Summary
PRRES20216410
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK
12/16/2021
12/21/2021
06/18/2022
10/21/2022
Locations
Contacts
JFE CONSTRUCTION INC, Address:1314 SW MARKET ST, Phone:(816) 470-0074  
Angie Mendenhall, Address:1314 SW Market Street  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
A BRIGHT PLUMBING LLC, Address:18107 E 18TH TER N, Phone:(816) 215-0730  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $420.00 $420.00 Paid 12/21/2021
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 12/21/2021
8350015-Water Meter Fee $479.24 $479.24 Paid 12/21/2021
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 12/21/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 12/21/2021
9110078-Valuation Fee New Single Family $1,122.24 $1,122.24 Paid 12/21/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed 2/11/2022 02/11/2022
Misc
Corrective Action Required
02/11/2022
-address ufer ground rod no located as indicated in third party inspection report
Footing Inspection - Residential Passed 2/14/2022 02/14/2022
Misc
Resolved
02/14/2022
-address ufer ground rod no located as indicated in third party inspection report
Sewer Service Inspection - R Passed 2/23/2022 (10:15) 2/23/2022 02/23/2022
Erosion Control Inspection Residential Failed 2/23/2022 02/23/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
02/23/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
02/23/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Partial 2/24/2022 02/24/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
02/24/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM3 ESC REQUIRED 2 DAY
Resolved
02/24/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Underslab Plumbing Inspection - Residential Passed 2/24/2022 2/24/2022 02/24/2022
Water Service Inspection - R Passed 3/3/2022 (11:00) 3/3/2022 03/03/2022
Erosion Control Inspection Residential Failed 3/31/2022 03/31/2022
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/31/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Mitchell Schwarz 03/31/2022 3:28 PM
Erosion Control Inspection Residential Failed 6/1/2022 06/01/2022
DCM3 ESC REQUIRED 2 DAY
Resolved
06/01/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Mitchell Schwarz 03/31/2022 3:28 PM
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
06/01/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. repair silt fence
Gas Service Inspection - Residential Failed 6/1/2022 6/1/2022 06/01/2022
Misc
Corrective Action Required
06/01/2022
minimum 10psi at pressure gauge for inspection.
Electrical Service Inspection Passed 6/1/2022 6/1/2022 06/01/2022
All Rough Inspection - Residential Failed 6/1/2022 6/1/2022 06/01/2022
Misc
Corrective Action Required
06/01/2022
-no further inspections until erosion control is in compliance -uncover anchor bolt at PFH for inspection -address hanger used for hip rafter above dining/kitchen -cspf nailing at rear of home -seal gaps in fireblock if left of fireplace -seal gaps in RA stud space foyer -uncover cover patios for inspection -address hip rafter connect in master NW wall -seal bottom plate penetration in master N wall -seal top plate penetration in master to master bath wall -seal area for RA in master bath where lighting fixture is -anchor bolts in basement to be in the middle 1/3 of sill plate -fire block into furr down in wet bar -minimum 10psi at gas pressure gauge for inspection -seal gaps into furr down bed 4 E wall -
All Rough Inspection - Residential Failed 6/7/2022 6/7/2022 06/07/2022
Misc
Corrective Action Required
06/01/2022
-uncover anchor bolt at PFH for inspection -address hanger used for hip rafter above dining/kitchen -cspf nailing at rear of dining address over nailed sheathing, cspf nail pattern not to plans -seal gaps in fireblocking left of fireplace -uncover cover front patio for inspection -address hip rafter connect in master NW walll
Gas Service Inspection - Residential Failed 6/7/2022 6/7/2022 06/07/2022
Misc
Corrective Action Required
06/01/2022
minimum 10psi at pressure gauge for inspection.
Gas Service Inspection - Residential Passed 6/9/2022 6/9/2022 06/09/2022
Misc
Resolved
06/09/2022
minimum 10psi at pressure gauge for inspection.
All Rough Inspection - Residential Failed 6/13/2022 6/13/2022 06/13/2022
Misc
Corrective Action Required
06/07/2022
-uncover anchor bolt at PFH for inspection -address hanger used for hip rafter above dining/kitchen -cspf nailing at rear of dining address over nailed sheathing, cspf nail pattern not to plans -uncover cover front patio for inspection -address hip rafter connect in master NW walll -okay to insulate
Driveway Inspection Partial 7/15/2022 7/15/2022 07/15/2022
Misc
Informational
07/15/2022
On 7.15.2022 I conducted a driveway inspection and pass the sub-grade to pour concrete.
Driveway Inspection Passed 7/18/2022 7/18/2022 07/18/2022
Misc
Informational
07/15/2022
On 7.15.2022 I conducted a driveway inspection and pass the sub-grade to pour concrete. 7-18-22 RH. Driveway meets LS and ADA Specification.
All Rough Inspection - Residential Passed 10/11/2022 10/11/2022
Misc
Informational
10/11/2022
-uncover anchor bolt at PFH for inspection -address hanger used for hip rafter above dining/kitchen -cspf nailing at rear of dining address over nailed sheathing, cspf nail pattern not to plans -uncover cover front patio for inspection -address hip rafter connect in master NW walll -okay to insulate
Misc
Informational
10/11/2022
passed per engineer letter.
Piers/Caissons Inspection - Residential Passed 10/11/2022 10/11/2022
Plot Plan Inspection Passed 10/11/2022 10/11/2022
Occupancy Inspection - Codes Residential Failed 10/11/2022 10/11/2022 10/11/2022
Misc
Corrective Action Required
10/11/2022
Erosion control to remain in place and compliance until time of sod -sod -obtain lawn irrigation permit -check water meter at time of sod -hardware at rear slider -fire blocking for engineered I joists in unfinished spaces
Erosion Control Inspection Residential Passed 10/21/2022 10/21/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
10/21/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. repair silt fence
Occupancy Inspection - Codes Residential Full C of O 10/21/2022 10/21/2022 10/21/2022
Misc
Resolved
10/21/2022
-check water meter at time of sod -hardware at rear slider -fire blocking for engineered I joists in unfinished spaces
Documents & Images
Date Uploaded File Type Document Name
12/16/2021 HF 50 - Permit App
12/16/2021 HF50 - Tax App
12/20/2021 Permit Codes Residential Plan Review
12/20/2021 Approved Plans Approved Drawings
12/21/2021 Plot Plan APPROVED PLOT PLAN
12/21/2021 Permit Codes Residential Plan Review
12/21/2021 Permit DS Building Permit
12/21/2021 Receipt Receipt for transaction:2021-009435
02/11/2022 2826 SW Hearthstone Pl LSMO Hook Farms Lot 50 Foundation Footing Inspection Report 2-10-22
02/11/2022 Letter INSPECTION SUMMARY
02/14/2022 2826 SW Hearthstone Pl LSMO Hook Farms Lot 50 Foundation Footing Inspection Report 2-10-22 Revised to Correct Ufer Location
02/23/2022 Letter INSPECTION SUMMARY
02/23/2022 Letter INSPECTION SUMMARY
02/23/2022 Letter INSPECTION SUMMARY
02/24/2022 Letter INSPECTION SUMMARY
02/24/2022 Letter INSPECTION SUMMARY
03/03/2022 Letter INSPECTION SUMMARY
03/15/2022 2826 SW Hearthstone Pl_ALL SLAB & DECK PIER INSP_2022-03-14
03/31/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/07/2022 Letter INSPECTION SUMMARY
06/08/2022 Jun 8, Doc 1
06/09/2022 Letter INSPECTION SUMMARY
06/09/2022 Letter INSPECTION SUMMARY
06/09/2022 Letter INSPECTION SUMMARY
06/13/2022 Letter INSPECTION SUMMARY
07/18/2022 Letter INSPECTION SUMMARY
07/21/2022 Letter INSPECTION SUMMARY
10/07/2022 2826 SW Heatherstone Place_Framing Evaluation Report_10-3-22
10/11/2022 Letter INSPECTION SUMMARY
10/11/2022 Letter INSPECTION SUMMARY
10/11/2022 Letter INSPECTION SUMMARY
10/11/2022 Letter INSPECTION SUMMARY
10/21/2022 Letter INSPECTION SUMMARY
10/21/2022 Letter Field Certificate of Occupancy
10/21/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home