Permit Application Status

PRRES20233392


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20233392
Building Permit - Residential
Certificate of Occupancy
NEW DUPLEX
NEW DUPLEX - UNFINISHED BASEMENT - ROOF TRUSSES -
07/13/2023
07/24/2023
03/04/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
SAVANNA@SUMMITHOMESKC.COM  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Duplex $2,914.95 $2,914.95 Paid 07/24/2023
Sanitary Sewer Development Fee $4,318.00 $4,318.00 Paid 07/24/2023
Right of Way Permit Fee $85.00 $85.00 Paid 07/24/2023
Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 07/24/2023
Water Tap Fee $7,520.00 $7,520.00 Paid 07/24/2023
Water Meter Fee $1,360.92 $1,360.92 Paid 07/24/2023
Not Ready Inspection Fee $75.00 $75.00 Paid 12/11/2023
Not Ready Inspection Fee $75.00 $75.00 Paid 12/14/2023
Temporary Occupancy Fee $50.00 $50.00 Paid 03/01/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - R Failed 8/21/2023 (1:15) 8/21/2023 08/21/2023
Miscellaneous Correction
Informational
08/21/2023
3744 sewer passed only. 3746 sewer will be scheduled at a later date. This is a partial pass only.
Underslab Plumbing Inspection - Residential Failed 8/22/2023 8/22/2023 08/22/2023
Miscellaneous Correction
Informational
08/22/2023
Footing inspection must pass before an under ground plumbing can be completed. Have a third party inspection letter uploaded since the footing has already been completed without a city inspection
Water Service Inspection - R Failed 8/22/2023 8/22/2023 08/22/2023
Miscellaneous Correction
Corrective Action Required
08/22/2023
Water at 3744 passed. 3746 water will be scheduled at a later date. This is a partial pass only.
Footing Inspection - Residential Passed 8/23/2023 08/23/2023
Misc
Informational
08/23/2023
Footing passed by a third party. Piers were not mentioned in third party footing inspection
Erosion Control Inspection Residential Partial 8/23/2023 08/23/2023
Miscellaneous Correction
Informational
08/23/2023
Full erosion control is needed until occupancy. Keep the street free from rocks. Erosion control is in place at this time.
Sewer Service Inspection - R Passed 8/23/2023 (9:15) 8/23/2023 08/23/2023
Miscellaneous Correction
Resolved
08/23/2023
3744 sewer passed only. 3746 sewer will be scheduled at a later date. This is a partial pass only.
Water Service Inspection - R Passed 8/23/2023 08/23/2023
Miscellaneous Correction
Resolved
08/23/2023
Water at 3744 passed. 3746 water will be scheduled at a later date. This is a partial pass only.
Erosion Control Inspection Residential Failed 8/25/2023 08/25/2023
Miscellaneous Correction
Informational
08/23/2023
Full erosion control is needed until occupancy. Keep the street free from rocks. Erosion control is in place at this time.
Miscellaneous Correction
Corrective Action Required
08/25/2023
Erosion control is not in place after back filling of the foundation. Erosion must be maintained until occupancy.
Underslab Plumbing Inspection - Residential Not Ready 8/25/2023 8/25/2023 08/25/2023
Miscellaneous Correction
Informational
08/22/2023
Footing inspection must pass before an under ground plumbing can be completed. Have a third party inspection letter uploaded since the footing has already been completed without a city inspection
Misc
Corrective Action Required
08/25/2023
-clear gravel from drain tile for underslab inspection
Underslab Plumbing Inspection - Residential Passed 8/28/2023 8/28/2023 08/28/2023
Miscellaneous Correction
Resolved
08/28/2023
Misc
Resolved
08/28/2023
Erosion Control Inspection Residential Failed 8/29/2023 08/29/2023
Miscellaneous Correction
Informational
08/25/2023
Full erosion control is needed until occupancy. Keep the street free from rocks. Erosion control is in place at this time.
Miscellaneous Correction
Corrective Action Required
08/25/2023
Erosion control is not in place after back filling of the foundation. Erosion must be maintained until occupancy.
Miscellaneous Correction
Corrective Action Required
08/29/2023
Full erosion control of the property is not in place. There is dirt in the street that needs to be cleaned up. Full erosion control must be maintained until full CO. No inspections will proceed until erosion control is achieved and dirt and rock is removed from the street. Erosion control is also needed on the north lot adjacent to 3744. 08/29/2023. KBEARD
All Rough Inspection - Residential Failed 9/28/2023 9/28/2023 09/28/2023
Miscellaneous Correction
Informational
09/28/2023
Garage CSPF portal passed on both units. This is a partial pass for all rough only.
All Rough Inspection - Residential Failed 10/6/2023 10/06/2023
Miscellaneous Correction
Informational
09/28/2023
Garage CSPF portal passed on both units. This is a partial pass for all rough only.
Miscellaneous Correction
Corrective Action Required
10/06/2023
3746 Air supply ducts in kitchen need to be sealed at top and bottom for Fire blocking Top plate in living room has a break within 4 feet of corner Air supply duct in dining room needs to be sealed at the bottom Gas gauge is missing Service line in party wall appears to be missing fire caulking 3744 Metal air vent in garage chase needs to be fire blocked Electrical line in garage next to stairs going to basement needs to be fire blocked Stud shoe is needed in powder bathroom Top plate in great room has a break within 4 feet of the corner Supply vent in kitchen needs to be fire blocked at the floor and ceiling Address top plate at stud pack in basement at stairs Service line going through party wall needs to be sealed Anti siphon valve is missing its screw
Gas Service Inspection - Residential Failed 10/6/2023 10/6/2023 10/06/2023
Miscellaneous Correction
Corrective Action Required
10/06/2023
Gas gauge is missing and line has no pressure
Rated Assembly Inspection Passed 10/6/2023 10/6/2023 10/06/2023
Electrical Service Inspection Passed 10/6/2023 10/6/2023 10/06/2023
Erosion Control Inspection Residential Partial 10/6/2023 10/06/2023
Miscellaneous Correction
Informational
08/29/2023
Full erosion control is needed until occupancy. Keep the street free from rocks. Erosion control is in place at this time.
Miscellaneous Correction
Resolved
10/06/2023
Erosion control is not in place after back filling of the foundation. Erosion must be maintained until occupancy.
Miscellaneous Correction
Resolved
10/06/2023
Full erosion control of the property is not in place. There is dirt in the street that needs to be cleaned up. Full erosion control must be maintained until full CO. No inspections will proceed until erosion control is achieved and dirt and rock is removed from the street. Erosion control is also needed on the north lot adjacent to 3744. 08/29/2023. KBEARD
Miscellaneous Correction
Informational
10/06/2023
Erosion control is in place at the time of all rough inspection
Gas Service Inspection - Residential Passed 10/9/2023 10/9/2023 10/09/2023
Miscellaneous Correction
Resolved
10/09/2023
Gas gauge is missing and line has no pressure
All Rough Inspection - Residential Passed 10/9/2023 10/9/2023 10/09/2023
Miscellaneous Correction
Informational
10/06/2023
Garage CSPF portal passed on both units. This is a partial pass for all rough only.
Miscellaneous Correction
Resolved
10/09/2023
3746 Air supply ducts in kitchen need to be sealed at top and bottom for Fire blocking Top plate in living room has a break within 4 feet of corner Air supply duct in dining room needs to be sealed at the bottom Gas gauge is missing Service line in party wall appears to be missing fire caulking 3744 Metal air vent in garage chase needs to be fire blocked Electrical line in garage next to stairs going to basement needs to be fire blocked Stud shoe is needed in powder bathroom Top plate in great room has a break within 4 feet of the corner Supply vent in kitchen needs to be fire blocked at the floor and ceiling Address top plate at stud pack in basement at stairs Service line going through party wall needs to be sealed Anti siphon valve is missing its screw
All Rough Inspection - Residential Failed 10/10/2023 10/10/2023
Miscellaneous Correction
Corrective Action Required
10/10/2023
3744 Has a floor joist cut under the powder bathroom by the plumbing waste line and HVAC supply line. Joist needs to be addressed before passing the all rough. Okay to insulate and sheet rock house. Basement will be unfinished and joist repair can be checked at final
Erosion Control Inspection Residential Failed 10/26/2023 10/26/2023
Miscellaneous Correction
Informational
10/06/2023
Full erosion control is needed until occupancy. Keep the street free from rocks. Erosion control is in place at this time.
Miscellaneous Correction
Informational
10/06/2023
Erosion control is in place at the time of all rough inspection
Miscellaneous Correction
Corrective Action Required
10/26/2023
Some erosion control is missing or torn down. Erosion control must be in place until occupancy. Mud in the street needs to be removed.
Driveway Inspection Partial 10/31/2023 10/31/2023 10/31/2023
Misc
Informational
10/31/2023
10-31-23 PS Performed driveway approach pre pour, forms are in place and aggregate compacted, surface temp above freezing, approved to pour
Sidewalk Inspection Partial 10/31/2023 10/31/2023 10/31/2023
Misc
Informational
10/31/2023
10-31-23 PS Performed sidewalk pre pour, forms are in place and aggregate compacted, surface temp above freezing, approved to pour
Sidewalk Inspection Passed 11/9/2023 11/9/2023 11/08/2023
Misc
Informational
10/31/2023
10-31-23 PS Performed sidewalk pre pour, forms are in place and aggregate compacted, surface temp above freezing, approved to pour 11-8-23 Dustin A, SW is poured. Frames are pulled. Slopes are in compliance . Passed
Driveway Inspection Passed 11/9/2023 11/9/2023 11/08/2023
Misc
Informational
10/31/2023
10-31-23 PS Performed driveway approach pre pour, forms are in place and aggregate compacted, surface temp above freezing, approved to pour 11-8-23 Dustin A, DW is poured, Slopes are in compliance and forms are pulled. Passed
Erosion Control Inspection Residential Passed 12/8/2023 12/08/2023
Miscellaneous Correction
Informational
10/26/2023
Full erosion control is needed until occupancy. Keep the street free from rocks. Erosion control is in place at this time.
Miscellaneous Correction
Informational
10/26/2023
Erosion control is in place at the time of all rough inspection
Miscellaneous Correction
Informational
12/08/2023
Some erosion control is missing or torn down. Erosion control must be in place until occupancy. Mud in the street needs to be removed.
All Rough Inspection - Residential Passed 12/8/2023 12/8/2023 12/08/2023
Miscellaneous Correction
Resolved
12/08/2023
Occupancy Inspection - Codes Residential Failed 12/8/2023 12/8/2023 12/08/2023
Misc
Corrective Action Required
12/08/2023
-Break off security screw at anti siphon device in basement -Adjust self closing hinges at garage door -Caulk missing at the tops of exterior lights next to garage -Sod too close to exterior siding at rear of house -Grading at north side of house appears to be running towards the house
Occupancy Inspection - Codes Residential Not Ready 12/12/2023 12/12/2023 12/12/2023
Misc
Corrective Action Required
12/08/2023
-Break off security screw at anti siphon device in basement -Adjust self closing hinges at garage door -Caulk missing at the tops of exterior lights next to garage -Sod too close to exterior siding at rear of house -Grading at north side of house appears to be running towards the house
Misc
Corrective Action Required
12/12/2023
None of the deficiencies from the previous inspections have been addressed. PLEASE WALK PROPERTIES BEFORE SCHEDULING ANY FURTHER INSPECTIONS
Occupancy Inspection - Codes Residential Failed 12/14/2023 12/14/2023 12/14/2023
Misc
Partial Correction
12/14/2023
-Break off security screw at anti siphon device in basement -Adjust self closing hinges at garage door -Caulk missing at the tops of exterior lights next to garage -Sod too close to exterior siding at rear of house -Grading at north side of house appears to be running towards the house
Misc
Resolved
12/14/2023
None of the deficiencies from the previous inspections have been addressed. PLEASE WALK PROPERTIES BEFORE SCHEDULING ANY FURTHER INSPECTIONS
Miscellaneous Correction
Corrective Action Required
12/14/2023
3744 Clayton Basement stair to wood floor is over the allowable 7 3/4 inch riser height and does not meet code Electrical line is in contact with the hot water heater Garage to house door missing its seal Outside slope appears to run towards the foundation All the exterior penetrations needs to be sealed 3746 garage to house door is missing its seal Outside slope appears to run towards the foundation Exterior penetrations need to be sealed Basement stair to wood floor has a riser of 8 inches and does not meet code Garage stairs is missing its graspable top hand rail
Plot Plan Inspection Passed 12/14/2023 12/14/2023
Occupancy Inspection - Codes Residential Failed 12/19/2023 12/19/2023 12/19/2023
Misc
Partial Correction
12/14/2023
-Break off security screw at anti siphon device in basement -Adjust self closing hinges at garage door -Caulk missing at the tops of exterior lights next to garage -Sod too close to exterior siding at rear of house -Grading at north side of house appears to be running towards the house
Miscellaneous Correction
Partial Correction
12/19/2023
3744 Clayton Basement stair to wood floor is over the allowable 7 3/4 inch riser height and does not meet code Electrical line is in contact with the hot water heater Garage to house door missing its seal Outside slope appears to run towards the foundation All the exterior penetrations needs to be sealed 3746 garage to house door is missing its seal Outside slope appears to run towards the foundation Exterior penetrations need to be sealed Basement stair to wood floor has a riser of 8 inches and does not meet code Garage stairs is missing its graspable top hand rail
Miscellaneous Correction
Corrective Action Required
12/19/2023
3744 Clayton Garage to house door missing its top seal 3746 garage to house door is missing its seal Exterior penetrations need to be sealed Basement stair to wood floor has a riser of 8 inches and does not meet code Garage stairs is missing its graspable top hand rail 3746 -Unit appears to be occupied. No one answered when door bell was ring -sod to exterior siding is 1/2 inch in the backyard. Exterior sod to siding code is a 6 inch height difference
Occupancy Inspection - Codes Residential Ready for Temp CO 12/21/2023 12/21/2023 12/21/2023
Misc
Partial Correction
12/19/2023
-Break off security screw at anti siphon device in basement -Adjust self closing hinges at garage door -Caulk missing at the tops of exterior lights next to garage -Sod too close to exterior siding at rear of house -Grading at north side of house appears to be running towards the house
Miscellaneous Correction
Partial Correction
12/19/2023
3744 Clayton Basement stair to wood floor is over the allowable 7 3/4 inch riser height and does not meet code Electrical line is in contact with the hot water heater Garage to house door missing its seal Outside slope appears to run towards the foundation All the exterior penetrations needs to be sealed 3746 garage to house door is missing its seal Outside slope appears to run towards the foundation Exterior penetrations need to be sealed Basement stair to wood floor has a riser of 8 inches and does not meet code Garage stairs is missing its graspable top hand rail
Miscellaneous Correction
Partial Correction
12/21/2023
3744 Clayton Garage to house door missing its top seal 3746 garage to house door is missing its seal Exterior penetrations need to be sealed Basement stair to wood floor has a riser of 8 inches and does not meet code Garage stairs is missing its graspable top hand rail 3746 -Unit appears to be occupied. No one answered when door bell was ring -sod to exterior siding is 1/2 inch in the backyard. Exterior sod to siding code is a 6 inch height difference
Miscellaneous Correction
Corrective Action Required
12/21/2023
3744 and 3746 sod to exterior siding is 1/2 inch in the backyard. Exterior sod to siding code is a 6 inch height difference Passed for TCO only
Occupancy Inspection - Codes Residential Full C of O 3/4/2024 3/4/2024 03/04/2024
Misc
Resolved
03/04/2024
-Break off security screw at anti siphon device in basement -Adjust self closing hinges at garage door -Caulk missing at the tops of exterior lights next to garage -Sod too close to exterior siding at rear of house -Grading at north side of house appears to be running towards the house
Miscellaneous Correction
Resolved
03/04/2024
3744 Clayton Basement stair to wood floor is over the allowable 7 3/4 inch riser height and does not meet code Electrical line is in contact with the hot water heater Garage to house door missing its seal Outside slope appears to run towards the foundation All the exterior penetrations needs to be sealed 3746 garage to house door is missing its seal Outside slope appears to run towards the foundation Exterior penetrations need to be sealed Basement stair to wood floor has a riser of 8 inches and does not meet code Garage stairs is missing its graspable top hand rail
Miscellaneous Correction
Resolved
03/04/2024
3744 Clayton Garage to house door missing its top seal 3746 garage to house door is missing its seal Exterior penetrations need to be sealed Basement stair to wood floor has a riser of 8 inches and does not meet code Garage stairs is missing its graspable top hand rail 3746 -Unit appears to be occupied. No one answered when door bell was ring -sod to exterior siding is 1/2 inch in the backyard. Exterior sod to siding code is a 6 inch height difference
Miscellaneous Correction
Resolved
03/04/2024
3744 and 3746 sod to exterior siding is 1/2 inch in the backyard. Exterior sod to siding code is a 6 inch height difference Passed for TCO only
Documents & Images
Date Uploaded File Type Document Name
07/13/2023 OS #45 - PERMIT APP
07/13/2023 LOT 45 FINAL
07/13/2023 45 osage roof layout
07/13/2023 OS #45 - Twin Honeydew - Farmhouse - 230711
07/13/2023 P230314-01 Roof Seals
07/24/2023 Approved Plans approved plans
07/24/2023 Plot Plan approved plot plan
07/24/2023 Approved Plans APPROVED TRUSS LAYOUT
07/24/2023 Approved Plans APPROVED TRUSS PACKAGE
07/24/2023 Application Form APPLICATION
07/24/2023 Permit Codes Residential Plan Review
07/24/2023 Permit DS Building Permit
07/24/2023 Receipt Receipt for transaction:2023-005698
07/25/2023 Letter DS Building Permit
08/21/2023 Letter INSPECTION SUMMARY
08/22/2023 Letter INSPECTION SUMMARY
08/22/2023 Letter INSPECTION SUMMARY
08/23/2023 M L Crose 3744 & 3746 SW Clayton LSMO Osage Lot 45 Clayton P 2023-3392 3rd Party Footing Inspection Report 8-4-23
08/23/2023 Letter INSPECTION SUMMARY
08/23/2023 Letter INSPECTION SUMMARY
08/23/2023 Letter INSPECTION SUMMARY
08/23/2023 Letter INSPECTION SUMMARY
08/25/2023 Letter INSPECTION SUMMARY
08/25/2023 Letter INSPECTION SUMMARY
08/28/2023 Letter INSPECTION SUMMARY
08/29/2023 Letter INSPECTION SUMMARY
09/28/2023 Letter INSPECTION SUMMARY
10/06/2023 Letter INSPECTION SUMMARY
10/06/2023 Letter INSPECTION SUMMARY
10/06/2023 Letter INSPECTION SUMMARY
10/06/2023 Letter INSPECTION SUMMARY
10/06/2023 Letter INSPECTION SUMMARY
10/09/2023 Letter INSPECTION SUMMARY
10/09/2023 Letter INSPECTION SUMMARY
10/10/2023 Letter INSPECTION SUMMARY
10/23/2023 45 Osage B - Field Issue Letter
10/26/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter INSPECTION SUMMARY
11/08/2023 Letter INSPECTION SUMMARY
11/08/2023 Letter INSPECTION SUMMARY
12/08/2023 Letter INSPECTION SUMMARY
12/08/2023 Letter INSPECTION SUMMARY
12/08/2023 Letter INSPECTION SUMMARY
12/11/2023 Receipt Receipt for transaction:2023-009030
12/14/2023 Letter INSPECTION SUMMARY
12/14/2023 Letter INSPECTION SUMMARY
12/14/2023 Letter INSPECTION SUMMARY
12/14/2023 Receipt Receipt for transaction:2023-009102
12/19/2023 Letter INSPECTION SUMMARY
01/29/2024 LOT 45 ASBUILT ROUGH
03/01/2024 Certificate/License Codes Temporary Certificate of Occupancy
03/01/2024 Receipt Receipt for transaction:2024-001289
03/04/2024 Letter Codes Final Certificate of Occupancy
03/04/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home