Permit Application Status

PRRES20220641


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20220641
Building Permit - Residential
Certificate of Occupancy
CLAYTON PROPERTIES GROUP INC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED AND UNFINISHED BASEMENT - ROOF TRUSSES - COVERED PATIO
02/22/2022
03/08/2022
04/25/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
PERMITTING@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $330.00 $330.00 Paid 03/08/2022
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 03/08/2022
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 03/08/2022
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 03/08/2022
8350015-Water Meter Fee $479.24 $479.24 Paid 03/08/2022
9110078-Valuation Fee New Single Family $790.40 $790.40 Paid 03/08/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 02/13/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 04/24/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 3/31/2022 3/31/2022 03/31/2022
Misc
Corrective Action Required
03/31/2022
APPROVED PER DAVID P AINSWORTH 3/29/22
Underslab Plumbing Inspection - Residential Passed 4/12/2022 4/12/2022 04/12/2022
Sewer Service Inspection - R Passed 4/14/2022 (10:00) 4/14/2022 04/14/2022
Water Service Inspection - R Passed 4/26/2022 (11:15) 4/26/2022 04/26/2022
Erosion Control Inspection Residential Failed 4/26/2022 4/26/2022 04/26/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/26/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Gas Service Inspection - Residential Passed 12/27/2022 12/27/2022 12/27/2022
Electrical Service Inspection Failed 12/27/2022 12/27/2022 12/27/2022
Misc
Corrective Action Required
12/27/2022
-Connect ufer ground to middle grounded bus bar
All Rough Inspection - Residential Failed 12/22/2022 12/27/2022 12/27/2022
Misc
Corrective Action Required
12/27/2022
-address floor joists above service panel holes drilled closer than 2” to one another -seal penetrations in fireblocking above service panel -support dwv in joist space NE corner of rec room -midway strap all dwv 2” in diameter or less in wall space -uncover cspf nailing at bottom of framing
All Rough Inspection - Residential Passed 12/29/2022 12/29/2022 12/29/2022
Misc
Resolved
12/29/2022
Electrical Service Inspection Failed 12/29/2022 12/29/2022 12/29/2022
Misc
Corrective Action Required
12/27/2022
E3607.5 SYSTEM GROUNDING. An unspliced main bonding jumper shall be used to connect the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor of the system within the enclosure for each service disconnect. -Provide jumper from ground bar to neutral bar or land CEE on neutral bar
Electrical Service Inspection Passed 1/5/2023 1/5/2023 01/05/2023
Misc
Resolved
01/05/2023
E3607.5 SYSTEM GROUNDING. An unspliced main bonding jumper shall be used to connect the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor of the system within the enclosure for each service disconnect. -Provide jumper from ground bar to neutral bar or land CEE on neutral bar
Driveway Inspection Failed 1/26/2023 1/26/2023 01/26/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps.
Sidewalk Inspection Failed 1/26/2023 1/26/2023 01/26/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps.
Driveway Inspection Partial 1/27/2023 1/27/2023 01/27/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour
Sidewalk Inspection Partial 1/27/2023 1/27/2023 01/27/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour
Driveway Inspection Passed 2/10/2023 2/10/2023 02/06/2023
Misc
Corrective Action Required
01/27/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour 2-6-23 PS Driveway meets LS and ADA specifications
Sidewalk Inspection Passed 2/10/2023 2/10/2023 02/06/2023
Misc
Corrective Action Required
01/27/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour 2-6-23 PS Sidewalk meets LS and ADA specifications
Erosion Control Inspection Residential Partial 8/7/2023 08/07/2023
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/26/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Miscellaneous Inspection Passed 8/17/2023 08/17/2023
Miscellaneous Correction
Informational
08/17/2023
This is for permit extension only.
Erosion Control Inspection Residential Passed 10/31/2023 10/31/2023
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
10/31/2023
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Miscellaneous Inspection Failed 1/8/2024 01/08/2024
Miscellaneous Correction
Informational
01/08/2024
Permit has been extended before (08/16/22) and is in expired status. Permit extension is denied.
Miscellaneous Inspection Failed 1/16/2024 01/16/2024
Miscellaneous Correction
Informational
01/08/2024
Permit has been extended before (08/16/22) and is in expired status. Permit extension is denied.
Miscellaneous Correction
Informational
01/16/2024
Builder is making progress towards the building final. Permit has been moved to issued status for builder to schedule building finals
Occupancy Inspection - Codes Residential Failed 2/1/2024 2/1/2024 02/01/2024
Miscellaneous Correction
Corrective Action Required
02/01/2024
3537 SE Corbin. Occupancy front porch electrical outlet is loose inside the protective cover Hatch is not installed under stairwell for fire protection Breaker panel is not labeled Hot water tank electrical whip is in contact with the hot water pipe Seal all ceiling penetrations in the garage Sod to siding in the back yard needs to be a minimum of 6 inch clearance Seal top of service meter Back side of exterior a/c unit has an open trench and will not properly drain Submit as graded plot plan, due to the backyard not matching the existing plot plan
Plot Plan Inspection Failed 2/1/2024 02/01/2024
Miscellaneous Correction
Corrective Action Required
02/01/2024
Submit as graded plot plan, due to the backyard not matching the existing plot plan
Occupancy Inspection - Codes Residential Ready for Temp CO 2/13/2024 2/13/2024 02/13/2024
Miscellaneous Correction
Resolved
02/13/2024
3537 SE Corbin. Occupancy front porch electrical outlet is loose inside the protective cover Hatch is not installed under stairwell for fire protection Breaker panel is not labeled Hot water tank electrical whip is in contact with the hot water pipe Seal all ceiling penetrations in the garage Sod to siding in the back yard needs to be a minimum of 6 inch clearance Seal top of service meter Back side of exterior a/c unit has an open trench and will not properly drain Submit as graded plot plan, due to the backyard not matching the existing plot plan
Miscellaneous Correction
Corrective Action Required
02/13/2024
3537 SE Corbin. Occupancy (2) Sod to siding in the back yard needs to be a minimum of 6 inch clearance Seal top of service meter Back side of exterior a/c unit has an open trench and will not properly drain Submit as graded plot plan, due to the backyard not matching the existing plot plan TCO passed 02/13/24 KBEARD
Occupancy Inspection - Codes Residential Not Ready 3/18/2024 03/18/2024
Miscellaneous Correction
Resolved
03/18/2024
3537 SE Corbin. Occupancy (2) Sod to siding in the back yard needs to be a minimum of 6 inch clearance Seal top of service meter Back side of exterior a/c unit has an open trench and will not properly drain Submit as graded plot plan, due to the backyard not matching the existing plot plan TCO passed 02/13/24 KBEARD
Miscellaneous Correction
Corrective Action Required
03/18/2024
3537 SE Corbin. Occupancy (2) Sod to siding in the back yard needs to be a minimum of 6 inch clearance Seal top of service meter Back side of exterior a/c unit has an open trench and will not properly drain Submit as graded plot plan, due to the backyard not matching the existing plot plan TCO passed 02/13/24 KBEARD TCO extension requested on 03/14/24. No response from request. No improvements were made during a virtual drive bye. 03/14/24 Not ready fee assessed 03/18/24. KBEARD
Plot Plan Inspection Passed 4/24/2024 04/24/2024
Miscellaneous Correction
Resolved
04/24/2024
Submit as graded plot plan, due to the backyard not matching the existing plot plan
Occupancy Inspection - Codes Residential Full C of O 4/25/2024 04/25/2024
Miscellaneous Correction
Resolved
04/25/2024
3537 SE Corbin. Occupancy (2) Sod to siding in the back yard needs to be a minimum of 6 inch clearance Seal top of service meter Back side of exterior a/c unit has an open trench and will not properly drain Submit as graded plot plan, due to the backyard not matching the existing plot plan TCO passed 02/13/24 KBEARD TCO extension requested on 03/14/24. No response from request. No improvements were made during a virtual drive bye. 03/14/24 Not ready fee assessed 03/18/24. KBEARD
Documents & Images
Date Uploaded File Type Document Name
02/22/2022 CB #143 - PERMIT APPLICATION
02/23/2022 Approved Plans APPROVED PLANS
02/23/2022 Approved Plans APPROVED TRUSS LAYOUT
02/23/2022 Approved Plans APPROVED TRUSS PACKAGE
02/23/2022 Plot Plan APPROVED PLOT PLAN
03/07/2022 Permit Codes Residential Plan Review
03/08/2022 Permit DS Building Permit
03/08/2022 Receipt Receipt for transaction:2022-001223
03/30/2022 M L Crose 3537 SE Corbin Dr LSMO Cobey Creek Lot 143 Clayton Permit 2022-0641 Footing Inspection Report 3-29-22
03/31/2022 Letter INSPECTION SUMMARY
04/12/2022 Letter INSPECTION SUMMARY
04/14/2022 Letter INSPECTION SUMMARY
04/26/2022 Letter INSPECTION SUMMARY
04/26/2022 Letter INSPECTION SUMMARY
12/27/2022 Letter INSPECTION SUMMARY
12/27/2022 Letter INSPECTION SUMMARY
12/27/2022 Letter INSPECTION SUMMARY
12/28/2022 143 cobey creek truss inspection letter- signed
12/28/2022 I55619068_220100
12/28/2022 143 Cobey Creek Letter floor joist
12/29/2022 Letter INSPECTION SUMMARY
12/29/2022 Letter INSPECTION SUMMARY
01/02/2023 143 Cobey Creek Letter
01/05/2023 Letter INSPECTION SUMMARY
01/26/2023 Letter INSPECTION SUMMARY
01/26/2023 Letter INSPECTION SUMMARY
01/27/2023 Letter INSPECTION SUMMARY
01/27/2023 Letter INSPECTION SUMMARY
02/06/2023 Letter INSPECTION SUMMARY
02/06/2023 Letter INSPECTION SUMMARY
06/26/2023 Letter Codes 140 Day Letter
08/11/2023 Letter INSPECTION SUMMARY
08/11/2023 Letter Codes 180 Day Letter
08/16/2023 Perrmit Extension Request Form CB#143
08/17/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter Codes 180 Day Letter
01/04/2024 CB # 143 - Permit Extension
01/08/2024 Letter INSPECTION SUMMARY
01/11/2024 CB # 143 - Permit Extension
01/16/2024 Letter INSPECTION SUMMARY
02/01/2024 Letter INSPECTION SUMMARY
02/01/2024 Letter INSPECTION SUMMARY
02/01/2024 Letter INSPECTION SUMMARY
02/13/2024 Letter INSPECTION SUMMARY
02/13/2024 Certificate/License Codes Temporary Certificate of Occupancy
02/13/2024 Receipt Receipt for transaction:2024-000809
03/07/2024 CB #143 - TCO Extension App_
03/07/2024 CB #143 - TCO Extension App_
03/18/2024 Letter INSPECTION SUMMARY
04/23/2024 LOT 143 ASBUILT
04/23/2024 Plot Plan approved as graded plot plan
04/24/2024 Letter INSPECTION SUMMARY
04/24/2024 Receipt Receipt for transaction:2024-002623
04/25/2024 Letter Codes Final Certificate of Occupancy
04/25/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home