Summary
PRRES20216204
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE. WALKOUT BASEMENT. FINISHED/UNFINISHED BASEMENT. COVERED DECK. ROOF TRUSSES.
12/02/2021
12/07/2021
01/17/2023
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CMH PARKS INC, Address:5000 CLAYTON RD  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
AJ@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $600.00 $600.00 Paid 12/07/2021
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 12/07/2021
8350015-Water Meter Fee $479.24 $479.24 Paid 12/07/2021
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 12/07/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 12/07/2021
9110078-Valuation Fee New Single Family $1,729.81 $1,729.81 Paid 12/07/2021
8331504-EFHB Middle Big Creek, Full $669.60 $669.60 Paid 12/07/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/10/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 10/10/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 1/11/2022 1/11/2022 01/11/2022
Misc
Informational
01/11/2022
APPROVED PER BRADLEY HUXOL 12/16/21
Underslab Plumbing Inspection - Residential Not Ready 1/11/2022 1/11/2022 01/11/2022
Misc
Corrective Action Required
01/11/2022
INSPECTION DENIED ADDRESS EROSION CONTROL ON LOT, CLEAN ALL MUD AND GRAVEL FROM STREET, GRAVEL FILTER REQUIRED WITH 6" LIFT
Erosion Control Inspection Residential Failed 1/11/2022 1/11/2022 01/11/2022
Misc
Corrective Action Required
01/11/2022
INSPECTION DENIED ADDRESS EROSION CONTROL ON LOT, CLEAN ALL MUD AND GRAVEL FROM STREET, GRAVEL FILTER REQUIRED WITH 6" LIFT
Underslab Plumbing Inspection - Residential Passed 1/24/2022 1/24/2022 01/24/2022
Misc
Resolved
01/24/2022
Erosion Control Inspection Residential Partial 1/24/2022 1/24/2022 01/24/2022
Misc
Corrective Action Required
01/11/2022
EROSION CONTROL ACCEPTABLE AT TIME OF INSPECTION
Sewer Service Inspection - R Partial 1/28/2022 (1:00) 1/28/2022 01/28/2022
Miscellaneous Correction
Corrective Action Required
01/28/2022
partial
Water Service Inspection - R Passed 2/1/2022 (10:00) 2/1/2022 02/01/2022
Sewer Service Inspection - R Passed 2/1/2022 (1:00) 2/1/2022 02/01/2022
Miscellaneous Correction
Resolved
02/01/2022
partial
Suspended Slab Inspection Passed 6/17/2022 (8:30) 6/17/2022 06/17/2022
Erosion Control Inspection Residential Partial 06/17/2022
Misc
Resolved
06/17/2022
EROSION CONTROL ACCEPTABLE AT TIME OF INSPECTION
Electrical Service Inspection Passed 6/21/2022 06/21/2022
Gas Service Inspection - Residential Failed 6/21/2022 06/21/2022
Misc
Corrective Action Required
06/21/2022
complete fireplace install
All Rough Inspection - Residential Failed 6/21/2022 06/21/2022
Misc
Corrective Action Required
06/21/2022
-address dbl top plate removed for HVAC duct at garage wall -min 24” lap between dbl top plate breaks, see garage -provide structural straps all top plates bores 50% or more all interior load bearing walls and all exterior walls, strap min 1 1/2” wide, 16 ga, extend 6” passed opening each side with (4) 10D nails each side of strap -Secure all LIB X bracing straps -complete bath exhaust fan duct master bed -Fireblock all tub traps -provide bocca protection plate bottom plate master bed -nail all intersecting corners 12” oc -install fireplace -address top plate corner lap connection required by code great room exterior walk -install all doors and windows -address trusses and girder truss supported by blocks above top plate at sliding glass door -fireblock HVAC chase garage entry -provide attic access for kitchen and front bedroom attic space -provide 3” SCH 40 column at garage steel beam per plans -provide attic access garage per plans -(4) 2x4 stud pack at trpl lvl garage wall per plans -dbl every other joist at garage single car bay per plans -(3) 2x10 joist garage per plans -(2) 2x4 trimmer studs at garage entry per plans -provide LIB X bracing master bath per plans -CS-PF portal bracing at great room and kitchen sliding glass door per plans -all truss hangers per plans -provide (4) 2X stud pack at all girder truss bearing ends per plans -provide H2.5 clips all trusses throughout -complete bath exhaust fans 2nd floor -protect all NM within 6’ of attic entry -provide studs packs and full bearing at dbl girder truss stair wall per plans -fireblock vertical every 10’ at finished basement -fireblock vertical to horizontal at furred down soffit ends -provide security blocking basement door -anchor bolts within 12” of plate break basement -seal top plate penetrations at finished basement -anchor steel columns to floor at basement -EC#2 hold down device at basement den near walkout per plans -provide additional studs at basement for 1st floor bearing per plans -support all DWV every 48” oc, traps not considered support -address overbored floor joist for DWV basement den -(3) 2x10 joist basement den per plans -3.5” and 4” SCH 40 steel columns at W10x26 steel beam basement -complete plumbing/framing finished basement bathroom -provide deck ledger attachment at cantilever per plans 10/S2.0 -provide (2) 1/2” through bolts each post/beam connection at deck -nail all exterior sheathing per plans
Erosion Control Inspection Residential Partial 06/21/2022
All Rough Inspection - Residential Failed 7/8/2022 7/8/2022 07/08/2022
Misc
Corrective Action Required
06/21/2022
-install all doors and windows -provide attic access for kitchen and front bedroom attic space -provide security blocking basement door -provide (2) 1/2” through bolts each post/beam connection at deck Ok to insulate
Gas Service Inspection - Residential Passed 7/11/2022 7/11/2022 07/11/2022
Misc
Resolved
07/11/2022
complete fireplace install
All Rough Inspection - Residential Passed 7/12/2022 7/12/2022 07/12/2022
Misc
Resolved
07/12/2022
Driveway Inspection Partial 8/9/2022 8/9/2022 08/09/2022
Misc
Informational
08/09/2022
8.9.2022 I performed a driveway inspection and pass the subgrade to pour concrete
Driveway Inspection Passed 8/12/2022 (1:00) 8/12/2022 08/12/2022
Misc
Informational
08/09/2022
8.9.2022 I performed a driveway inspection and pass the subgrade to pour concrete 8.12.2022 Driveway appears to be compliant
Occupancy Inspection - Codes Residential Failed 10/7/2022 10/7/2022 10/07/2022
Misc
Corrective Action Required
10/07/2022
-resolve outstanding inspection fee -final grade and sod -gutters and downspouts -splash blocks -provide tempered glass at window above tub master bath -install cover plates on outlets, master closet, great room -handrail height 34”-38” per code, 2nd floor stairs too low -max 4” sphere spacing between spindles at 2nd floor guardrail -anchor steel column to floor at mechanical -secure main water line to foundation wall
Occupancy Inspection - Codes Residential Ready for Temp CO 10/10/2022 10/10/2022 10/10/2022
Misc
Corrective Action Required
10/07/2022
-final grade and sod -splash blocks
Erosion Control Inspection Residential Passed 10/18/2022 10/18/2022 10/18/2022
Occupancy Inspection - Codes Residential Failed 10/18/2022 10/18/2022 10/18/2022
Misc
Corrective Action Required
10/10/2022
-UNCOVER MANHOLE MH1-5 AT FRONT OF LOT AS SHOWN ON PLOT PLAN -RAISE WATER METER LID TO GRADE, MAINTAIN REQUIRED 14"-18" FROM METER TO LID
Plot Plan Inspection Failed 10/18/2022 10/18/2022 10/18/2022
Misc
Corrective Action Required
10/18/2022
-UNCOVER MANHOLE MH1-5 AT FRONT OF LOT AS SHOWN ON PLOT PLAN
Occupancy Inspection - Codes Residential Failed 11/9/2022 11/09/2022
Misc
Corrective Action Required
10/18/2022
-RAISE WATER METER LID TO GRADE, MAINTAIN REQUIRED 14"-18" FROM METER TO LID, CAN BE NO MORE THAN 18", CURRENTLY OVER 18" TCO HAS EXPIRED, ADDRESS ASAP, IF REQUESTING EXTENSION SUBMIT TCO EXTENSION LETTER FOR REVIEW
Plot Plan Inspection Passed 11/9/2022 11/9/2022 11/09/2022
Misc
Resolved
11/09/2022
-UNCOVER MANHOLE MH1-5 AT FRONT OF LOT AS SHOWN ON PLOT PLAN
Occupancy Inspection - Codes Residential Full C of O 1/17/2023 1/17/2023 01/17/2023
Misc
Resolved
01/17/2023
-RAISE WATER METER LID TO GRADE, MAINTAIN REQUIRED 14"-18" FROM METER TO LID, CAN BE NO MORE THAN 18", CURRENTLY OVER 18" TCO HAS EXPIRED, ADDRESS ASAP, IF REQUESTING EXTENSION SUBMIT TCO EXTENSION LETTER FOR REVIEW
Documents & Images
Date Uploaded File Type Document Name
12/02/2021 RR #118 - PERMIT APP
12/06/2021 Approved Plans APPROVED TRUSS PACKAGE
12/06/2021 Approved Plans APPROVED TRUSS LAYOUT
12/06/2021 Approved Plans APPROVED DRAWINGS
12/06/2021 Plot Plan APPROVED PLOT PLAN
12/06/2021 Permit Codes Residential Plan Review
12/07/2021 Permit DS Building Permit
12/07/2021 Receipt Receipt for transaction:2021-009144
01/10/2022 118 Reserve at Stoney Creek-FTNG
01/10/2022 118 Reserve at Stoney Creek-FDTN
01/11/2022 Letter INSPECTION SUMMARY
01/11/2022 Letter INSPECTION SUMMARY
01/11/2022 Letter INSPECTION SUMMARY
01/24/2022 Letter INSPECTION SUMMARY
01/24/2022 Letter INSPECTION SUMMARY
01/28/2022 Letter INSPECTION SUMMARY
02/01/2022 Letter INSPECTION SUMMARY
02/01/2022 Letter INSPECTION SUMMARY
06/17/2022 Letter INSPECTION SUMMARY
06/17/2022 Letter INSPECTION SUMMARY
06/21/2022 Letter INSPECTION SUMMARY
06/21/2022 Letter INSPECTION SUMMARY
06/21/2022 Letter INSPECTION SUMMARY
06/21/2022 Letter INSPECTION SUMMARY
07/07/2022 118 ReserveStoney Letter
07/08/2022 Letter INSPECTION SUMMARY
07/11/2022 Letter INSPECTION SUMMARY
07/12/2022 Letter INSPECTION SUMMARY
08/12/2022 Letter INSPECTION SUMMARY
08/12/2022 Letter INSPECTION SUMMARY
08/12/2022 Letter INSPECTION SUMMARY
10/07/2022 Letter INSPECTION SUMMARY
10/10/2022 Receipt Receipt for transaction:2022-008125
10/10/2022 Letter Codes Temporary Certificate of Occupancy
10/18/2022 Letter INSPECTION SUMMARY
10/18/2022 Letter Codes Temporary Certificate of Occupancy
10/18/2022 Letter INSPECTION SUMMARY
10/18/2022 Letter INSPECTION SUMMARY
11/09/2022 Letter INSPECTION SUMMARY
11/09/2022 Letter INSPECTION SUMMARY
01/17/2023 Letter Codes Final Certificate of Occupancy
01/17/2023 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home