMARY
04/11/2024 Letter INSPECTION SUMMARY
04/12/2024 Letter INSPECTION SUMMARY
04/12/2024 Letter INSPECTION SUMMARY
04/20/2024 240617 Layout
04/20/2024 240617 Seals
04/22/2024 Approved Plans APPROVED TRUSS PACKAGE
05/03/2024 Letter INSPECTION SUMMARY
05/06/2024 Engineers Reponse Letter - 134 MN - Devotion
05/10/2024 Letter INSPECTION SUMMARY
05/15/2024 Letter INSPECTION SUMMARY
05/15/2024 134 Manor at Stoney Creek - Column Pad-Signed
05/20/2024 Letter INSPECTION SUMMARY
05/24/2024 Letter INSPECTION SUMMARY
06/06/2024 Letter INSPECTION SUMMARY
06/07/2024 Letter INSPECTION SUMMARY
06/07/2024 Letter INSPECTION SUMMARY
06/07/2024 Letter INSPECTION SUMMARY
06/07/2024 Letter INSPECTION SUMMARY
06/07/2024 AVITIAL - 134 SC - JOIST REPAIR - 240607
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/11/2024 Letter INSPECTION SUMMARY
07/08/2024 Letter INSPECTION SUMMARY
07/10/2024 Letter INSPECTION SUMMARY
07/10/2024 Letter INSPECTION SUMMARY
07/18/2024 Receipt Receipt for transaction:2024-005940
07/23/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter INSPECTION SUMMARY
07/26/2024 Letter INSPECTION SUMMARY
07/26/2024 Letter INSPECTION SUMMARY
07/30/2024 Letter Codes Final Certificate of Occupancy
07/30/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home