Summary
PRRES20204958
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED PATIO
12/29/2020
12/30/2020
06/28/2021
10/27/2021
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
DUSTIN@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 01/04/2021 12/30/2020
Kim Brennan
Basement opening elevations
Corrective Action Required
12/30/2020

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan.
Basement egress
Corrective Action Required
12/30/2020

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Residential Plan Review Approved 01/04/2021 12/30/2020
Kim Brennan
Plot Plan Review Rejected 12/31/2020 12/30/2020
Kim Brennan
Basement opening elevations
Corrective Action Required
12/30/2020

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan.
Basement egress
Corrective Action Required
12/30/2020

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Residential Plan Review Approved 12/31/2020 12/30/2020
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $961.90 $961.90 Paid 12/30/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 12/30/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 12/30/2020
8331504-EFHB Middle Big Creek, Full $502.20 $502.20 Paid 12/30/2020
8331507-Sewer Connection Fee $450.00 $450.00 Paid 12/30/2020
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 12/30/2020
8350015-Water Meter Fee $455.54 $455.54 Paid 12/30/2020
Outstanding Fees Amount Paid Owing Date Paid
9110080-3rd and Subsequent Inspection Fee (Per Hour) $150.00 $0.00 $150.00 Not Paid
9110080-Not Ready Inspection Fee $50.00 $0.00 $50.00 Not Paid


$200.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 02/22/2021
Misc
Corrective Action Required
02/22/2021
FOOTING POURED WITHOUT INSPECTION - SUBMIT ENGINEER REPORT
Footing Inspection - Residential Failed 02/22/2021
Misc
Corrective Action Required
02/22/2021
FOOTING POURED WITHOUT INSPECTION - SUBMIT ENGINEER REPORT
Underslab Plumbing Inspection - Residential Failed 3/1/2021 3/1/2021 03/01/2021
Misc
Corrective Action Required
03/01/2021
-No footing inspection performed, submit engineer report -No inspection performed - backfill at foundation -Clean mud and gravel from street
Underslab Plumbing Inspection - Residential Passed 3/24/2021 3/24/2021 03/24/2021
Misc
Resolved
03/24/2021
Sewer Service Inspection - R Passed 5/19/2021 (8:00) 5/19/2021 05/19/2021
Erosion Control Inspection Residential Failed 05/19/2021
Misc
Resolved
05/19/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
05/19/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Erosion Control Inspection Residential Failed 5/21/2021 5/21/2021 05/21/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
05/21/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/21/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. CLEAN ALL MUD FROM STREET
Footing Inspection - Residential Passed 5/25/2021 5/25/2021 05/25/2021
Misc
Resolved
05/25/2021
All Rough Inspection - Residential Failed 5/25/2021 5/25/2021 05/25/2021
Misc
Corrective Action Required
05/25/2021
**HAVE TRUSS PLANS ON SITE IF COVERED PORCH/DECK TRUSSES TO BE INSPECTED AT SAME TIME AS GARAGE PORTAL** **GARAGE PORTAL 5/25/21** -FASTEN TOP PLATE TO HEADER WITH TWO ROWS OF 16D SINKER NAILS AT 3" O.C. -HEADER TO JACK STUD STRAP REQ, SEE R602.10.6.4 -UNABLE TO DETERMINE HOLD DOWN STRAP EMBEDDED IN CONCRETE DUE TO SIDING COVER, REMOVE SIDING -UNABLE TO DETERMINE COMPLETE NAILING PATTERN OF SHEATHING TO FRAMING DUE TO SIDING COVER, REMOVE SIDING
Gas Service Inspection - Residential Passed 6/10/2021 6/10/2021 06/10/2021
All Rough Inspection - Residential Failed 6/29/2021 6/29/2021 06/29/2021
Misc
Corrective Action Required
05/25/2021
**HAVE TRUSS PLANS ON SITE IF COVERED PORCH/DECK TRUSSES TO BE INSPECTED AT SAME TIME AS GARAGE PORTAL** **GARAGE PORTAL 5/25/21** -FASTEN TOP PLATE TO HEADER WITH TWO ROWS OF 16D SINKER NAILS AT 3" O.C. -HEADER TO JACK STUD STRAP REQ, SEE R602.10.6.4 -UNABLE TO DETERMINE HOLD DOWN STRAP EMBEDDED IN CONCRETE DUE TO SIDING COVER, REMOVE SIDING -UNABLE TO DETERMINE COMPLETE NAILING PATTERN OF SHEATHING TO FRAMING DUE TO SIDING COVER, REMOVE SIDING **GARAGE PORTAL 6/29/21** **HAVE TRUSS PLANS ON SITE IF COVERED PORCH/DECK TRUSSES TO BE INSPECTED AT SAME TIME AS GARAGE PORTAL** -RESTORE GRAVEL FILTER AT DRIVE AND SILT FENCE AT PERIMETER AND CLEAN DEBRIS FROM STREETS BEFORE ANY FURTHER INSPECTION -NO ITEMS ADDRESSED FROM PREVIOUS INSPECITON -NO PLANS ON SITE -FASTEN TOP PLATE TO HEADER WITH TWO ROWS OF 16D SINKER NAILS AT 3" O.C. -HEADER TO JACK STUD STRAP REQ, SEE R602.10.6.4 -UNABLE TO DETERMINE HOLD DOWN STRAP EMBEDDED IN CONCRETE DUE TO SIDING COVER, REMOVE SIDING -UNABLE TO DETERMINE COMPLETE NAILING PATTERN OF SHEATHING TO FRAMING DUE TO SIDING COVER, REMOVE SIDING
All Rough Inspection - Residential Failed 7/2/2021 7/2/2021 07/02/2021
Misc
Corrective Action Required
06/29/2021
**CORRECTIONS FROM GARAGE PORTAL 5/25/21 REMAIN** -FASTEN TOP PLATE TO HEADER WITH TWO ROWS OF 16D SINKER NAILS AT 3" O.C. -HEADER TO JACK STUD STRAP REQ, SEE R602.10.6.4 -UNABLE TO DETERMINE HOLD DOWN STRAP EMBEDDED IN CONCRETE DUE TO SIDING COVER, REMOVE SIDING -UNABLE TO DETERMINE COMPLETE NAILING PATTERN OF SHEATHING TO FRAMING DUE TO SIDING COVER, REMOVE SIDING -Fireblock fur out in garage around DWV -Seal all top and bottom plate penetrations-see garage, 2nd floor Bed#2, bed#4 -seal all penetrations through air returns -(2) Overbored floor joists for DWV, R502.8.1 , above great room 1st floor, replace or submit engineer letter -Penetrations bored through floor joists must be min 2” apart, R502.8.1, (7) joists bored for pex water lines less than 2” apart, above kitchen and great room 1st floor, replace or submit engineer letter -add Joist hanger at sgl joist to header connection at great room East corner, over 4’ -All truss hangers per plans -Unable to inspect trusses at covered porch due to cover, remove lid to allow for inspection -(4) 1 3/4” x 9 1/4” lvl to bear on (5) 2x4 per plans at garage -(2) 1 3/4” x 9 1/4” lvl to bear on (3) 2x4 per plans -12” o.c. Nailing at all abutting and intersecting wall corners (braced walls) -Strap 2x6 to 2x4 top plates at 2nd floor stairs -Protection nail plates at NM 1 1/4” or less from end of stud - see bed #2 bath wall -Protection plate at DWV bath #2 -strap dbl top plates at bed #3 closet 2nd floor, less than 24” offset -Use approved fireblock materials per r302.11.1 at HVAC/B vent chase at bed #4 2nd floor -Provide proper bearing for tpl truss girder at master bed 2nd floor -Nail all truss hangers at tpl truss girder 2nd floor -(4) 2x4 stud pack at all girder truss bearing ends per plans -anchor all steel columns to floor in basement -Color code or label GEC at service panel -(3) 2x10 joists at basement stair header per plans -Nail all exterior sheathing per plans
All Rough Inspection - Residential Failed 7/12/2021 7/12/2021 07/12/2021
Misc
Corrective Action Required
07/02/2021
**7/12/21 - INSPECTION DENIED, CLEAN ALL MUD AND GRAVEL FROM STREET, MAINTAIN EROSION CONTROL, GRAVEL FILTER W/ 4" LIFT REQUIRED **CORRECTIONS FROM GARAGE PORTAL 5/25/21 REMAIN** -FASTEN TOP PLATE TO HEADER WITH TWO ROWS OF 16D SINKER NAILS AT 3" O.C. -HEADER TO JACK STUD STRAP REQ, SEE R602.10.6.4 -UNABLE TO DETERMINE HOLD DOWN STRAP EMBEDDED IN CONCRETE DUE TO SIDING COVER, REMOVE SIDING -UNABLE TO DETERMINE COMPLETE NAILING PATTERN OF SHEATHING TO FRAMING DUE TO SIDING COVER, REMOVE SIDING -Fireblock fur out in garage around DWV -Seal all top and bottom plate penetrations-see garage, 2nd floor Bed#2, bed#4 -seal all penetrations through air returns -(2) Overbored floor joists for DWV, R502.8.1 , above great room 1st floor, replace or submit engineer letter -Penetrations bored through floor joists must be min 2” apart, R502.8.1, (7) joists bored for pex water lines less than 2” apart, above kitchen and great room 1st floor, replace or submit engineer letter -add Joist hanger at sgl joist to header connection at great room East corner, over 4’ -All truss hangers per plans -Unable to inspect trusses at covered porch due to cover, remove lid to allow for inspection -(4) 1 3/4” x 9 1/4” lvl to bear on (5) 2x4 per plans at garage -(2) 1 3/4” x 9 1/4” lvl to bear on (3) 2x4 per plans -12” o.c. Nailing at all abutting and intersecting wall corners (braced walls) -Strap 2x6 to 2x4 top plates at 2nd floor stairs -Protection nail plates at NM 1 1/4” or less from end of stud - see bed #2 bath wall -Protection plate at DWV bath #2 -strap dbl top plates at bed #3 closet 2nd floor, less than 24” offset -Use approved fireblock materials per r302.11.1 at HVAC/B vent chase at bed #4 2nd floor -Provide proper bearing for tpl truss girder at master bed 2nd floor -Nail all truss hangers at tpl truss girder 2nd floor -(4) 2x4 stud pack at all girder truss bearing ends per plans -anchor all steel columns to floor in basement -Color code or label GEC at service panel -(3) 2x10 joists at basement stair header per plans -Nail all exterior sheathing per plans
Erosion Control Inspection Residential Failed 7/12/2021 7/12/2021 07/12/2021
DCM3 ESC REQUIRED 2 DAY
Resolved
07/12/2021
Misc
Corrective Action Required
07/12/2021
INSPECTION DENIED, CLEAN ALL MUD AND GRAVEL FROM STREET, MAINTAIN EROSION CONTROL, GRAVEL FILTER W/ 4" LIFT REQUIRED
All Rough Inspection - Residential Failed 7/26/2021 7/26/2021 07/26/2021
Misc
Corrective Action Required
07/12/2021
-seal all penetrations through air returns -(2) Overbored floor joists for DWV, R502.8.1 , above great room 1st floor, submit engineer letter on field fix -Penetrations bored through floor joists must be min 2” apart, R502.8.1, (7) joists bored for pex water lines less than 2” apart, above kitchen and great room 1st floor, submit engineer letter on field fix -All truss hangers per plans-covered patio -Strap 2x6 to 2x4 top plates at 2nd floor stairs -strap dbl top plates at bed #3 closet 2nd floor, less than 24” offset **OK TO INSULATE**
All Rough Inspection - Residential Passed 8/3/2021 8/3/2021 08/03/2021
Misc
Resolved
08/03/2021
Electrical Service Inspection Passed 9/10/2021 9/10/2021 09/10/2021
Water Service Inspection - R Partial 9/15/2021 (10:00) 9/15/2021 09/15/2021
Misc
Corrective Action Required
09/15/2021
PARTIAL INSPECTION ON PEX TO HOUSE ENTRANCE
Water Service Inspection - R Passed 9/15/2021 (1:00) 9/15/2021 09/15/2021
Misc
Resolved
09/15/2021
PARTIAL INSPECTION ON PEX TO HOUSE ENTRANCE
Driveway Inspection Passed 9/27/2021 9/27/2021 09/27/2021
Misc
Informational
09/27/2021
On Monday 9/27/2021 I performed a driveway inspection and pass the sub-grade to pour concrete
Occupancy Inspection - Codes Residential Failed 10/6/2021 10/6/2021 10/06/2021
Misc
Corrective Action Required
10/06/2021
Final grading and sod Repair unused siding bore by gas meter Seal all siding penetrations, seal along top of AC disconnect and meter can Label all dedicated receptacles in garage and unfinished basement as not GFCI protected Install lock and Secondary locking device on sliding door Secure hvac duct brackets in basement Dishwasher receptacle requires GFCI protection Secure exterior receptacle to box near AC Splash blocks at all downspout and sump pump discharge locations, min 36" distance from foundation
Occupancy Inspection - Codes Residential Not Ready 10/11/2021 10/11/2021 10/11/2021
Misc
Corrective Action Required
10/06/2021
Final grading and sod Repair unused siding bore by gas meter Seal all siding penetrations, seal along top of AC disconnect and meter can Label all dedicated receptacles in garage and unfinished basement as not GFCI protected Dishwasher receptacle requires GFCI protection Secure exterior receptacle to box near AC Splash blocks at all downspout and sump pump discharge locations, min 36" distance from foundation
Erosion Control Inspection Residential Failed 10/12/2021 10/12/2021 10/12/2021
Misc
Corrective Action Required
07/12/2021
10-12-21 RESTORE AND MAINTAIN EROSION CONTROL AT PERIMETER OF LOT AND CLEAN MUD AND SILT FFOM STREET AND STOM INLET IMMEDIATELY
Occupancy Inspection - Codes Residential Temporary C of O 10/12/2021 10/12/2021 10/12/2021
Misc
Corrective Action Required
10/11/2021
TCO UNTIL 11-9-21 10-12-21 RESTORE AND MAINTAIN EROSION CONTROL AT PERIMETER OF LOT AND CLEAN MUD AND DEBRIS FFOM STREET AND STOM INLET IMMEDIATELY Final grading and sod Splash blocks at all downspout and sump pump discharge locations, min 36" distance from foundation
Plot Plan Inspection Passed 10/27/2021 10/27/2021
Occupancy Inspection - Codes Residential Full C of O 10/27/2021 10/27/2021 10/27/2021
Misc
Resolved
10/27/2021
Documents & Images
Date Uploaded File Type Document Name
12/29/2020 Application Form Permit Application and License Tax Form
12/30/2020 Letter Codes Residential Plan Review
12/30/2020 Approved Plans Approved Drawings
12/30/2020 Approved Plans Approved Truss Layout, 2nd floor
12/30/2020 Approved Plans Approved Truss Layout 1st floor
12/30/2020 Approved Plans Approved Truss Package
12/30/2020 Plot Plan Approved Plot Plan
12/30/2020 Receipt Receipt for transaction:2020-008277
12/30/2020 Letter DS Building Permit
02/22/2021 Letter INSPECTION SUMMARY
02/22/2021 Letter INSPECTION SUMMARY
03/01/2021 Letter INSPECTION SUMMARY
03/09/2021 MN107 Footing Inspection
03/24/2021 Letter INSPECTION SUMMARY
05/19/2021 Letter INSPECTION SUMMARY
05/19/2021 Letter INSPECTION SUMMARY
05/21/2021 Letter INSPECTION SUMMARY
05/25/2021 Letter INSPECTION SUMMARY
05/25/2021 Letter INSPECTION SUMMARY
06/10/2021 Letter INSPECTION SUMMARY
06/29/2021 Letter INSPECTION SUMMARY
07/02/2021 Letter INSPECTION SUMMARY
07/12/2021 Letter INSPECTION SUMMARY
07/12/2021 Letter INSPECTION SUMMARY
07/26/2021 Letter INSPECTION SUMMARY
07/28/2021 MN107floorjoistsletter
08/03/2021 Letter INSPECTION SUMMARY
09/10/2021 Letter INSPECTION SUMMARY
09/15/2021 Letter INSPECTION SUMMARY
09/15/2021 Letter INSPECTION SUMMARY
09/27/2021 Letter INSPECTION SUMMARY
10/06/2021 Letter INSPECTION SUMMARY
10/11/2021 Letter INSPECTION SUMMARY
10/12/2021 Letter INSPECTION SUMMARY
10/12/2021 Letter Codes Temporary Certificate of Occupancy
10/27/2021 Letter Codes Final Certificate of Occupancy
10/27/2021 Letter Field Certificate of Occupancy
10/27/2021 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home