Permit Application Status

PRRES20213811


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20213811
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - UNCOVERED DECK
07/22/2021
09/10/2021
11/08/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
JOE@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $420.00 $420.00 Paid 09/10/2021
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 09/10/2021
8350015-Water Meter Fee $479.24 $479.24 Paid 09/10/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 09/10/2021
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 09/10/2021
9110078-Valuation Fee New Single Family $995.23 $995.23 Paid 09/10/2021
8331504-EFHB Middle Big Creek, Full $468.72 $468.72 Paid 10/22/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 10/21/2021 10/21/2021 10/21/2021
Misc
Informational
10/21/2021
APPROVED PER DAVID P AINSWORTH 10/18/21
Underslab Plumbing Inspection - Residential Passed 11/12/2021 11/12/2021 11/12/2021
Sewer Service Inspection - R Passed 11/29/2021 (11:30) 11/29/2021 11/29/2021
Water Service Inspection - R Passed 12/2/2021 (2:00) 12/2/2021 12/02/2021
Erosion Control Inspection Residential Failed 12/2/2021 12/2/2021 12/02/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/02/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Piers/Caissons Inspection - Residential Failed 6/7/2022 (9:00) 6/7/2022 06/07/2022
Misc
Corrective Action Required
06/07/2022
- BOTH PIERS FILLED WITH WATER, PUMP OUT WATER OR WAIT FOR CONDITIONS TO IMPROVE BEFORE RESCHEDULING
Piers/Caissons Inspection - Residential Passed 6/9/2022 (8:45) 6/9/2022 06/09/2022
Misc
Resolved
06/09/2022
- BOTH PIERS FILLED WITH WATER, PUMP OUT WATER OR WAIT FOR CONDITIONS TO IMPROVE BEFORE RESCHEDULING
Electrical Service Inspection Passed 6/16/2022 6/16/2022 06/16/2022
Gas Service Inspection - Residential Passed 6/16/2022 6/16/2022 06/16/2022
All Rough Inspection - Residential Failed 6/16/2022 6/16/2022 06/16/2022
Misc
Corrective Action Required
06/16/2022
-seal all top plate penetrations garage -nail off stud shoe 1st floor bath -toenail all floor joists per code -nail all intersecting corners 12” oc -overnotched king stud at front window -nail off all joist hangers -structural strap top plate master bath -min 24” lap between plate breaks 2nd floor hall bath -provide (4) 2X stud pack at garage wall for 2nd floor girder truss bearing per plans -provide correct header design at 2nd floor front bedroom
Erosion Control Inspection Residential Partial 06/16/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
06/16/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
All Rough Inspection - Residential Failed 6/24/2022 6/24/2022 06/24/2022
Misc
Corrective Action Required
06/16/2022
-nail off stud shoe 1st floor bath , Incomplete. -over notched king stud at front window , install a full length stud, stud does not meet top plate. -structural strap top plate master bath -provide (4) 2X stud pack at garage wall for 2nd floor girder truss bearing per plans , incomplete. -provide correct header design at 2nd floor front bedroom,, was this addressed? -Address five joist that are bored more than 3 inches over kitchen for 3 inch DWV provide engineers letter on strapping or install floor Joist per code. See picture on portal
All Rough Inspection - Residential Failed 6/28/2022 6/28/2022 06/28/2022
Misc
Corrective Action Required
06/24/2022
-nail off stud shoe 1st floor bath , Incomplete. -provide correct header design at 2nd floor front bedroom,, was this addressed? -Address five joist that are bored more than 3 inches over kitchen for 3 inch DWV provide engineers letter on strapping or install floor Joist per code. See picture on portal
All Rough Inspection - Residential Passed 6/29/2022 6/29/2022 06/29/2022
Misc
Resolved
06/29/2022
Driveway Inspection Partial 07/08/2022
Misc
Informational
07/08/2022
On 7.8.2022 I performed a driveway inspection and pass the sub-grade to pour concrete
Sidewalk Inspection Partial 7/8/2022 7/8/2022 07/08/2022
Misc
Informational
07/08/2022
On 7.8.2022 I performed a sidewalk inspection and pass the sub-grade to pour concrete.
Driveway Inspection Passed 8/8/2022 8/8/2022 08/08/2022
Misc
Informational
07/08/2022
On 7.8.2022 I performed a driveway inspection and pass the sub-grade to pour concrete 8.8.2022 Driveway appears to be compliant
Sidewalk Inspection Passed 8/8/2022 8/8/2022 08/08/2022
Misc
Informational
07/08/2022
On 7.8.2022 I performed a sidewalk inspection and pass the sub-grade to pour concrete. 8.8.2022 Sidewalk appears to be compliant
Plot Plan Inspection Passed 9/8/2022 09/08/2022
Occupancy Inspection - Codes Residential Failed 11/1/2022 11/1/2022 11/01/2022
Misc
Corrective Action Required
11/01/2022
-provide cover plates at garage outlets -fireblock beam pockets at foundation wall garage -provide security screws, door hardware, and weather strip at basement walkout -install exterior light at basement walkout -provide (2) 1/2” through bolts each post/beam connection at deck -handrail height at deck stairs must be between 34”-38” -Sump pump discharge min 36”
Erosion Control Inspection Residential Passed 11/1/2022 11/1/2022 11/01/2022
Occupancy Inspection - Codes Residential Full C of O 11/8/2022 11/8/2022 11/08/2022
Misc
Resolved
11/08/2022
Documents & Images
Date Uploaded File Type Document Name
07/22/2021 OS #27 - PERMIT APP
07/23/2021 Permit Codes Residential Plan Review
07/23/2021 Permit Codes Residential Plan Review
07/26/2021 Plot Plan Approved Plot Plan
07/26/2021 Permit Codes Residential Plan Review
09/03/2021 Approved Plans Approved Truss Layout
09/03/2021 Approved Plans Approved Truss Package
09/03/2021 Approved Plans Approved Drawings
09/10/2021 Permit DS Building Permit
09/10/2021 Receipt Receipt for transaction:2021-007248
10/20/2021 3813 SW Maryville Pl LSMO Osage Lot 27 Clayton Prop Permit 2021-3811 3rd Party Footing Inspection Report 10-18-21
10/21/2021 Letter INSPECTION SUMMARY
10/22/2021 Receipt Receipt for transaction: 2021-008192
11/12/2021 Letter INSPECTION SUMMARY
11/29/2021 Letter INSPECTION SUMMARY
12/02/2021 Letter INSPECTION SUMMARY
12/02/2021 Letter INSPECTION SUMMARY
06/07/2022 Letter INSPECTION SUMMARY
06/09/2022 Letter INSPECTION SUMMARY
06/16/2022 Letter INSPECTION SUMMARY
06/16/2022 Letter INSPECTION SUMMARY
06/16/2022 Letter INSPECTION SUMMARY
06/16/2022 Letter INSPECTION SUMMARY
06/24/2022 EDD02FA4-0EA5-4839-8593-9669141C5D1A
06/24/2022 Letter INSPECTION SUMMARY
06/28/2022 Letter INSPECTION SUMMARY
06/28/2022 27 Osage Header Field Issue
06/28/2022 37 Osage OB Joists Field Issue Letter
06/29/2022 Letter INSPECTION SUMMARY
07/08/2022 Letter INSPECTION SUMMARY
07/08/2022 Letter INSPECTION SUMMARY
09/07/2022 Plot Plan Approved As Graded Plot Plan
09/08/2022 Letter INSPECTION SUMMARY
11/01/2022 Letter INSPECTION SUMMARY
11/01/2022 Letter INSPECTION SUMMARY
11/08/2022 Letter Field Certificate of Occupancy
11/08/2022 Letter Codes Final Certificate of Occupancy
01/29/2024 LOT 27 ASBUILT
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home