Permit Application Status

PRRES20201500


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20201500
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSS PACKAGE - FINISHED BASEMENT
06/05/2020
06/09/2020
12/16/2020
Locations
Contacts
CMH PARKS INC, Address:5000 CLAYTON RD  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
PERMITTING@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 06/10/2020 06/09/2020
Dylan Eppert
Planning Review (RES) Approved 06/11/2020 06/09/2020
Dylan Eppert
Residential Plan Review Approved 06/10/2020 06/09/2020
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $959.04 $959.04 Paid 06/09/2020
8331507-Sewer Connection Fee $360.00 $360.00 Paid 06/09/2020
Water Tap Fee $3,477.00 $3,477.00 Paid 06/09/2020
Water Meter Fee $425.02 $425.02 Paid 06/09/2020
Right of Way Permit Fee $80.00 $80.00 Paid 06/09/2020
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 06/09/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 7/8/2020 07/08/2020
Sewer Service Inspection - R Passed 8/31/2020 (2:15) 8/31/2020 08/31/2020
Water Service Inspection - R Passed 9/1/2020 (10:15) 9/1/2020 09/01/2020
Electrical Service Inspection Failed 9/28/2020 9/28/2020 09/28/2020
Misc
Corrective Action Required
09/28/2020
- color code grounding electrode conductor
Gas Piping Inspection - Residential Passed 9/28/2020 9/28/2020 09/28/2020
Gas Service Inspection - Residential Failed 9/28/2020 9/28/2020 09/28/2020
Misc
Corrective Action Required
09/28/2020
- Gas pressure at 7 psi, must maintain 10 psi for 15 minutes
All Rough Inspection - Residential Failed 9/28/2020 9/28/2020 09/28/2020
Misc
Corrective Action Required
09/28/2020
-Protection plate at pex for refrigerator in kitchen -Security blocking at back door, front door, basement -Structural straps at top plate,all exterior walls and interior load bearing walls bored 50% or more -Fireblock unused bore in bottom plate at shower -Fireblock deadspace bedroom #2 -2x4 laid flat at furred down 3’ or more in basement must be connected to floor joists to support ceiling load - bedroom #4 -color code grounding electrode conductor -SCH steel 40 3” column missing at pier location “A”, W8x10 steel beam, unfinished basement -Gas pressure at 7 psi, must maintain 10 psi for 15 minutes
Electrical Service Inspection Passed 9/30/2020 9/30/2020 09/30/2020
Misc
Resolved
09/30/2020
Gas Service Inspection - Residential Passed 9/30/2020 9/30/2020 09/30/2020
Misc
Resolved
09/30/2020
All Rough Inspection - Residential Failed 9/30/2020 9/30/2020 09/30/2020
Misc
Corrective Action Required
09/28/2020
-Security blocking at basement door OK TO INSULATE
All Rough Inspection - Residential Passed 10/1/2020 10/1/2020 10/01/2020
Misc
Resolved
10/01/2020
Driveway Inspection Passed 10/19/2020 (A.M.) 10/19/2020 10/19/2020
Misc
Informational
10/19/2020
On Monday, 10-19-2020. I performed a Driveway inspection that passed city standards.
Sidewalk Inspection Passed 10/19/2020 10/19/2020 10/19/2020
Misc
Informational
10/19/2020
On Monday, 10-19-2020. I performed a sidewalk inspection that passed city standard.
Underslab Plumbing Inspection - Residential Passed 10/30/2020 10/30/2020
Piers/Caissons Inspection - Residential Passed 12/11/2020
Miscellaneous Correction
Informational
12/11/2020
-Completed by third party 6/18/20
Deck Final Inspection - Residential Failed 12/11/2020
Miscellaneous Correction
Corrective Action Required
12/11/2020
-PROVIDE (2) BOLTS PER RIM/ POST CONNECTION -SUPPORT END JOIST AT HOUSE AT SOUTHEAST CORNER OF DECK
Occupancy Inspection - Codes Residential Failed 12/11/2020 12/11/2020 12/11/2020
Miscellaneous Correction
Corrective Action Required
12/11/2020
-
Miscellaneous Correction
Corrective Action Required
12/11/2020
-FINAL GRADE AND SOD -SPLASH BLOCKS AND SUMP DRAINAGE -OPEN ELECTRICAL BOX IN CEILING OF FAMILY ROOM -PROVIDE HIGH/LOW VENTILATION FOR COMBUSTION AIR -PROVIDE (2) BOLTS PER RIM/ POST CONNECTION -SUPPORT END JOIST AT HOUSE AT SOUTHEAST CORNER OF DECK -SEAL PENETRATION AT INTERSYSTEM BONDING BAR
Plot Plan Inspection Passed 12/16/2020 12/16/2020 12/16/2020
Occupancy Inspection - Codes Residential Full C of O 12/16/2020 12/16/2020 12/16/2020
Miscellaneous Correction
Resolved
12/16/2020
Miscellaneous Correction
Resolved
12/16/2020
Documents & Images
Date Uploaded File Type Document Name
06/05/2020 Application Form H3 #5 - PERMIT APPLICATION
06/05/2020 5 HAWTHORNE RIDGE ROOF LAYOUT
06/05/2020 LOT 5 FINAL
06/05/2020 H3 #05 - Somerset - Farm House - Sheets
06/05/2020 - H3 #5 - TRUSS DETAILS SEALED
06/09/2020 Specifications APPROVED TRUSS PACKAGE
06/09/2020 Drawing APPROVED TRUSS LAYOUT
06/09/2020 Plans APPROVED HOUSE PLANS
06/09/2020 Plans APPROVED Elevations
06/09/2020 Plot Plan APPROVED PLOT PLAN
06/09/2020 Receipt Receipt for transaction:2020-002805
06/09/2020 Letter DS Building Permit
07/07/2020 Engineer Report/Study Lot 5 Hawthorne Ridge -Footing Inspection
07/08/2020 Letter INSPECTION SUMMARY
08/31/2020 Letter INSPECTION SUMMARY
09/01/2020 Letter INSPECTION SUMMARY
09/28/2020 Letter INSPECTION SUMMARY
09/28/2020 Letter INSPECTION SUMMARY
09/28/2020 Letter INSPECTION SUMMARY
09/28/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
10/01/2020 Letter INSPECTION SUMMARY
10/28/2020 H3 5 waterproofing
10/30/2020 Letter doc08128720201028105813
10/30/2020 Letter Summit Homes Letter Head
10/30/2020 Letter INSPECTION SUMMARY
12/11/2020 Letter INSPECTION SUMMARY
12/11/2020 Letter INSPECTION SUMMARY
12/11/2020 Letter INSPECTION SUMMARY
12/11/2020 Letter INSPECTION SUMMARY
12/11/2020 Letter INSPECTION SUMMARY
12/16/2020 Letter INSPECTION SUMMARY
12/16/2020 Letter Field Certificate of Occupancy
12/16/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home